BRS09HPL1IA
Split Air Conditioner
Thank you for choosing our product.
For proper operation, please read and keep this manual carefully.
If you have lost the Owner's Manual, please contact the local agent or visit
www.borealintl.com or sent email to borealsales@borealintl.com for electronic version.

Advertisement

Table of Contents
loading

Summary of Contents for Boreal brisa BRS09HPL1IA

  • Page 1 BRS09HPL1IA Split Air Conditioner Thank you for choosing our product. For proper operation, please read and keep this manual carefully. If you have lost the Owner’s Manual, please contact the local agent or visit www.borealintl.com or sent email to borealsales@borealintl.com for electronic version.
  • Page 2 BRS09HPL1IA...
  • Page 3: Table Of Contents

    Content Operation Notices Precautions......................1 Parts name ......................9 Screen Operation Guide Buttons on remote controller ................11 Introduction for icons on display screen .............. 11 Introduction for buttons on remote controller ............12 Function introduction for combination buttons .............18 Operation guide ....................19 Replacement of batteries in remote controller .............19 Emergency operation ..................
  • Page 4 Explanation of Symbols Indicates a hazardous situation that, if not avoided, will DANGER result in death or serious injury. Indicates a hazardous situation that, if not avoided, could WARNING result in death or serious injury. Indicates a hazardous situation that, if not avoided, may CAUTION result in minor or moderate injury.
  • Page 5: Precautions

    Precautions WARNING Operation and Maintenance This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  • Page 6 Precautions WARNING Maintenance must be performed by qualified professionals. Otherwise, it may cause personal injury or damage. Do not repair air conditioner by yourself. It may cause electric shock or damage. Please contact dealer when you need to repair air conditioner. Do not extend fingers or objects into air inlet or air outlet.
  • Page 7 Precautions WARNING Attachment Installation must be performed by qualified professionals. Otherwise, it may cause personal injury or damage. Must follow the electric safety regulations when installing the unit. According to the local safety regulations, use qualified power supply circuit and circuit break. Do install the circuit break.
  • Page 8 Precautions WARNING Do not put through the power before finishing installation. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
  • Page 9 Precautions WARNING For the air conditioner with plug, the plug should be reachable after finishing installation. For the air conditioner without plug, an circuit break must be installed in the line. If you need to relocate the air conditioner to another place, only the qualified person can perform the work.
  • Page 10 Precautions FCC STATEMENT (1) this device may not cause harmful interference, and (2) this device must accept any interference received,including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
  • Page 11 Precautions IC STATEMENT This device complies with Industry Canada licence- exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
  • Page 12 Precautions IC STATEMENT antennes utilisées pour cet émetteur doivent être installées et doivent fonctionner à au moins 20 cm de distance des utilisateurs et ne doivent pas être placées près d’autres antennes ou émetteurs ou fonctionner avec ceux-ci. Les installateurs doivent s’assurer qu’une distance de 20 cm sépare l’appareil (à...
  • Page 13: Parts Name

    Parts Name Indoor Unit air inlet panel aux.button horizontal louver air outlet remote controller (Display content or position may be different from above graphics, please refer to actual products) NOTICE: Actual product may be different from above graphics, please refer to actual products.
  • Page 14 Parts name Display For some models: temp. For some models: indicator heating cooling power receiver indicator indicator indicator window display cooling indicator receiver power window indicator heating temp. drying display drying indicator indicator indicator indicator For some models: For some models: drying indicator heating...
  • Page 15: Buttons On Remote Controller

    Buttons on remote controller ON/OFF button MODE button FAN button TURBO button ▲/ button button button T-ON / T-OFF button I FEEL button CLOCK button SLEEP button WiFi button button LIGHT button TEMP button Introduction for icons on display screen Set fan speed fan speed.
  • Page 16: Introduction For Buttons On Remote Controller

    Introduction for buttons on remote controller Note: ● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
  • Page 17 Introduction for buttons on remote controller Note: ● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor ambient temperature). ● Set temperature range from remote controller: 16~30℃ (61-86°F); Fan speed: auto, low speed, medium speed, high speed.
  • Page 18 Introduction for buttons on remote controller auto mode) ● When setting T-ON, T-OFF or CLOCK, press "▲" or " " button to adjust time. (Refer to CLOCK, T-ON, T-OFF buttons) When setting T-ON, T-OFF or CLOCK press "▲" or " "...
  • Page 19 Introduction for buttons on remote controller T-ON / T-OFF button ● T-ON button "T-ON" button can set the time for timer on. After pressing this button, " " icon disappears and the word "ON" on remote controller blinks. Press "▲" or "...
  • Page 20 Introduction for buttons on remote controller CLOCK button Press this button to set clock time. " " icon on remote controller will blink. Press "▲" or " " button within 5s to set clock time. Each pressing of "▲" or " "...
  • Page 21 Introduction for buttons on remote controller LIGHT button Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on display light. " " icon is displayed. TEMP button By pressing this button, you can see indoor set temperature, indoor ambient temp- erature or outdoor ambient temperature on indoor unit’s display.
  • Page 22: Function Introduction For Combination Buttons

    Function introduction for combination buttons Energy-saving function Under cooling mode, press "TEMP" and " CLOCK" buttons simultaneously to start up or turn off energy-saving function. When energy-saving function is started up, "SE" will be shown on remote controller, and air conditioner will adjust the set temperature automatically according to ex-factory setting to reach to the best energy-saving effect.
  • Page 23: Operation Guide

    Operation guide After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT. Press "▲" or " " button to set your required temperature. (Temperature can’t be adjusted under auto mode).
  • Page 24: Emergency Operation

    Emergency operation If remote controller is lost or damaged, please use aux. button to turn on or turn off the air conditioner. The operation in details is as below: air conditioner. When the air conditioner is turned on, it will operate under auto mode.
  • Page 25 Clean and maintenance Open panel Pull out the panel to a certain ● Use dust catcher or water to the water (below 45℃ ) to clean it, and then put it in a shady and cool place to dry. panel cover tightly. WARNING operation environment, clean frequency can be increased.
  • Page 26 Clean and maintenance NOTICE: Checking before use-season 1. Check whether air inlets and air outlets are blocked. 2. Check whether circuit break, plug and socket are in good condition. 4. Check whether drainage pipe is damaged. NOTICE: Checking after use-season 1.
  • Page 27: Malfunction Analysis

    Malfunction analysis General phenomenon analysis Please check below items before asking for maintenance. If the malfunction still Phenomenon Check items Solution ● Whether it's interfered severely ● Pull out the plug. Reinsert (such as static electricity, stable the plug after about 3min, and voltage)? then turn on the unit again.
  • Page 28 Malfunction analysis Phenomenon Check items Solution ● Power failure? ● Wait until power recovery. ● Is plug loose? ● Reinsert the plug. ● Circuit break trips off or ● Ask professional to replace fuse is burnt out? circuit break or fuse. Air condit- ●...
  • Page 29 Malfunction analysis Phenomenon Check items Solution ● Whether there’s odour source, ● Eliminate the odour source. Odours are such as furniture and cigarette, emitted ● Clean the filte . etc. ● Whether there’s interference, ● Disconnect power, put back Air conditioner such as thunder, wireless power, and then turn on the operates nor-...
  • Page 30 Malfunction analysis Error Code ● When air conditioner status is abnormal, temperature indicator on indoor unit will ation of error code. Error code Troubleshooting It can be eliminated after restarting the unit. If not, please It can be eliminated after restarting the unit. If not, please It can be eliminated after restarting the unit.
  • Page 31: Installation Dimension Diagram

    Installation dimension diagram Space to the wall At least 15cm At least 15cm Space to the wall...
  • Page 32: Safety Precautions For Installing And Relocating The Unit

    Safety precautions for installing and relocating the unit To ensure safety, please be mindful of the following precautions. Warning When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant. Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in injury.
  • Page 33: Tools For Installation

    Tools for installation 1 Level meter 2 Screw driver 3 Impact drill 4 Drill head 5 Pipe expander 6 Torque wrench 7 Open-end wrench 8 Pipe cutter 9 Leakage detector 10 Vacuum pump 11 Pressure meter 12 Universal meter 13 Inner hexagon spanner 14 Measuring tape Note: ●...
  • Page 34: Requirements For Electric Connection

    Requirements for electric connection Safety precaution 1. Must follow the electric safety regulations when installing the unit. 2. According to the local safety regulations, use qualified power supply circuit and circuit break. Make sure the power supply matches with the requirement of air conditioner. Unstable power supply or incorrect wiring or malfunction.
  • Page 35: Installation Of Indoor Unit

    Installation of indoor unit Step one: choosing installation location rm it with the client. Step two: install wall-mounting frame Hang the wall-mounting frame on the wall; adjust it in horizontal position with the plastic expansion particles in the holes. 3. Fix the wall-mounting frame on the wall with tapping screws and then check if the frame is firmly installed by pulling the frame.If the plastic expansion particle is loose, please drill another fixing hole nearby.
  • Page 36 Installation of indoor unit Indoor outdoor Note: ● Pay attention to dust prevention and take relevant safety measures when opening the hole. 5-10° Φ70/Φ55 Step four: outlet pipe 1. The pipe can be led out in the When select leading out the pipe direction of right, rear right, left or from left or right, please cut off the rear left.
  • Page 37 Installation of indoor unit Hex nut diameter Tightening torque (N . m) open-end wrench Φ 6 15~20 Φ 9.52 30~40 union nut Φ 12 45~55 pipe Φ 16 60~65 torque wrench Φ 19 70~75 indoor pipe 4. Wrap the indoor pipe and joint of con- nection pipe with insulating pipe, and then wrap it with tape.
  • Page 38 Installation of indoor unit 2. Make the power connection wire go cable-cross through the cable-cross hole at the back hole of indoor unit and then pull it out from the front side. power connection wire 3. Remove the wire clip; connect the power connection wire to the wiring terminal with wire clip.
  • Page 39 Installation of indoor unit Step eight: bind up pipe 1. Bind up the connection pipe, power drain hose connection pipe band cord and drain hose with the band. indoor and outdoor power cord indoor unit pipe indoor power cord liquid pipe Bind them evenly.
  • Page 40: Check After Installation

    Check after installation Items to be checked Possible malfunction The unit may drop, shake or emit noise. Have you done the refrigerant leakage test? (heating) capacity. It may cause condensation and water dripping. It may cause condensation and water Is water drained well? dripping.
  • Page 41 Configuration of connection pipe 1. Standard length of connection pipe ● 5m, 7.5m, 8m. 2.Min. length of connection pipe is 3m. 3.Max. length of connection pipe. Max. length of connection pipe Unit: m Max. length Max. length Cooling Cooling of connec- of connec- capacity capacity...
  • Page 42 Configuration of connection pipe Additional refrigerant charging amount for R22, R407C, R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe(mm) Gas pipe(mm) Cooling only(g/m) Cooling and heating(g/m) Φ6 Φ9.52 or Φ12 Φ6 or Φ9.52 Φ16 or Φ19 Φ12 Φ19 or Φ22.2 Φ16...
  • Page 43: Pipe Expanding Method

    Pipe expanding method Note: Improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe according to the following steps: A: Cut the pipe E: Expand the port ● Expand the port with expander. the distance of indoor unit and hard outdoor unit.
  • Page 44 Boreal International a Watsco Inc. subsidiary borealsales@borealintl.com, www.borealintl.com, 66129935316 10300 NW 19th St. #105, Doral, FL 33172, 786-621-8250...