Table
o f
C ontents I.
Key
&
L egend.................................. 4
Key
t o
M odel
N umbers ..............................4
Legend
f or
T ables................................4
II.
...
Page 3
3
T ON
H eating
P erformance
D ata ..........................18
3
T ON
C ooling
P erformance
D ata ..........................19
4
T ON
H eating
P erformance
D ata ..........................20
4
...
conditioning codes are followed. Note – These units feature braze-plate heat WARNING – ELECTRICAL SHOCK CAN exchangers. Enertech requires that a strainer be CAUSE PERSONAL INJURY DEATH. installed on the water inlet of the source side Disconnect all power supplies before installing or circuit.
covered or in original shipping packaging during BUILDING
HEAT
LOSS/HEAT
GAIN
job site construction. All physical connections (air supply and return, piping, electrical) should be T he space load must be estimated accurately for protected and covered/capped prior to installation. any successful HVAC installation.
F freeze protection, since This section deals with some common practices more concentrated mixtures of propylene glycol used when coupling the Enertech hydronic heat become too viscous at low temperatures and will pumps to the space conditioning heat exchanger. become more difficult to pump through the earth There are so many possible applications for loop.
HP high-head pump to circulate fluid through the stream. loop to remove all the air out of the loop. Allow the Important – A visual flow meter is highly pump to run 10 to 15 minutes after the last air bubbles have been removed.
The hydronic side circulator supplying the heat Hydronic circulator pumps transfer the energy pump should be controlled to run only when the supplied by Enertech hydronic heat pumps to the compressor runs. If the pump is allowed to water storage tank. Select a quiet operating pump...
recommended for most indoor applications. Forty a heat pump on its side or back. ° percent (40%) propylene glycol in water (-5 F freeze CAUTION – Do not use this unit during protection) is recommended by radiant tube manufactures for snow melt applications to protect construction.
9)
2 4Vac Fuse VI.
ELECTRICAL
10)
P lug Accessory Note – Always refer to the inside of the front panel 11)
A larm Output
for the correct wiring diagram. ...
When 24Vac is applied to the O terminal on the connector. The green system power LED will be off wiring block, the controller energizes its O output if this fuse is open. A spare fuse is located in the to provide 24Vac power to the reversing valve to saddle attached to the side of the 24VAC power switch the refrigerant circuit to the cooling mode.
(50°F or above) to start in the heating mode. MAINTENANCE
Apply power to the unit. A 4-minute and 35-second Properly installed, the Enertech heat pump requires delay on power-up is programmed into the only minor maintenance such as periodic cleaning controller before the compressor will operate.
Installations may include a wide variation of valves allow access to the desuperheater plumbing available electronic room thermostats, and most of without draining the hot water tank. Keep the them must be configured by the Installer and valves open when the pump is running. checked out after installation.
Page 15
rotor's bearing, which reduces pump life and causes noise problems in the pump. Note – A spring-type check valve with a pressure-drop rating of 1/2 psig or less is recommended. 15
...
IX.
ENGINEERING
SPECIFICATIONS
PERFORMANCE
RATINGS
Heating
P erformance
D ata
( Tested
i n
a ccordance
w ith
A SHRAE/AHRI/
I SO
S tandard
1 3256-‐2) Total
...
Page 17
Cooling
P erformance
D ata
( Tested
i n
a ccordance
w ith
A SHRAE/AHRI/
I SO
S tandard
1 3256-‐2) Total
H eat
Heat
o f
Source
...
WATER
COIL
PRESSURE
DROP
RATINGS
Pressure drops (PSI) with pure water. 3
TON
GPM
W ater
F low
6
7
8
9
10
11
Source
W ater
P ressure
D rop
( Copper)
1.2
...
X. FIGURES
Figure 1 Hydronic Heat Pump – Supplying Radiant Floor Heating, Fan Coil Cooling, and Water Heating Note – Always use copper pipe on the hydronic side. Note – Conceptual drawing only. Check local codes and use proper plumbing procedures. ...
Page 37
Ground Loop Plumbing Note
–
These
units
feature
braze-‐plate
heat
exchangers.
Enertech
requires
that
a
strainer
be
installed
on
the
water
inlet
of
the
source
circuit.
A
strainer
w ith
a
s ize
o f
1 6-‐20
m esh
m inimum
s hould
b e
u sed.
F or
your
convenience
a
strainer
and
connection
hardware
have
been
included
with
...
Page 38
Figure 4 Hydronic Heat Pump – Radiant Floor Heating and Fan Coil Cooling 38
...
Page 39
Note – Always use copper pipe on the hydronic side. Note – Conceptual drawing only. Check local codes and use proper plumbing procedures. Figure 5 Hydronic Heat Pump – Multizone System Note – Always use copper pipe on the hydronic side. 39
...
Page 40
Note – Conceptual drawing only. Check local codes and use proper plumbing procedures.
40
...
Page 41
Figure 6 –Single Tank Desuperheater Installation Note – Always use copper pipe. Check local codes and use proper plumbing procedures. Figure 7 – Two Tank Desuperheater Installation 41
...
XI.
TROUBLESHOOTING
after replacing refrigeration component If the heat pump goes into lockout on a high or low (compressor, etc.). pressure switch discharge refrigerant temperature, the cause of the lockout can be narrowed down by identifying the operating mode WARNING –...
Page 43
INDICATOR LIGHTS CONDITION COMMENTS PWR ASC DISCHARGE REFRIGERANT TEMPERATURE INDICATOR (DT) Heating or Cooling – -Check if DT switch is open. before Y call -Check electrical connections between DT switch and Controller. -Significantly low flow through hydronic side and/or ground-side heat exchanger.
Page 44
PROBLEM CHECKS AND CORRECTIONS POSSIBLE CAUSE The unit could be off on high pressure, low-pressure or discharge refrigerant High Pressure or Low Pressure compressor temperature cutout. Check water GPM and temperatures, ambient temperature and Switch or Discharge Refrigerant does not, or loss of refrigerant.
PROBLEM CHECKS AND CORRECTIONS POSSIBLE CAUSE Purge air from the water side of the desuperheater heat exchanger or defective Squealing Sound from Inside the desuperheater heat exchanger. Cabinet WIRING
DIAGRAM
3
THROUGH
7
TON,
208-‐230V,
SINGLE
PHASE
45
...
Need help?
Do you have a question about the WS Series and is the answer not in the manual?
Questions and answers