Gas Piping - Noritz ecoTOUGH NRC71 OD Installation Manual

Condensing tankless gas water heater
Hide thumbs Also See for ecoTOUGH NRC71 OD:
Table of Contents

Advertisement

7.

Gas Piping

The guidelines and examples we have provided in this manual section are for reference only.
The sizing and installation of the gas system for this water heater, as with any gas appliance, is the sole
responsibility of the installer. The installer must be professionally trained to do such work and must always
follow all local and national codes and regulations. Gas line sizing calculations must be performed for
every installation. Please contact Noritz America at 866-766-7489 if you have any questions or concerns.
Gas Type
The gas type indicated on the water heater rating plate (NG or LP) must match the type of gas being supplied to the water heater.
Gas Conversions
If the gas type supplied does not match the gas type on the rating plate, contact your water heater supplier for a replacement
unit with the proper gas type. If a gas type conversion must be made, there are conversion kits available for some
models. [The conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's
instructions and all applicable codes and requirements of the authority having jurisdiction. The qualified service
agency is responsible for the proper installation of this kit. Improper installation of this kit will void the warranty.
Conversion kits will only be shipped directly to the Distributor or Agency performing the conversion.]
Meter
The gas meter must be sized properly for the water heater and other gas appliances to operate properly.
Select a gas meter capable of supplying the entire btuh demand of all gas appliances in the building.
Regulators
Ensure that all gas regulators used are operating properly and providing gas pressures within the specified
range of the water heater being installed. Excess gas inlet pressure may cause serious accidents.
Pressure
Check the gas supply pressure immediately upstream at a location provided by the gas company. Supplied
gas pressure must be within the limits shown in the specifications section with all gas appliances operating.
The inlet gas pressure must be within the range specified. This is for the purposes of input adjustment. Low
gas pressure may cause a loss of flame or ignition failure at other appliances in the home, which may result
in unburned gas in the home. Serious accidents such as fire or explosion may result.
Measuring Gas Pressure
In order to check the gas supply pressure to the unit, a tap is provided on the gas
inlet. Remove the 9/32" hex head/Philips screw from the tap, and connect a
manometer using a silicon tube. In order to measure the supply gas pressure, hold in
the maximum manifold pressure by following procedure.
Procedure to holding in the maximum manifold pressure
1. Open up at least 2 fixtures.
2. Press and hold both the Mode and DOWN Buttons on the
circuit board simultaneously for more than 2 seconds.
3. Data Display changes with the right illustration, when the
unit is ready for checking manifold gas pressure.
4. Press and hold the maximum manifold pressure button on the circuit board.
5. After checking the gas supply pressure, press and hold both the Mode and DOWN Buttons
simultaneously for more than 2 seconds in order to return to the normal mode.
Please call Noritz for details.
8
Follow the instructions from the gas supplier.
CAUTION
CAUTION
WARNING
Mode Button
Data Display
UP Button
DOWN Button
8
DIP Switch
7
Minimum Manifold
6
5
Pressure Set Button
4
3
Maximum Manifold
2
1
Pressure Set Button