Step 4 - Position the base sections around the
mat and fit AE-C corner pieces. Drill pilot
holes through each corner piece and holes in
the base sections if applicable. Remove base
sections / corner pieces and drill and plug the
floor. Refit base sections and corner pieces
and secure in position with the screws
provided, as shown in figure 8. Ensure the
cable exits neatly through the slot(s) in the
base section.
Figure 8 - AE-13 & AE-C Installation
NOTE: MAT SENSORS MUST BE
FITTED WITH THE LABEL SIDE UP.
Step 5 - Route the cable(s) to the interface.
The cable(s) should exit from the edging as
close to the interface position as possible.
The cables should be protected in suitable
conduit between the edging and the interface.
Protect any edges over which the cables pass
with grommet strip or similar.
Step 6 - Fit the cover extrusion of the edging
using suitable self-tapping screws.
4.2.4 ELECTRICAL INSTALLATION
The CKP/Solo mat is supplied with 2 x 4 core
cables 0.5m long, each cable is fitted with an
M12 plug. The connections to the mat sensor
are shown in Figure 9.
One cable is used for the d.c. supply, and one
cable is used for the Volt-Free Safety Outputs.
NOTE: In order to achieve EN954-1
Category 3 safety integrity, the outputs must
be wired as two separate channels to a suitable
control capable of monitoring them for
equivalence.
+24V
0V
O/P
1
O/P
2
CKP/Solo SENSOR
Figure 9 - CKP/Solo Connection Details
BROWN
1
CABLE B
BLUE
3
BROWN
1
WHITE
2
CABLE A
BLUE
3
BLACK
4
2
3
1
4
11