SUN2000-(5KTL, 6KTL)-M0
User Manual
Alarm ID
Alarm
Name
2072
Transient
AC
Overvolta
ge
Contact your dealer or Huawei technical support if the measures listed in the Troubleshooting
Suggestion column have been taken but the fault persists.
Issue 03 (2019-07-19)
Alarm
Possible Cause
Severity
Major
Cause ID = 1
The inverter detects that the
phase voltage exceeds the
transient AC overvoltage
protection threshold.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestion
1. Check whether the grid
connection voltage exceeds the
upper threshold. If yes, contact
the local power operator.
2. If you have confirmed that the
grid-tied voltage exceeds the
upper threshold and have
obtained the consent of the local
power operator, modify the
overvoltage protection threshold
through the mobile phone app,
SmartLogger, or NMS.
3. Check whether the peak power
grid voltage exceeds the upper
threshold.
7 Maintenance