Table 20 – Altitude Compensation* Models 48TC08- - 14 (D, E, F, S, R, T)
ELEVATION
72k BTUH
Orifice
FT
M
Size
1
0 --- 2000
0 --- 610
33
1
2000
610
35
1
3000
914
35
1
4000
1219
36
1
5000
1524
36
2
6000
1829
37
2
7000
2134
38
2
8000
2438
38
9000
2743
†40
10000
3048
†41
11000
3353
†42
12000
3658
†42
13000
3962
†43
14000
4267
†43
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
{ Not included in kit. May be purchased separately through dealer.
ORIFICE
ACC. KIT PN
1
XX
CRLPELEV001A00
2
XX
CRLPELEV002A00
3
XX
CRLPELEV003A00
4
XX
CRLPELEV004A00
Table 21 – Altitude Compensation* Models 48TC08- - 14 (D, E, F, S, R, T)
ELEVATION
72k BTUH
Orifice
FT
M
Size
4
0 --- 2000
0 --- 610
51
4
2000
610
51
4
3000
914
52
4
4000
1219
52
4
5000
1524
52
4
6000
1829
52
4
7000
2134
53
4
8000
2438
53
4
9000
2743
53
4
10000
3048
54
4
11000
3353
54
4
12000
3658
54
4
13000
3962
55
4
14000
4267
55
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
{ Not included in kit. May be purchased separately through dealer.
ORIFICE
ACC. KIT PN
1
XX
CRLPELEV001A00
2
XX
CRLPELEV002A00
3
XX
CRLPELEV003A00
4
XX
CRLPELEV004A00
NATURAL GAS
125k BTUH
Input
Orifice
Input
Orifice
(btu/hr)
Size
(btu/hr)
Size
1
72,000
31
125,000
32
1
66,240
32
115,000
33
1
63,360
32
110,000
35
1
60,480
33
105,000
35
1
57,600
33
100,000
35
1
54,720
35
95,000
36
1
51,840
35
90,000
36
1
48,960
36
85,000
36
2
46,080
37
80,000
37
2
43,200
38
75,000
38
2
40,320
39
70,000
†40
37,440
†41
65,000
†40
34,560
†42
60,000
†41
31,680
†43
55,000
†41
PROPANE GAS
125k BTUH
Input
Orifice
Input
Orifice
(btu/hr)
Size
(btu/hr)
Size
3
72,000
49
125,000
50
3
66,240
50
115,000
51
3
63,360
50
110,000
51
3
60,480
50
105,000
51
4
57,600
51
100,000
51
4
54,720
51
95,000
52
4
51,840
51
90,000
52
4
48,960
52
85,000
52
4
46,080
52
80,000
53
4
43,200
52
75,000
53
4
40,320
53
70,000
53
4
37,440
53
65,000
53
4
34,560
54
60,000
53
4
31,680
54
55,000
55
NOMINAL HEAT INPUT
150k BTUH
180k BTUH
Input
Orifice
Input
(btu/hr)
Size
(btu/hr)
1
1
150,000
31
180,000
1
1
138,000
32
165,600
1
1
132,000
32
158,400
1
1
126,000
33
151,200
1
1
120,000
33
144,000
1
1
114,000
33
136,800
1
1
108,000
35
129,600
1
1
102,000
36
122,400
2
2
96,000
37
115,200
2
2
90,000
38
108,000
2
84,000
39
100,800
78,000
†41
93,600
72,000
†42
86,400
66,000
†43
79,200
NOMINAL HEAT INPUT
150k BTUH
180k BTUH
Input
Orifice
Input
(btu/hr)
Size
(btu/hr)
3
3
150,000
48
180,000
4
3
138,000
49
165,600
4
3
132,000
49
158,400
4
3
126,000
49
151,200
4
3
120,000
50
144,000
4
3
114,000
50
136,800
4
3
108,000
50
129,600
4
4
102,000
51
122,400
4
4
96,000
51
115,200
4
4
90,000
52
108,000
4
4
84,000
52
100,800
4
4
78,000
53
93,600
4
4
72,000
53
86,400
4
4
66,000
54
79,200
57
224k BTUH
250k BTUH
Orifice
Input
Orifice
Input
Size
(btu/hr)
Size
(btu/hr)
1
31
224,000
†30
250,000
1
32
206,080
†30
230,000
1
1
32
197,120
31
220,000
1
1
33
188,160
31
210,000
1
1
33
179,200
31
200,000
1
1
33
170,240
31
190,000
1
1
35
161,280
32
180,000
1
1
36
152,320
33
170,000
2
1
37
143,360
33
160,000
2
1
38
134,400
35
150,000
2
1
39
125,440
36
140,000
2
†41
116,480
37
130,000
2
†42
107,520
38
120,000
†43
98,560
†40
110,000
224k BTUH
250k BTUH
Orifice
Input
Orifice
Input
Size
(btu/hr)
Size
(btu/hr)
3
3
48
224,000
46
250,000
3
3
49
206,080
47
230,000
3
3
49
197,120
47
220,000
3
3
49
188,160
48
210,000
3
3
50
179,200
48
200,000
3
3
50
170,240
48
190,000
3
3
50
161,280
49
180,000
4
3
51
152,320
49
170,000
4
3
51
143,360
50
160,000
4
3
52
134,400
50
150,000
4
4
52
125,440
51
140,000
4
4
53
116,480
51
130,000
4
4
53
107,520
52
120,000
4
4
54
98,560
53
110,000

Advertisement