5. Removal of Fan Motor

Procedure
Step
1
Cut the clamps at 2
locations.
2
Remove the 2 lower
screws first.
3
Then, remove the 2
upper screws.
4
Remove the fan motor.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
2
1
Fan motor
Removal of Fan Motor
Preparation
Remove the electrical box
according to the "Removal of
Electrical Box".
(R9630)
Be sure to remove the lower
screws first. If the top screws
are removed first, the fan
motor may tilt down or fall
and cause injury because its
center of gravity is shifted to
the front.
(R6442)
When reassembling, make
sure that the wire harness is
facing downward.
Harness
(R6443)
Points