Blower Performance - Lennox Allied Air A96UH2E Installation Instructions Manual

Warm air gas furnace
Hide thumbs Also See for Allied Air A96UH2E:
Table of Contents

Advertisement

Blower Performance

A96UH2E030B08 Performance (Less Filter)
External
Static
High
Pressure
in. w.g.
cfm
0.00
1025
0.10
985
0.20
955
0.30
915
0.40
875
0.50
830
0.60
800
0.70
765
0.80
715
A96UH2E045B12 Performance (Less Filter)
External
Static
High
Pressure
in. w.g.
cfm
0.00
1345
0.10
1305
0.20
1290
0.30
1275
0.40
1220
0.50
1215
0.60
1190
0.70
N/A
0.80
N/A
Page 50 of 60
Air Volume / Watts at Various Blower Speeds
Medium-High
Watts
cfm
Watts
122
935
97
129
910
104
139
875
114
145
830
120
155
790
130
161
750
136
172
700
146
181
650
150
187
615
159
Air Volume / Watts at Various Blower Speeds
Medium-High
Watts
cfm
Watts
340
1255
245
345
1225
250
360
1190
260
370
1150
270
385
1120
280
390
1090
290
395
1060
300
N/A
1015
300
N/A
1000
310
Medium
cfm
Watts
855
76
820
82
770
87
730
96
680
101
635
110
580
115
550
124
500
127
Medium
cfm
Watts
1150
185
1105
200
1080
205
1045
215
1015
220
980
230
950
240
900
250
870
260
Issue 2128
Medium-Low
cfm
Watts
cfm
820
76
765
775
72
700
640
62
575
575
67
375
530
74
330
470
79
260
420
82
210
385
90
180
325
94
135
Medium-Low
cfm
Watts
cfm
895
105
845
855
110
810
825
120
780
785
125
720
735
135
690
705
140
635
650
150
600
620
155
555
580
160
520
Low
Watts
69
63
52
40
47
51
47
51
52
Low
Watts
95
95
105
110
120
125
135
140
145
507581-04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: