UTICA BOILERS UHSW Series Installation, Operation & Maintenance Manual page 36

Gas-fired hot water induced draft boilers
Table of Contents

Advertisement

STEP 3: Check spark ignition circuit.
!
WARNING
Electrical shock hazard. Ignition circuit generates
over 10,000 volts. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Disconnect ignition cable at SPARK terminal on module.
Energize module and listen for audible sparking noise.
When operating normally, there should be buzzing noise
turns on and off twice per second for duration of 1–7
seconds, depending on model.
STEP 4: Verify pilot and main burner light-off.
• Initiate call for heat. Turn thermostat above room
temperature. Ignition sequence may be delayed by
thermal purge until boiler water temperature is below
140°F (60°C)
• Watch pilot burner during ignition sequence.
— Verify ignition spark continues after pilot is lit.
— Verify pilot lights and spark stops, verify main
burner does not light.
• If so, ensure adequate flame current as follows.
— Turn off boiler at circuit breaker or fuse box.
— Clean flame rod with emery cloth.
— Verify electrical connections are clean and tight.
Replace damaged wire..
— Check for cracked ceramic insulator, which can
cause short to ground, and replace igniter-sensor if
necessary.
— At gas valve, disconnect main valve wire from MV
terminal.
— Turn on power and set thermostat to call for heat. Pilot
should light, main burner will remain off because main
valve actuator is disconnected.
— Check pilot flame. Verify it is blue, steady and
envelops 3/8 to 1/2 in. [10 to 13 mm] of flame rod.
Figure 19 for possible flame problems and causes.
— If necessary, adjust pilot flame by turning pilot. See
Figure 15, Page 26. adjustment screw on gas control
clockwise to decrease or counterclockwise to increase
pilot flame. Following adjustment, always replace pilot
adjustment cover screw and tighten firmly to assure
proper gas control operation. See Figure 14, Page 26.
— Set temperature below room set-point to end call for
heat.
APPENDIX A - CONTROL MODULE
• Recheck ignition sequence as follows.
— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace
— If main burner does not light or if main burner lights
Figure 19 - Pilot Flame
Correct Pilot Flame: 3/8 to 1/2 inch in flame.
See Figure 15, Page 26.
36
module.
and system locks out, check module, ground wire and
gas control as described in troubleshooting table. See
Table 9, Page 35.
PN 240012689 Rev. A [05/15/2019]