PERMACONN
PM1030 Includes DI300
Installation Manual
RDCCO Pty Ltd
Unit 3/9 - 11 Stubbs Street
Rydalmere NSW 2116
Telephone: 02 9352 1777
Web: www.permaconn.com

Advertisement

Table of Contents
loading

Summary of Contents for Permaconn PM1030

  • Page 1 PERMACONN PM1030 Includes DI300 Installation Manual RDCCO Pty Ltd Unit 3/9 - 11 Stubbs Street Rydalmere NSW 2116 Telephone: 02 9352 1777 Web: www.permaconn.com...
  • Page 2: Table Of Contents

    Programming the Alarm panel / Battery Charging............6 .........7 Input and Output / Defaulting the Permaconn PM1030 DI300 Powered by Panel – PM1030 Powered Independent Supply....PM1030 V2 and DI300 Powered by Panel / Transmission Delay Times..LED Status Indicators PM1030..............LED Status Indicators DI300 ................10 Final Commissioning Check List..............11...
  • Page 3: Introduction / Features Of The Pm1030

    Introduction The PERMACONN system provides two-way communication between supervised premises and the monitoring centre. The Permaconn PM1030 is a versatile state of the art microprocessor based 3G and NextG security communicator. This unit can interface with a range of alarm panels using RS485 / RS232 and Contact ID. It also has four (4) Inputs and three (3) Outputs.
  • Page 4: Installation Procedure

    Installation Procedure Place the Permaconn PM1030 unit in the exact position where you intend to install it.  Screw the antenna onto SMA connector.  Unit is by default set up to operate with the DI300. If any other module is required remove ...
  • Page 5: Connecting The Di300 / Connecting The Alarm Panel

    If PSTN is primary you must test the following:  Trigger the ‘tamper’ input on the Permaconn PM1030 unit. Verify with the monitoring centre that a tamper was received with the correct CID account number PM1030 Manual March 2019 v2.2...
  • Page 6: Programming The Alarm Panel / Battery Charging

    Disable telephone line monitoring feature from the panel. Battery Charging A dedicated 14.5V power supply is required if you want to charge a battery  Do not fit a battery if power is being supplied by the Alarm panel.  PM1030 Manual March 2019 v2.2 RDCCO_2143_E_IN...
  • Page 7: Input And Output / Defaulting The Permaconn Pm1030

    Output is open collector 12V, 50mA switching negative, for heavier loads a relay  must be used. The outputs can be Opened, Closed or Pulsed remotely using the Permaconn Atlas  web platform. Ensure there is a common negative between PM1030 and the device being ...
  • Page 8: Pm1030 V2 And Di300 Powered By Panel / Transmission Delay Times

    PM1030 V2 and DI300 Powered by Panel Do not fit a battery when PM1030  is powered by the alarm panel Transmission Delay Times Tamper input status message are transmitted immediately.  Message originating from the panel are forwarded immediately.
  • Page 9: Led Status Indicators Pm1030

    Normal operation Unit is c No connection to network On * maconn network. Unit is registered on Permaconn Network but has ONLINE/GPOL No connection to network Blinking not received message with account details from the Unit is registered on Perm ONLINE/ alarm panel.
  • Page 10: Led Status Indicators Di300

    Unit is faulty Blinking Indicates connectivity between the PM1030 and the DI300 Link Indicates fault with wiring between PM1030 and DI300. Check blue and white wire Indicates that there is no line voltage on the incoming telephone (from the ex- change).
  • Page 11: Final Commissioning Check List

    Generate event from alarm panel. Verify with monitoring centre that correct CID account and event received via PSTN. Test Permaconn PM1030 communication Trigger the tamper input on Permaconn PM1030. Trigger outputs and inputs Verify with monitoring centre that correct CID account and event received.
  • Page 12: Pm1030 Contact Id Event Table

    955 & Dialer Interface Lead Fail – Issue with dialer lead between Permaconn unit and the alarm panel. Serial Interface Fail – Issue with Permaconn unit serial connection to the alarm panel. IP path poll fail. 3G path poll fail.
  • Page 13: Specifications Pm1030 V2

    DCV > 5V for more than 8 seconds Response Dialler Interface: < 10 sec typical (seizing line to receiving ACK) < 50 sec absolute maximum Serial Interface: < 2 sec typical (dispatch to receiving ACK) < 50 sec absolute maximum RDCCO_2143_E_IN PM1030 Manual March 2019 v2.2...
  • Page 14: Standards Compliance / Liability / Warning

    12V/1.2AH sealed lead acid battery. The unit must only be operated with the supplied antenna. Install the Permaconn PM1030 in a location that no person[s] is closer than 200 mm to the antenna at all times. Australian Standard AS2201 requires regular service by qualified and licensed techni- cians and regular testing.
  • Page 15: Notes

    NOTES ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… ………………………………………………………………………………………………… RDCCO_2143_E_IN PM1030 Manual March 2019 v2.2...