Robertshaw 2374-510 Installation Data

Robertshaw 2374-510 Installation Data

Universal air pressure sensing switch

Advertisement

Quick Links

General DesCription & operation
The Robertshaw
2374-510 Air Pressure Sensing Switch
®
has a glass-filled polycarbonate housing containing a
sensing diaphragm and an integral snap-acting switch
with three male 90° quick-connect terminals. The switch
can sense positive, negative or differential air pressure.
The field adjustable set point range of this switch is
0.10" W.C. to 10.0" W.C. Using the switch accessories
contained in this kit, the switch can be applied to a
wide variety of residential and light commercial HVAC
applications.
set point ranGe & aDjustment
Calibration requires a manometer (not included in the kit)
as well as the included
7
1. Establish the set point as follows. Referring to Table 2 in
this manual, select the appropriate spring for the required
set point range. Insert the spring into the center well of
the mounting pan (light gray side of the switch housing).
2. Insert the black set point adjustment screw, and rotate
it manually until the threads are engaged.
3. Connect the switch to a manometer. Using the
hex wrench provided in the kit, turn the adjustment screw
in small increments until the desired set point is reached.
Turn the screw clockwise to increase the set point or
counterclockwise to decrease the set point. For precise
calibration, confirm the set point at actual operating
temperature with a manometer. Following precise
calibration, if desired, seal the adjusting screw using a
UV curable adhesive/sealant. Do not place the switch
in operation without knowing what the set point is:
doing so could create a hazardous situation.
mountinG
Using the (2) #6 x ⅜" mounting screws included in the
kit, mount via the integral foot bracket (see Fig. 1) or, via
either of the optional brackets (see Figs 4 & 5) included
in the kit. If using one of the optional brackets, attach it
to the switch with the self-tapping screw provided before
mounting the switch. Select a mounting location free
from vibration. Mount with the diaphragm in any vertical
plane. Avoid mounting with the sample line connections
directed upward.
eleCtriCal ConneCtions
The snap switch has three ¼" 90° male quick connect
terminals. Before pressure is applied to the diaphragm,
the switch contacts are in the deactivated position as
shown in Figure 2.
191 E. North Avenue
Carol Stream Illinois 60188 USA
Customer Service Telephone 1.800.304.6563
Customer Service Facsimile 1.800.426.0804
HVACCustomerService@Invensys.com
" hex wrench.
32
For Technical Service
Telephone 1.800.445.8299
Facsimile 1.630.260.7294
TechnicalService@Invensys.com
UNIVERSAL AIR PRESSURE
Carton Contents
(1) field adjustable switch
(1) black set point adjustment screw
(1) hexagon key wrench
(5) color-coded springs
(8) color-coded orifices
(1) half strap mounting bracket
(1) angle ("L") bracket
(1) mounting screw for optional brackets
7
"
32
(2) #6 x ⅜" mounting screws for optional brackets
air samplinG ConneCtion
Integral sample line connectors, located on both sides
of the diaphragm, accept
Figure 3. The High or Positive inlet (P1) is black and the
Low or Negative inlet (P2) is gray. Connect the sample
lines as follows:
positive pressure only: Connect the sample line to P1;
P2 remains open to the atmosphere.
negative pressure only: Connect the sample line to P2;
P1 remains open to the atmosphere.
two negative samples: Connect higher negative sample
to P2; lower sample to P1.
two positive samples: Connect higher positive sample
to P1; lower sample to P2.
one positive and one negative: Connect positive
sample to P1; connect negative sample to P2.
usinG a Flow-restriCtinG oriFiCe
Some applications require a delayed switching action
after set point is reached. The delay is created by
inserting an orifice plug into either or both of the sample
line connectors to restrict air flow. Eight orifice plugs in
four color-coded sizes are included in the kit as shown
in Table 3. Note that the measuring device and the air
switch must both contain the same size restricting orifice in
order to obtain an accurate measurement of the set point.
Invensys™ and Robertshaw
are trademarks of Invensys
®
plc., its subsidiaries and/or affiliated companies. All
other brands mentioned may be the trademarks of their
respective owners.
INSTALLATION DATA
2374-510
SENSING SWITCH
3
" ID flexible tubing. See
16
www.Uni-Line.com
www.InvensysControls.com
©2011 Invensys Controls
5/11 - LTNS2000008 00

Advertisement

loading

Summary of Contents for Robertshaw 2374-510

  • Page 1 2374-510 UNIVERSAL AIR PRESSURE SENSING SWITCH General DesCription & operation The Robertshaw 2374-510 Air Pressure Sensing Switch ® has a glass-filled polycarbonate housing containing a sensing diaphragm and an integral snap-acting switch with three male 90° quick-connect terminals. The switch can sense positive, negative or differential air pressure.
  • Page 2 If you have any questions regarding the installation, use or safety of this switch, please call Technical Service at (800) 445-8299. This sensing switch must be installed, adjusted and serviced by a qualified HVAC installation technician. table 1: moDel seleCtion p/n 2374-510 Kit Bleed hole in Mounting Pan table 2: sprinG seleCtion Color set point range ("w.C.)
  • Page 3  Fig. 1: Dimensions: NS2 Switch with integral connectors and mounting feet. Figure 4: Half Strap Bracket Figure 5: "L" Bracket...
  • Page 4 Kits For HVaC teCHniCal speCiFiCation appliCations! material the new sensing probe Kits contain a 7" universal probe with mounting hardware, 3' of Body Glass-filled polycarbonate vinyl tubing, a slip on adapter, and complete application instructions. Order 10-650 Today!