PM-PROGRESS Technical Documentation MULTIFUNCTION POWER METER Part Number:...
Page 2
For further information, please contact your CRE Technology distributor or the After-Sales Service Team. All CRE Technology products are delivered with one year warranty, and if necessary we will be happy to come on site for product commissioning or troubleshooting. The company also provide specific trainings on our products and softwares.
Page 3
Technical documentation history Date Version Comments 2011 Initial version. Added details about internal current connection. Dec. 2015 Typos. Documentations available on CRE Technology Web site: pmp-sales-documentation.pdf pmp-technical-documentation.pdf pmp-documentation-commerciale.pdf...
1 Inst allation and operating instruction PM-Progress is designed for accurate measurement and display of all major electrical and power quality parameters, in single-phase two wire, and three-phase three and four-wire system configurations. This manual provides all the necessary instructions to safely install and operate the instrument. For more information please contact your distributor.
The system setup screen will be displayed on the screen. Press the button to scroll down the menu until you see the CT primary setting screen. Press the button to enter the CT primary setting screen. The first digit should start flashing. ...
Reset: Reset cumulative energy and Demand measurements to zero. Communication parameters: For RS485 interface (optional), Modbus protocol Baud rate 2400/4800/9600/19200/38400 Parity none/odd/even Stop bits 1 (1 or 2 if parity is none) RS485 network address nnn – 3-digit number 1 to 247 Order –Norm/Rev indicates if the Modbus word order is normal or reversed.
Press button to select the desired parameter and enter the second level menu structure. If an item flashes, then it can be adjusted by keys. If not, there may be a further layer, e.g. Comms - Baud rate, before adjustment is possible. Press to select the lower layer.
1.5.2 Three phase, three wire Negative current inputs are internally connected together. Figure 2 - Three phase, three wire 1.5.3 Three phase, four wire Negative current inputs are internally connected together. Figure 3 - Three phase, four wire PMP 9 0020 B EN –Technical documentation...
1.5.4 Cut-out details Figure 4 – Case dimensions and Cut-out details The unit may be mounted in a panel of any thickness up to a maximum of 6 mm (0·25in). Leave enough space behind the instrument to allow for bends in the connection cables. As the front of panel enclosure conforms to IP52, it is protected from dripping water.
Page 12
Fusing This unit must be fitted with external fuses in voltage and auxiliary supply lines. Voltage input lines must be fused with a quick blow fuse 1 A maximum. Auxiliary supply lines must be fused with a slow blow fuse rated 1 A maximum.
A total maximum length of 3900 feet (1200 meters) is allowed for the RS485 network. A maximum of 32 electrical nodes can be connected, including the controller. The address of each PM-Progress can be set to any value between 1 and 247. Broadcast mode (address 0) is not supported.
1 stop bit if parity is used; 1 or 2 bits if no parity Data Coding All data values in the PM-Progress are transferred as 32 bits IEEE 754 floating point numbers, (input and output) therefore each PM-Progress value is transferred using two MODBUS Protocol registers. All register read requests and data write requests must specify an even number of registers.
Average line to line volts THD. Avail. Avail. Table 2 - PM-Progress input registers Notes: 1. The power factor has its sign adjusted to indicate the nature of the load: a positive value for a capacitive load, a negative value for an inductive load.
4X registers. Modbus Protocol Function Code 03 is used to read the parameter and Function Code 16 is used for write access. Write to only one parameter per message. 2.3.1 PM-progress MODBUS Protocol Holding Register Parameters Address...
Modbus Protocol transactions involving floating point numbers. It is perfectly feasible to change PM-Progress set-up using a general purpose Modbus Protocol master, but often easier to use the PM-Progress display or PM-Progress configuration software, especially for gaining password protected access.
Page 18
Once the required changes have been made to the protected parameters the password lock should be reapplied by following one of these actions: Allowing the password to timeout Writing any value to the Password Lock register Power cycling the instrument. PMP 9 0020 B EN –Technical documentation...
3 R5485 general information RS485 or EIA (Electronic Industries Association) RS485 is a balanced line, half-duplex transmission system allowing transmission distances up to 1.2 km. The following table summarizes the RS-485 Standard: Parameters Description Mode of Operation Differential Number of Drivers and Receivers 32 Drivers 32 Receivers Maximum Cable Length...
Figure 6 – Recommended wiring A and B terminals The A and B connections to the PM-Progress can be identified by the signals present on them while there is activity on the RS485 bus: Figure 7 – A and B terminal...
3.4 Troubleshooting Start with a simple network, one master and one slave. With PM-Progress this is easily achieved as the network can be left intact while individual instruments are disconnected by removing the RS485 connection from the rear of the instrument.
4 Maintenance and safety requirement 4.1 Maintenance In normal use, maintenance operations are pretty simple. As appropriate for service conditions, isolate electrical power, inspect the unit and remove any dust or other foreign material present. Periodically check all connections for screw tightness and make sure there is no corrosion, particularly if vibration is present. The front of the case should be wiped with a dry cloth only.