Honeywell Ex-Or MLS2000DALIMBW Installation And Commissioning Instructions page 3

Mls digital mid-bay & hi-bay luminaire controllers

Advertisement

Commissioning Detectors using the HP2000
It is important that the HP2000 be held perpendicular and at a distance of between 0.5m and 2m from the detector.
1. Switch on HP2000 by pressing the red power button.
2. Point HP2000 at detector and press the DOWNLOAD button. The HP2000 will confirm the product's identity,
and call up the correct menu of parameters and their current settings. It will also show the ballast type and the
duration (shown in hours) remaining on the 100-hour burn-in.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting
options for each shown. (See Tips below.)
4. When options for all parameters have been selected, point the HP2000 at the detector and press the UPLOAD
button. The luminaire(s) will switch off briefly during the programming process and the HP2000 shows DATA
OK to confirm operation.
5. After a short period of inactivity (default 5 minutes), the HP2000 hibernates retaining the most recent settings.
Tips
i)
Where there are only two options such as ON/OFF, a double click of the OK button toggles between them.
ii)
Where there are multiple options, a double click of the OK button recalls a list of all options for that parameter.
Use the UP, DOWN and OK buttons to select.
iii) Use the OK button to go forward (through the menus) without displaying help pages.
iv) Press UPLOAD at any time to transfer all current settings from the handset to the product.
Please refer to HP2000 instructions for comprehensive commissioning details.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory:
Parameter
Power Up
Response
Off Delay
On Sensitivity
Bus Connect
Zones 1-4
Corridor 1-2: Begin
Corridor 1-2: End
Global 1-2 Rx
Start Lamps
Entry Scene
Bright Out
Dimming
Lamp Max
Fade to Off
When Vacant
Set-Point High
Set-Point Low
100 Hour Burn-In
Options
On / Off
Auto, Manual/Bus, Manual
1 min - 96 hrs, 10-sec (walk-test), Disabled
0-100
Yes / No
Address 1-100
1-100 Building Address Span
1-100 Building Address Span
Yes / No
Max / Min
1-6
Yes / No
Reg 50%-Reg100%
10%-100%
Yes / No
10 Exit Scenes
0-1023
0-1023
Additional feature accessible under Utilities:
See Application Note: AN4028
Default
On
Auto
20 mins
100
Yes
-- (no zone)
-- (no zone)
-- (no zone)
No
Max
1
No
Reg 100%
100%
No
Off
1023
1023
0 hr

Advertisement

loading