Figure 3. Attaching the slide rails at the front of the rack
5. Insert the rear slide flange locator studs on the slide rail into the rear EIA mounting holes.
6. Position the slam-latch bracket (B) to cover the front EIA space of the slide rail as shown in Figure 3.
7. Use the T25 hex tool to secure the slam-latch bracket to the front rail flange with one M5 X 16mm
torx socket pan head screw (A) placed in the middle hole (1b) of the EIA rack unit as shown in
Figure 3.
8. Repeat steps 2 on page 3 through 7 for the right slide rail (D) as shown in Figure 3. The right slide
rail has an R identifier stamped into the inside front location.
9. Attach the two nut clips (F) to relative EIA locations 3b on both right and left front vertical EIA
standards as shown in Figure 3.
4
Power Systems: Installing the IBM Power System E850 (8408-E8E)