I/O Terminals In I/O Unit - Service; To Replace A Terminal - Saab TankRadar G3 Service Manual

Monitoring and control system
Table of Contents

Advertisement

Figure 3-4
The automatic fuse
switch on the I/O
Terminal Main Block
turns off the power in
the I/O Unit.
G3 MaC Second edition, March 2000
3.5

I/O Terminals in I/O Unit - service

To replace a terminal

1
Identify the faulty terminal.
2
In the Saab TankRadar I/O Unit, turn off the power by
turning the automatic fuse switch on the I/O Terminal Main
Block to the off position.
3
Disconnect the connector (power and communication) from
the terminal.
4
Disconnect the cables from the cable terminal.
Note:
Make sure the cables are marked so you can re-connect
them.
5
Dismount the terminal from the rack.
Note:
Depending on where the terminal is located in the cabinet,
it is dismounted either by turning it upwards or down-
wards.
6
Bring out the replacement terminal and compare settings
with the old one. Check the address switches and the jump-
ers.
7
Put the old terminal in an ESD protection bag for transport
to Saab Marine Electronics.
8
Mount the replacement terminal.
9
Connect the cables to the cable terminal.