• Controller Hardware - C This guide contains installation and applications information for the model 2700 Automation Controller. The Model 2700 has a flexible plug-in architecture, which supports a variety of modules, and comes in three sizes: • The 2700-5, containing slots for five modules and a plug-in CPU •...
NOTES: 1. Not mutually inclusive. 2. Rev.2.26 and greater supports the Model 2206 Stepping Motor Control Module only. Model 2700 Controller Installation Guide Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Dimensions and Mounting Instructions for the Model 2700 The Model 2700 Automation Controller is provided with mounting ears, allowing them to be easily mounted to a flat surface (for example, an NEMA-rated electrical enclosure) with four mounting bolts. You should follow the guidelines described in this installation guide to ensure a successful design.
Inserting Modules into the Controller The Model 2700 controller accepts a variety of plug-in modules. You insert the modules into one of the slots of your Model 2700 controller. Any combination of modules, subject to system limits, may be inserted into the controller. The plug-in CPU has its own slot and is not counted as part of the total number of slots in a controller.
Page 6
The Model 2699 bracket requires an additional 2 in of clearance for the front of the controller. Control Technology Corporation Control Technology Corporation proprietary, Reproduction or distribution forbidden. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Model 2700 Power Connections Connecting AC Power The Model 2700 contains an internal power supply which provides two mutually- isolated voltages (+5 VDC and +24 VDC) for the operation of the controller. Also included are two LED indicators located on the CPU for these voltages and a power ON- OFF switch.
NOTE: Do not make any external connections to either the +5 V power supply or its common, as an increased susceptibility to electrical noise may result. Control Technology Corporation Control Technology Corporation proprietary, Reproduction or distribution forbidden. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Do not connect an external supply with a voltage rating other than +24 V to this connec- tor, as potential incompatibilities may exist with the modules installed in the controller. Consult CTC for further information. Model 2700 Controller Installation Guide Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Status Light Description The status light on the Model 2700 can indicate one of the following conditions: • Software fault: A periodic flashing light on the 2701E CPU indicates a program software fault. This means the controller was unable to execute due to an applica- tion problem within the program.
RS-232 port or on an Ethernet network. Using the RS-232 Port for Controller Communications The RS-232 port on your Model 2700 controller provides a means for both programming and data communications via a personal computer using Quickstep. The controller is also equipped with a built-in protocol allowing direct computer communications with the controller’s RS-232 port.
Page 12
Comm Common Yellow DB9-232 DB-25 Connector Modular Jack Green Common Black Comm Comm Yellow Common DB25-232 Control Technology Corporation Control Technology Corporation proprietary, Reproduction or distribution forbidden. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Setting-up Controller Communications Using Ethernet for Controller Communications Your 2700 controller can access an ethernet network for controller-computer communi- cations using a Model 2217 or 2717 Ethernet Module. The 2217 or 2717 contains both 10/100BaseT connections, as well as two RS-232 ports.
Using the Real Time Clock Feature The Model 2700 controller includes a real-time clock (RTC) feature. The clock is preset at the factory to Eastern Standard Time. Using the following registers, you can read the current time or set the clock to your local time: •...