Indoor Unit Installation
1.

Installing the mounting plate.

• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring
points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
Use tape measure
as shown.
Position the end
of a tape measure
at
.
Through the wall
hole φ70mm
2.
Boring a wall hole and installing wall embedded pipe.
• For walls containing metal frame or metal board, be sure to use a wall
embedded pipe and wall cover in the feed-through hole to prevent possible
heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to prevent
water leakage.
1) Bore a feed-through hole of 70mm in the wall so it has a down slope toward
the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole
gap with putty.
■English
Recommended mounting
plate retention spots.
(5 spots in all)
115
φ70
61
149
Drain hose position
* The removed pipe port cover can be
kept in the mounting plate pocket.
Place a leveler on raised tab.
450
Bilt size: M10
Bilt size: M10
Liquid pipe end
Gas pipe end
278.5
50
Keep here the piece cut out
from the unit for piping.
800
Removed pipe
port cover
A
Mounting plate
103
400
200
φ70
175.5
60.5
unit: mm
Inside
Outside
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
Caulking
8