Maintenance; Recommended Maintenance - ABB GOE(2) Installation And Commissioning Manual

Transformer bushing
Table of Contents

Advertisement

6 Maintenance

6.1 Recommended maintenance

General
The bushings are maintenance free, no regular maintenance is necessary.
DANGER!
Risk of electrocution!
Do not go near the bushing while it is energized, or ungrounded. High voltages can kill you.
Make sure that the bushing is de-energized, and grounded before you do work on it.
NOTE!
For bushings with oil-level indicator, it is recommended to check the oil-level at plant supervision.
Cleaning of the insulator surface
If the insulator is exposed to very high pollution, it can be necessary to clean the surface. Remove the
pollution with a moist cloth, or a low pressure water jet. If necessary, put isopropyl alcohol on the cloth.
DANGER!
1,1,1 -Trichloroethane or Methyl-chloride are not recommended as detergents, because they are
dangerous to persons and the environment.
CAUTION!
Do not wash the insulators with a high pressure water jet. This can cause damage to the joints in
the insulator, and between the insulator and metal parts.
CAUTION!
Do not apply alcohol on the porcelain joints.
Installation and commissioning guide
1ZSC000563-ACF EN, REV. A, 2020-06-25
57

Advertisement

Table of Contents
loading

Table of Contents