LG LT-H242PLE0 Installation Manual page 17

Type : ceiling cassette
Table of Contents

Advertisement

Connecting Pipes to the Indoor Unit
• Preparation of Piping
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the
following procedure.
1) Cut the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor and
the outdoor unit.
• Cut the pipes a little longer than measured
distance.
• Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
• Completely remove all burrs from the cut cross
section of pipe/tube.
• Put the end of the copper tube/pipe to downward
direction as you remove burrs in order to avoid
to let burrs drop in the tubing.
3) Putting nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube having
completed burr removal.
(Not possible to put them on after flaring work)
4) Flaring work
• Carry out flaring work using flaring tool as shown
below.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
5) Check
n Compare the flared work with figure below.
n If flare is noted to be defective, cut off the flared
section and do flaring work again.
• If the piping and the drain hose are in common
direction bundle the piping and the drain hose
together by wrapping them with vinyl tape.
Copper
tube
Bar
Copper pipe
A
mm
Smooth all round
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
1.9~2.1
Even length
all round
Connection pipe
Vinyl tape (wide)
Slanted Uneven Rough
90°
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
"A"
Clamp handle
Red arrow mark
Inside is shining without scratches
= Improper flaring =
Inclined
Surface
Cracked Uneven
damaged
Wrap with vinyl tape
Connecting cable
Vinyl tape(narrow)
Installation Manual 17
Installation
Handle
Yoke
Cone
thickness
Indoor unit pipe
Pipe

Advertisement

Table of Contents
loading

Table of Contents