Gardner Denver L55 User And Service Manual page 34

Screw air compressor
Table of Contents

Advertisement

To establish an electrical connection, proceed as
follows:
Route the supply cable (-1 - Fig. 12) through the cable
gland on the switch cabinet and tighten screws.
Connect the supply line to the connecting terminals as
shown in the circuit diagram.
Recommended supply cable cross-sections and fuses for multi-wire cables or three current-carrying
conductors in raceway based on 86 °F ambient temperature
Compressor type
Supply
voltage
60-Hz-compressors
L55
L55RS
L75,
L80
L75RS
32
Installed
Main supply
nominal motor
power
[V]
[hp]
200
230
75
460
575
460
75
200
230
100
460
575
460
100
Fig. 12
Fuse(s) protection
1)
type
(slow-blow fuse)
class J
[Amps]
Double
150
Double
150
Single
125
Single
90
Single
125
Double
225
Double
200
Single
175
Single
150
Single
175
Line cross section
conductor rated
140°F
167°F
194°F
AWG4/0
AWG2/0
AWG1/0
AWG3/0
AWG1/0
AWG1
AWG2/0
AWG1
AWG2
AWG1
AWG2
AWG3
AWG2/0 AWG1/0
AWG1
-
MCM250
AWG4/0
MCM250
AWG4/0
AWG3/0
AWG4/0
AWG3/0
AWG2/0
AWG3/0
AWG1/0
AWG1
AWG4/0 AWG3/0 AWG2/0
August 20, 2018