SAVE THESE INSTRUCTIONS TABLE OF CONTENTS This manual contains important instructions that should be followed during installation and maintenance INTRODUCTION of the generator and batteries. GUIDE TO PRODUCT SAFETY BASIC INFORMATION Read and understand all instructions in the manual Description before starting and operating the generator set.
IMPORTANT SAFETY FIRE HAZARD - Natural gas and L.P. present a hazard of possible explosion and/or fire. INSTRUCTIONS Do not smoke or use open flame near the generator set. Keep a fire extinguisher nearby and know its proper use. SAVE THESE INSTRUCTION Fire extinguishers rated ABC by NFPA are appropriate.
2) ENGINE/GENERATOR TESTING POLICY: PSS27LS- The engine generator set consists of a GM 3.0L, I-4 Industrial, four cylinder, liquid cooled engine equipped to run on Before any generator is shipped from the factory, it is fully L.P./N.G. fuel. The engine operates at 1800 rpm and frequency checked for performance.
Generator Protection and Metering All metering functions are displayed on the liquid crystal display. The front panel display begins with the SUMMARY SCREEN. Generator protection guards against over voltage, under voltage, Pressing the Right arrow key will open the MAIN MENU screen. under frequency, and over frequency.
J - Reset Push-button. This button is pressed to cancel a Repeat sequence 5 through 8 for day, minute, second and settings editing session and discard any settings changes. When DST (Daylight Saving Time. pressed, this button also resets the Breaker Management Pre- To finish clock setting, process - Press ‘K’...
General Information The engine manufacturer has established an excellent world-wide engine service organization; engine service is available from a nearby authorized dealer or distributor; check the Yellow Pages These engine generator sets are for outdoor installation. These of the telephone directory under “engines,” or ask the dealer from units must be bolted solidly to a concrete pad.
Connect the fuel supply to the inlet of the fuel solenoid (see table FUEL PRESSURE (vapor system) for recommended line size). The pressure at the secondary demand regulator must be four to six ounces psi (per square Correct fuel pressure cannot be stressed enough. The most inch) or 7 to 11 inches W.C.
Notice the preceding tables give two (2) different units of measur- When installing or replacing batteries, use the proper group/size ing fuel pressure. The first is with a pressure gauge calibrated in starting battery. The battery should be a Maintenance Free lead ounces per square inch.
properly installed, the normal A.T.S. Control and safety systems Never fill the battery above the fill line. Over filling above the will eliminate all paths for feedback. upper level line may cause the electrolyte to overflow, resulting in corrosion to the engine or nearby parts. Immediately wash off To wire the automatic transfer switch into the existing wiring, first any spilled electrolyte following the procedure above.
B - Generator Circuit Breaker, This circuit breaker provides By code, the wire must be heavy enough to handle the full current overload protection for the generator. Your power feeds from the rating of the main line circuit-breaker (or fuse) in the entrance (or transfer switch will connect to the bottom lugs on the circuit sub-panel) protecting the contactor switch.
Page 12
CONTROL PANEL LAYOUT generator control terminal box. Depending on the distance, 14 to 16 gauge stranded wire should be used. These wires should be A - DGC-2020 Digital Gen-Set Control. See Explanation on labeled S1 and S23. page 3. ************* B - DC Control Circuit Fuse.
With the engine running smoothly check the no load voltage and frequency on the digital display. The voltage should be 208/240/ 480 AC depending on which model you have and a frequency of 59.5 To 60.5 hertz (Hz). If you have the proper voltage at the generator the next step is to check the voltage at the generator terminals in the Automatic Transfer Switch.
Defective "Run/Auto" switch on generator or ATS PANEL WILL NOT RETRANSFER TO NORMAL transfer switch. POWER Defective starter. Defective start solenoid. Proper normal line power not available at line terminals in ATS panel. ENGINE WILL NOT CRANK WITH GENERATOR Defective holding coil in line side contactor. RUN PUSH-BUTTON DEPRESSED.
You are now ready to make the final fuel mixture adjustment. column. If not, adjust the screw down to increase and up to These engines were adjusted at the factory to produce about .7 to decrease and retest. 3.4% CO. If you have the ability to test the CO, adjust the mixture Next the timing on the engine must be changed.
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workman- ship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions.