INSTALLATION MANUAL
R-410A
OUTDOOR SPLIT-SYSTEM
AIR CONDITIONING
MODELS: 18 SEER - CZH / AC8B / AL8B SERIES
MODELS: 16 SEER - CZF / AC6B / AL6B SERIES
2 TO 5 TONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Installation with Required Clearances . . . . . . . . . . . . . . 3
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Communications Harness Connection . . . . . . . . . . . . . . . . . . . 6
Air Handler or Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
(with AC control) - PSC Air Handler . . . . . . . . . . . . . . . . . . . . . . . 8
(with AC control) - VS Air Handler . . . . . . . . . . . . . . . . . . . . . . . 9
(with AC control) - Modulating Furnace . . . . . . . . . . . . . . . . . . . 10
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . 18
TEST Input Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operational Mode Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the highest sales volume evaporator plus 15 feet of
field supplied lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some system
combinations, elevation differences, or total line lengths. See tabular
data sheet provided in unit literature packet for charge requirements.
Refer to Application Data covering "General Piping Recommendations
and Refrigerant Line Length" (Part Number 247077).

TABLE OF CONTENTS

SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . 17
AC CONTROL BOARD FUNCTIONALITY . . . . . . . . . . . . . 18
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
LIST OF FIGURES
Two Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . 11
Two Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . 12
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 14
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single Stage Wiring Diagram (2 - 4 Ton) . . . . . . . . . . . . . . . . 22
Single Stage Wiring Diagram (5 Ton) . . . . . . . . . . . . . . . . . . . . 23
Two Stage Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LIST OF TABLES
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operational Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Sensor or Switch Fault Codes . . . . . . . . . . . . . . . . . . . . . . . 20
Wiring Related Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . 20
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
®
835965-UIM-B-0413

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 18 Seer-CZH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls 18 Seer-CZH Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-410A OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: 18 SEER - CZH / AC8B / AL8B SERIES ® MODELS: 16 SEER - CZF / AC6B / AL6B SERIES 2 TO 5 TONS TABLE OF CONTENTS GENERAL ........1 SYSTEM CHARGE .
  • Page 2: Unit Installation

    Never leave a suc- observed to ensure a system that will give maximum performance tion-line drier in the system longer than 50 hours of run time. with minimum service. Johnson Controls Unitary Products...
  • Page 3: Typical Installation With Required Clearances

    Never install a suction-line filter drier in the liquid line of an R-410A system. Failure to follow this warning can cause a fire, injury or Filter-Drier death. Apply with Models Source 1 Part No. 029-22195-000 Johnson Controls Unitary Products...
  • Page 4: Tubing Hanger

    Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorp- tion. Johnson Controls Unitary Products...
  • Page 5: Evacuation

    The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. In all cases, mount the TXV bulb after vapor line is brazed and has had sufficient time to cool. Johnson Controls Unitary Products...
  • Page 6: Communications Harness Connection

    NOTICE To eliminate erratic operation, seal the hole in the wall at the ther- mostat with Pergamum or equivalent to prevent air drafts affecting the operation of the thermostat. Johnson Controls Unitary Products...
  • Page 7: Communicating Ac With Communicating

    FIGURE 7: Communicating AC with Communicating Air Handler or municating Control. Refer to the Touch Screen Communicating Control Furnace owner’s manual for this procedure. Manual setting of the airflow on the ID equipment is not necessary with the Touch Screen Communicating Control. Johnson Controls Unitary Products...
  • Page 8: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Psc Air Handler

    IRU : DQG : HOHFWULF WR ³(/(&´ KHDW VWDJLQJ RSWLRQV 3DUW 1XPEHUV 3DUW 1XPEHU 3DUW 1XPEHU /HJDF\ 6+8    FIGURE 9: Thermostat Wiring – Single Stage Air Conditioner (with AC control) – PSC Air Handler Johnson Controls Unitary Products...
  • Page 9: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Vs Air Handler

    -XPSHU  PXVW EH VHW IRU : DQG : HOHFWULF WR ³(/(&´ KHDW VWDJLQJ RSWLRQV 3DUW 1XPEHU 3DUW 1XPEHU 3DUW 1XPEHU 6+8   FIGURE 10: Thermostat Wiring – Single Stage Air Conditioner (with AC control) – VS Air Handler Johnson Controls Unitary Products...
  • Page 10: Thermostat Wiring - Single Stage Air Conditioner (With Ac Control) - Modulating Furnace

    LI KXPLGLVWDW LV WR EH XVHG -XPSHU  PXVW EH VHW WR ³*$6´ 3DUW 1XPEHU¶V 3DUW 1XPEHU 3DUW 1XPEHU  6+8   FIGURE 11: Thermostat Wiring – Single Stage Air Conditioner (with AC control) – Modulating Furnace Johnson Controls Unitary Products...
  • Page 11: Thermostat Chart - Two Stage Ac - Two Stage Variable Speed Furnaces

    Multistage Conventional Thermostat Installer Setup 15-Compressor Protection -must be set to 5 Part Numbers: Part Number: SAP = Legacy S1-2HU16700124 265904 = 031-09169 FIGURE 12: Thermostat Chart - Two Stage AC – Two Stage Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 12: Thermostat Chart - Two Stage Ac - Two Stage Variable Speed Furnaces

    Connection of the “C” batteries Terminal, 24-Volt Common, is optional when used with batteries Part Numbers: Part Number: SAP = Legacy S1-2HU16700124 265904 = 031-09169 FIGURE 13: Thermostat Chart - Two Stage AC – Two Stage Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 13: Thermostat Chart - Two Stage Ac

    Multistage Conventional Multistage Conventional Thermostat Installer Setup 15-Compressor Protection -must be set to 5 Part Numbers: SAP = Legacy Part Number: 171334 = 031-09153 S1-2HU16700124 FIGURE 14: Thermostat Chart - Two Stage AC – Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 14: Thermostat Chart - Two Stage Ac

    Connection of the “C” terminal, 24-Volt common is optional when used with batteries Part Numbers: SAP = Legacy Part Number: 171334 = 031-09153 S1-2HU16700124 FIGURE 15: Thermostat Chart - Two Stage AC – Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 15: Thermostat Chart - Two Stage Ac - Variable Speed Furnaces

    Multistage Conventional Multistage Conventional Thermostat Installer Setup 15-Compressor Protection -must be set to 5 Part Numbers: Part Number: SAP = Legacy S1-2HU16700124 159481 = 031-09157 FIGURE 16: Thermostat Chart - Two Stage AC – Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 16: Thermostat Chart - Two Stage Ac - Variable Speed Furnaces

    W1 and W2 electric batteries heat staging options. Part Numbers: Part Number: SAP = Legacy S1-2HU16700124 159481 = 031-09157 FIGURE 17: Thermostat Chart - Two Stage AC – Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 17: R-410A Saturation Properties

    Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means. 2. The outdoor fan motor is permanently lubricated and does not require periodic oiling. Johnson Controls Unitary Products...
  • Page 18: Test Input Functionality

    The control includes a TEST input connector that can be used for vari- tion (Y1 input signal energized). ous testing functions during installation and service. Table 2 summa- rizes the behavior of the control when the two TEST pins are connected. Johnson Controls Unitary Products...
  • Page 19: Operational Mode Display

    Control normal operation – with active communication present System is active and presently communicating successfully. 0.1 sec OFF Control powered – without active communication present System has 24 VAC present and the microprocessor is active. 2s ON / 2s OFF Johnson Controls Unitary Products...
  • Page 20: Operational Fault Codes

    (24 VAC) must be cycled to the control for the control to sense TABLE 8: Wiring Related Fault Codes the wiring change and clear the lockout condition. LED1 Flash LED2 Flash Description Code (Red) Code (Green) Compressor contactor miswire Y2 present without Y1 Johnson Controls Unitary Products...
  • Page 21 It is used to display outdoor temperature to the home owner via the communicating thermostat. • Has no effect on operation. • Not required for operation, but a fault code will be displayed when sensor is not connected or if sensor is shorted. Johnson Controls Unitary Products...
  • Page 22: Wiring Diagram

    835965-UIM-B-0413 SECTION IX: WIRING DIAGRAM FIGURE 18: Single Stage Wiring Diagram (2 - 4 Ton) Johnson Controls Unitary Products...
  • Page 23: Single Stage Wiring Diagram (5 Ton)

    835965-UIM-B-0413 FIGURE 19: Single Stage Wiring Diagram (5 Ton) Johnson Controls Unitary Products...
  • Page 24 835965-UIM-B-0413 NOTES Johnson Controls Unitary Products...
  • Page 25: Start Up Sheet

    Venting system properly sized, within the limitations of the charts in the installation instructions. Intake Size # of 90 Degree Ells # 0f 45 Degree Ells Length Exhaust Size # of 90 Degree Ells # 0f 45 Degree Ells Length Continued on next Page Johnson Controls Unitary Products...
  • Page 26 Explain the importance of regular filter replacement and equipment maintenance Comments Section Subject to change without notice. Published in U.S.A. 835965-UIM-B-0413 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 835965-UIM-A-0112 Johnson Controls Unitary Products 5005 York Drive...

Table of Contents