Motor Speed
Correct heating and cooling motor speeds MUST be used for proper operation. Refer to the Blower Speed/Static Operation Table
below for correct cooling speed and for minimum allowable heating speed.
BLOWER SPEED / STATIC OPERATION TABLE
MOTOR
UNIT
SPEED
HIGH
A*PA24A1
MEDIUM
LOW
HIGH
A*PA24B1
MEDIUM
LOW
HIGH
A*PB36A1
MEDIUM
LOW
HIGH
A*PC48A1
MEDIUM
A*PC48B1
LOW
A*PC60A1
HIGH
MEDIUM
LOW
*Specifications applicable to upflow and horizontal applications
Air flow shown at the following conditions:
• No heat elements in air handler
• Decrease CFM 1% for 5 kW, 7.5 kW, or 10 kW heat kits. Decrease CFM 2% for 15 kW or 20 kW heat kits
• 60 Hertz — 230 volts. Decrease CFM 6% for 208 volt operation
• Standard air handler filter.Dry coil airflow shown
RESISTANCE HEAT
STATIC PRESSURE (IN. WC) ACROSS
HEAT ELEMENT @ MAX. CFM
RESISTANCE
AUXILIARY HEAT STAGED
HEAT ONLY
WITH HEAT PUMP
15 kW @ 0.20"
10 kW @ 0.15"
15 kW @ 0.20"
5 kW @ 0.15"
10 kW @ 0.15"
N/A
15 kW @ 0.20"
10 kW @ 0.15"
15 kW @ 0.20"
5 kW @ 0.15"
10 kW @ 0.15"
N/A
20 kW @ 0.25"
10 kW @ 0.15"
20 kW @ 0.20"
10 kW @ 0.15"
20 kW @ 0.15"
N/A
*20 kW @ 0.60"
15 kW @ 0.45"
*20 kW @ 0.50"
15 kW @ 0.40"
*20 kW @ 0.40"
15 kW @ 0.40"
*20 kW @ 0.60"
15 kW @ 0.45"
*20 kW @ 0.50"
15 kW @ 0.40"
*20 kW @ 0.35"
15 kW @ 0.35"
60 Hz OPERATION
CFM @ EXTERNAL DUCT STATIC (IN. WC)
.2
.3
925
900
800
760
655
625
905
880
785
735
645
615
1440
1350
1300
1220
1160
1070
1680
1640
1440
1410
1240
1220
2230
2105
1950
1930
1360
1350
11
.4
.5
850
795
690
745
670
N/A
600
N/A
N/A
830
780
680
730
655
N/A
590
N/A
N/A
1260
1180
1040
1050
940
860
950
880
780
1590
1520
1430
1380
1340
1250
1190
1150
1100
1990
1895
1725
1840
1770
1590
1340
1185
1080
.6