Space requirements
Final location
8
Delivery / Handling
Make sure a clear space equal to at least the width of the equipment units is available
on the operator side; this is the minimum space necessary for installation, operation
and maintenance (see the table below).
Footprint of space required for installation, operation and maintenance:
Fan section
Cooling coil, heating coil, KVS
Filter section up to KG 96
In back-to-back configurations with side-by-side units, leave clearances as stated above
on both sides for installation, operation and maintenance.
Install units that require a siphon (scrubber, humidifier, cooling coil, plate-type heat
exchanger, mist eliminator) in such a way as to ensure correct installation and operation
of the siphon (make adequate provision for the foundation height).
It is advisable to install a waterproof foundation for units with humidifiers and/ or cooling
coils installed above rooms containing moisture-sensitive equipment (e.g. IT rooms, etc.).
Always install KG air-handling units in rooms where frost cannot occur.
Note
If the occurrence of frost at the final location cannot be ruled out, adopt suitable measures
to prevent water-containing components from freezing. If an outside thermostat is
installed ensure it is adequately insulated to prevent the air-handling unit from shutting
down inadvertently (see frost protection measures, page 25).
KGW air conditioning units are designed to be installed outdoors.
0.8 x appliance width
1
x appliance width + 250 mm
1
x appliance width
from KG 130
0.5 x appliance width
KG Top
3062049_201610