Download Print this page

M-system R30NCIE1 Instruction Manual

Network module (cc-link ie field network)
Hide thumbs Also See for R30NCIE1:

Advertisement

Quick Links

INSTRUCTION MANUAL
NETWORK MODULE
(CC-Link IE Field network)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network module ..................................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■ HOT SWAPPABLE MODULES
• It is possible to replace a module with the power supplied
provided that the module is replaced with one with the
same model number and installed in the same base slot.
• Be sure to replace a module when it is not communicating
with the host as it may affect the system. Note that re-
placing multiple modules at one time may greatly change
line voltage levels. We strongly recommend to replace
them one by one.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 10 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
R30NCIE1
EM-9020 Rev.3 P. 1 / 13

Advertisement

loading
Need help?

Need help?

Do you have a question about the R30NCIE1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for M-system R30NCIE1

  • Page 1 (CC-Link IE Field network) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ CONFORMITY WITH EU DIRECTIVES contents of the package you received as outlined below. • The equipment must be mounted inside the instrument If you have any problems or questions with the product, panel of a metal enclosure.
  • Page 2: Component Identification

    For example, to set station No. 115, set the SW for MSB to B and SW for LSB to 5. Do NOT set to D, E, F as they are not in use. EM-9020 Rev.3 P. 2 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Installation

    Lock Tab 3) Tighten the base fixing screw using a screwdriver (stem length: 70 mm/2.76” or more) (torque 0.5 N·m). Base Fixing Screw EM-9020 Rev.3 P. 3 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Terminal Connections

    CONNECTOR INTERNAL POWER Regarding CN1 and CN2 of RJ-45 connector for CC-Link IE Field network, there is no restriction for connection order. EM-9020 Rev.3 P. 4 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5 Slot 3 R3-DA32A Di16 points Di16 points Di16 points Slot 4 R3-DC32A Do16 points Slot 4 R3-DC32A Do16 points Do16 points Do16 points EM-9020 Rev.3 P. 5 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 R3 series extension slot 3 RX(n+2)F, RX(n+4)F, RX(n+6)F R3 series extension slot 16 Link devices other than the above are not in use. EM-9020 Rev.3 P. 6 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 16-bit binary data. Integer that engineering unit value (A) multiplied by 100 (for CLSE-R5, integer that engineering unit value (A) multiplied by 1000). EM-9020 Rev.3 P. 7 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8 Input 1 (Output 1) Input 2 (Output 2) Input 3 (Output 3) Input 16 (Output 16) 0 : OFF 1 : ON EM-9020 Rev.3 P. 8 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 9 2) From the main menu, select [Tool] ➞ [Register Profile]. 1. Click 3) Select the downloaded CSP+ file, and click [Register] to finish registration. 1. Click EM-9020 Rev.3 P. 9 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 10 3) From the menu tree of Project, select [Parameter] ➞ [Network Parameter], and double click [Ethernet/CC IE/MELSEC- NET] to open the [Network Parameter Ethernet/CC IE/MELSECNET] window. 1. Double click EM-9020 Rev.3 P. 10 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 11 If CSP+ of R30GCIE1 is not registered, select [General CC IE Field Module]. 4. Click 1. Drag 3. Input 2. Drop EM-9020 Rev.3 P. 11 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 12 7) Click [End] on the [MELSECNET/CC IE Ethernet Module Configuration] window. 1. Click 8) After having programmed as necessary, write parameters and programs to CPU unit. EM-9020 Rev.3 P. 12 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 13 3) If an error has occurred, the button such as [Module Error] is displayed. Click the button to display the details, and trou- bleshoot accordingly. 1. Click EM-9020 Rev.3 P. 13 / 13 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...