Download Print this page

Siemens MKB-1 Installation Instructions page 2

Annunciator/keypad module

Advertisement

To Select Supervision
Use Switch S1-SW5 on the ANN-1 to select or
deselect supervision of the MKB-1. If your ANN-1
has a switch with position 1 indicated on the
lefthand side, ignore the printing on the switch.
SW1 on S1 is at the extreme right-hand side of
S1, regardless of any other marking.
To set for supervision:
S1-SW5 = Closed (ON)
To set for non-supervision:
S1-SW5 = Open (OFF)
This supervision is independent of the network
address.
Figure 1
MKB-1 Panel
Figure 3
Placing the MKB-1 Module in the Enclosure
Mechanical Installation
The installation kit for the MKB-1 includes:
two nuts
two 2 inch standoffs
1 . Mount the MKB-1 inside the main MXL
enclosure by placing the four holes in the
mounting bracket over the four studs provided
in the enclosure. These studs are placed two
above and two below the MMB-1 board (See
Figure 2).
When the MKB-1 is in position, it straddles the
middle of the MMB-1, leaving only the field
wiring terminals on the MMB-1 exposed.
2. Fasten the MKB-1 bracket in the enclosure
using the two 2 inch standoffs provided on top
and the two nuts provided at the bottom.
3. Once the MKB-1 is mounted to the enclosure,
connect the cable assembly on the back of
the MKB-1 to connector P8 on the MMB-1.
Figure 2
Setting S1 on the ANN-1 Board

Advertisement

loading