ADVANCED WARNING
SY ST EMS
Description:
The Apartment Module (AM) is a loop powered
addressable device that helps reduce the costly
consequences of an unwanted alarm
An occupant is able to silence a local audible warning,
activated by a local smoke detector, and allowing a
preset time to investigate the cause of the alarm. Local
smoke detectors can be connected directly to the AM
(conventional) or connected to the addressable loop
(addressable) and assigned to the AM.
The local smoke detector is self resetting and if the
smoke clears, then the system will return to normal. If
the smoke remains, then the local audible warning will
resound at the expiry of the preset timeout. A local
smoke detector will NOT cause a general fire alarm.
The fire system will go into general fire alarm (thus
calling the brigade) if:
Any thermal detector has gone into alarm
(conventional connected to the AM or addressable
connected to the addressable loop)
Any smoke detector in common areas has gone
into alarm
Any call point activated
ConfigManager
is
programmed
associations of AM's with the local smoke detectors
(conventional and addressable) and adjustment of the
"Investigation" period.
AM Features
Loop interface with Short Circuit Isolator (SCI)
On-board Hush Switch with integrated front panel
Fire LED (red) and external hush input
Indicators: Poll / SCI LED (green – behind cover),
Fault LED (yellow – behind cover)
100V Line output with EOL monitoring
Conventional Zone circuit with selectable EOL
MAN1570-2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Apartment Module
Installation Guide
to
identify
ADDRESS SWITCH
FAULT LED
POLL LED
EOL, EXT HUSH,
POLL SELECTION
SWITCH
ALARM LED
FAULT TESTING
1. SHORT/OPEN THE ZONE
2. REMOVE EACH EOL IN TURN
3. REMOVE THE 100V LINE IN
POLL/SCI FAULTS
1. OPEN THE LOOP
2. SHORT THE LOOP
Figure 1: Apartment Module general wiring
Installation:
Observe anti-static precautions at all times
1.
Two DIP switches are provided, SW2 for
addressing (8 way) and SW1 for module options
(4 way) as below.
DIP SW1
1
2 EOL
3 Ext. Hush
4 Poll
2.
Establish the operational criteria for the module
and configure the FACP software accordingly
3.
Remove the white face plate and set the
address and operational parameters via the dip
switches
4.
All cabling should be run into a general purpose
wall box and connected as per Figure 1
5.
the
The AM is then screwed to the wall box and
tested – replace the face plate once testing is
complete
Testing
1.
Prepare the most suitable situation for the
installation to test the AM then create a local
"alarm"
2.
The alarm indicator should illuminate when the
alarm is recognised by the AM
3.
Check the silence function, the configured
"Acknowledgement" and "Investigation" timing
4.
Introduce a fault condition eg 1. remove the "Ext.
Hush" EOL, 2. check short circuit isolation
operation.
N1236
Item Numbers: 226-0003
Name
Operational Parameters
Not used
Zone EOL
2 off:
EOL = 10uF
selection
(default setting)
2 on:
EOL = 6K2
Ext. HUSH
ON for monitoring the
Input
External Hush Input
Poll LED
ON for Poll LED operation
NOTES:
#1 SELECTED EOL MUST BE A APPLIED
EVEN IF THE FUNCTION IS UN-USED
-
100V LINE
TO SPEAKERS
+
-
I N
+
100V LINE
-
O UT
+
-
ZONE ( CONVENTIONAL DEVICES )
+
-
EXTERNAL "HUSH"
+
4K7
-
LOOP IN -VE
-
+
LOOP IN +VE
+
ZONE ( CONVENTIONAL DEVICES ) EOL
10uF ( SW1 / 2 OFF )
6K2 ( SW1 / 2 ON )
EOL
47K
EOL
22K
Page 1
Need help?
Do you have a question about the 226-0003 and is the answer not in the manual?
Questions and answers