elsner elektronik KNX TH-UP basic Installation And Adjustment

elsner elektronik KNX TH-UP basic Installation And Adjustment

Thermal hygrometer
Hide thumbs Also See for KNX TH-UP basic:

Advertisement

Quick Links

EN
KNX TH-UP basic
Thermal hygrometer
Article numbers 70362 (white), 70363 (aluminium), 70364 (anthracite)
Installation and Adjustment

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KNX TH-UP basic and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for elsner elektronik KNX TH-UP basic

  • Page 1 KNX TH-UP basic Thermal hygrometer Article numbers 70362 (white), 70363 (aluminium), 70364 (anthracite) Installation and Adjustment...
  • Page 2: Table Of Contents

    4.8. Absolute humidity ....................35 4.9. Comfort field ......................35 4.10.Variable comparator ....................36 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany KNX TH-UP basic • from software version 3.1, ETS version 3.1 Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 3 4.11.2. AND logic connection inputs ..............39 4.11.3. Connection inputs of the OR logic ............. 40 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany KNX TH-UP basic • from software version 3.1, ETS version 3.1 Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 4 Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
  • Page 5 Clarification of signs...
  • Page 6: Description

    (composite results) together with its own data. The KNX TH-UP basic provides six switched outputs whose threshold values can be adjusted. Switched outputs and other communication objects may be linked via AND and OR logic gates.
  • Page 7: Deliverables

    Temperature resolution 0.1°C Temperature accuracy* ±0,8°C at -25…-10°C ±0,5°C at -10...+65°C ±0,6°C at +65...+80°C Humidity measuring range 0…100% RH Humidity resolution 0.1% Indoor sensor KNX TH-UP basic • Software version 3.0 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 8: Measuring Accuracy

    After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately. Indoor sensor KNX TH-UP basic • Software version 3.0 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 9: Installation Position

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
  • Page 10: Rear View Sensor Plate With Connection

    After the bus voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received or sent via the bus. Indoor sensor KNX TH-UP basic • Software version 3.0 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 11 Installation and start-up Indoor sensor KNX TH-UP basic • Software version 3.0 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 12: Transfer Protocol

    Switching output block Temp. threshold value 2: Absolute Input/Output 9,001 C R W T value Temp. threshold value 2: (1:+ | 0:-) Input 1,002 Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 13 C R W T TR_1_ Target value, Standby cooling Input 1,002 (1:+ | 0:-) TR_1_ Target value, Eco heating Input/Output 9,001 C R W T Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 14 Humidity threshold value 1: Switch- Input 7,005 ing delay from 1 to 0 Humidity threshold value 1: Switch- Output 1,001 C R T ing output Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 15 Coolant temp.: Switching delay from Input 7,005 1 to 0 Coolant temp.: Switching output Output 1,001 C R T Coolant temp.: Switching output Input 1,002 block Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 16 Output 5,010 C R T AND logic 2: Block Input 1,002 AND logic 3: 1-bit switching output Output 1,002 C R T Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 17 Output 5,010 C R T OR logic 4: Block Input 1,002 OR logic 5: 1-bit switching output Output 1,002 C R T Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 18 Input 1,002 Logic input 13 Input 1,002 Logic input 14 Input 1,002 Logic input 15 Input 1,002 Logic input 16 Input 1,002 Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 19: Parameter Setting

    Use external reading Yes • No Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 20: Threshold Values: Temperature, Humidity

    Beforehand, enter how the threshold value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease. Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 21: Switching Output

    None • 1 s • 2 s • 5 s • 10 s • … • 2 h (when delay is not set using objects) Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 22: Block

    For an adequate regulation of the indoor temperature, comfort, standby, eco and build- ing protection modes may be used. Comfort when present, Standby during short absences, Eco as a night-time mode and Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 23 • on change and periodically cycle 5 s • ... • 5 min • … • 2 h for periodical transmission only Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 24: General Set Point Values

    (do not save) or remain saved even after voltage recovery (and pro- gramming). This also applies to a comfort extension. Grading for set point changes 1… 50; 10 (in 0.1 °C) Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 25: Set Point Comfort

    1st communication Min. object value heating/cooling (in 0.1 -300…800; 160 °C) Max. object value heating/cooling (in 0.1 -300…800; 280 °C) Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 26: Eco Set Point

    If the 2nd level has a common variable, this is also where you determine the control mode of the 2nd level. Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 27: Heating Control Level 1/2

    The reset time shows how quickly the controls react to deviations from the set point value. In case of a short reset time, the controls react with a fast increase of the varia- Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 28 In case of a common variable for heating and cooling, 0 is always transmitted as a fixed value. Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 29: Cooling Control Level 1/2

    PI control with control parameters: This setting allows individual input of the parameters for PI control. Control type • PI control Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 30 2-point-rule (only level 2): The 2-point-rule is used for systems which are only set to ON or OFF. Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 31: Humidity Pi Control

    Use Humidity control Yes • No General control Sensor KNX TH-UP basic can be used to control one- or two-stage dehumidification or combined humidification/dehumidification. Type of control • One-stage dehumidification • Two-stage dehumidification •...
  • Page 32: Controller Target Value

    Basically, an air humidity range is given in which the target value can be changed (object value limit). Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 33: Dehumidification And/Or Humidification

    On release, the control variable follows the rule again. When blocked, the variable shall • not be sent • send a specific value Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 34: Dewpoint Temperature

    Value (in %) 0...100 ((if a value is sent for an 8-bit object)) 4.7. Dewpoint temperature The Sensor KNX TH-UP basic calculates the dewpoint temperature and can output the value to the bus. Use dewpoint temperature No • Yes Dewpoint temperature sent •...
  • Page 35: Switching Output

    "Switching output sends" (see "Switching output") Switching output sends on change • Do not send message • Send switching output status Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 36: Absolute Humidity

    4.9. Comfort field The Sensor KNX TH-UP basic can send a message to the bus if the limits of the com- fort field are exceeded. In this way, it is for example possible to monitor compliance with DIN 1946 (standard values) or even to define your own comfort field.
  • Page 37: Variable Comparator

    • the current value (with 2 seconds release delay) • the current value after receipt of an object Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 38: Logic

    = 1  object B value Setting dependent on "type of object" if logic = 0  object B value Setting dependent on "type of object" Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 39: Block

    • Status object/s send/s on change of logic and receipt of object send value for current logic status and periodically (no selection) Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 40: And Logic Connection Inputs

    Switching output temperature 4 inverted Temp. control status changeover switching object Temp. control status changeover switching object inverted Temp. control status heating 1 Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 41: Connection Inputs Of The Or Logic

    AND logic output 6 inverted AND logic output 7 AND logic output 7 inverted AND logic output 8 AND logic output 8 inverted Sensor KNX TH-UP basic • Software version 3.1 and higher Version: 06.03.2017 • Technical changes and errors excepted.
  • Page 42 Elsner Elektronik GmbH Control and Automation Technology Sohlengrund 16 75395 Ostelsheim Phone +49(0)70 33/ 30945-0 info@elsner-elektronik.de Germany +49 (0) 70 33/ 30945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...