BAPI AD592 Termination And Troubleshooting

Room sensors sensor termination and troubleshooting

Advertisement

Quick Links

9557_ins_592_Room
Termination
BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger
gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes.
Do NOT run this device's wiring in the same conduit as AC power wiring of NEC class1 or NEC class 2, NEC class 3 or with
wiring used to supply highly inductive loads such as motors, contactors and relays.
BAPI's tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the
same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your BAPI representative.
BA/592 (2 Wire) sensors
1. Install a 10K 0.1% resistor between the sensor
Output (terminal 2) and Ground (GND).
2. Make sure that the resistor is connected
between the analog input (A.I.) point and
Ground.
3. Connect the sensor Output to the A.I. point.
4. Connect the 5 to 30 VDC wire last.
SENS
+5 to +30 VDC
R1
1
Sensor output (1mV/°K)
2
3
10K 0.1%
R2
GND(Common)
Offsetting
All BA592 sensors will have the following information provided on a label:
Therm Reading_______
The actual temperature reading
according to a thermometer that is
certified traceable to recognized
standards by the National Institute of
Standards and Technology (NIST).
To correct the Sensor Reading, simply add the offset value to the sensor reading so that it equals the thermometer
reading.
e.g.
Therm Reading 74.6
Correction: Add (+1.6) °F to the sensor for an accurate reading: 73 + 1.6 = 74.6°F
e.g.
Therm Reading 75.4
Correction: Add (-1.6) °F to the sensor for an accurate reading: 77.2 + (-1.8) = 75.4°F
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
AD592/592-10K Room Sensors
[To Power of Controller or Supply]
[To Analog Input of Controller]
[To GND(Common) of Controller]
Sensor Reading ______
The temperature reading according to
the AD592 sensor, using the output
in either mA or mV and converting
the output to a Fahrenheit tempera-
ture.
Sensor Reading 73.0
Offset +1.6
Sensor Reading 77.2
Offset -1.8
Specifications subject to change without notice.
Sensor Termination and Troubleshooting
BAPI does not recommend wiring the sensor with
power applied as accidental arcing may damage
the product and will void the warranty
BA/592-10K (3 Wire) sensors
1. All BA/592-10K (3 wire) sensors have a 10K
0.1% resistor built in.
2. Connect the Ground (terminal 3) wire first.
3. Connect the Sensor Output wire second.
4. Connect the 5 to 30 VDC wire last.
SENS
+5 to +30 VDC
R1
1
2
Sensor output (1mV/°K)
3
R2
GND(Common)
Offset_______
The difference between the
Thermometer Reading and the
Sensor Reading
rev.
3/14/05
[To Power of Controller or Supply]
[To Analog Input of Controller]
[To GND(Common) of Controller]

Advertisement

loading

Summary of Contents for BAPI AD592

  • Page 1 BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your BAPI representative.
  • Page 2 AD592/592-10K Room Sensors Sensor Termination and Troubleshooting 9557_ins_592_Room rev. 3/14/05 Troubleshooting Possible Solutions: Problems: Confirm the input is set up correctly in the front Temperature sensor in front end software is end software reading high Check wiring for proper termination Verify the “Sensor”...

This manual is also suitable for:

Ad592-10kBa/592Ba/592-10k