Lennox Allied Air A95UH1D Installation Instructions Manual page 17

Warm air gas furnace
Table of Contents

Advertisement

Exhaust Piping
See Figure 25 and Figure 26
1.
In areas where piping penetrates joist or interior walls,
hole must be large enough to allow clearance on all
sides of pipe through center of hole using a hanger.
2.
When furnace is installed in a residence where unit
is shut down for an extended period of time, such
as a vacation home, make provisions for draining
condensate collection from trap and lines.
3.
Route piping to outside of structure. Continue with
installation following instructions given in piping
termination section.
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
Vent Piping Guidelines
This gas furnace can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE: In non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from
outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing - Size pipe according to
Table 4 and Table 5A through Table 6C. Table 4 lists the
minimum vent pipe lengths permitted. Table 5A and Table
5B list the maximum pipe lengths permitted for A93UH1D
and 92G1UH-P. Table 6A through Table 6C list the maximum
pipe lengths permitted for A95UH1D and 95G1UH-P.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to Table 8.
In some applications which permit the use of several
different sizes of vent pipe, a combination vent pipe may
be used. Contact Allied Air Technical Service for assistance
in sizing vent pipe in these applications.
507270-03
CAUTION
CAUTION
NOTE: It is acceptable to use any pipe size which fits
within the guidelines allowed in Table 5A and Table 5B,
and Table 6A through Table 6C.
NOTE: The exhaust collar on all models is sized to
accommodate 2" Schedule 40 vent pipe. In horizontal
applications, transition to exhaust pipe larger than 2" must
be made in vertical runs of the pipe. A 2" elbow must be
added before the pipe is transitioned to any size larger
than 2". This elbow must be added to the elbow count
used to determine acceptable vent lengths. Contact the
Application Department for more information concerning
sizing of vent systems which include multiple pipe sizes.
Capacity
045, 070, 090, 110
135**
* Any approved termination may be added to the minimum
length listed.
** This gas furnace must have 3" to 2" reducing elbow
(supplied or field replacement Canadian kit) installed directly
into unit flue collar.
Table 4. Minimum Vent Pipe Lengths
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
Issue 1917
Figure 23.
Min. Vent Length*
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
IMPORTANT
Page 17 of 60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents