7-5. Auto Address Setting
Example: Basic Wiring Diagram (1)
• Case of no link wiring
(Inter-unit control wiring is not connected to a multiple system.)
Indoor unit address setting is possible without starting the compressor.
Unit 1 setting (outdoor main unit)
System address
(System 1 setting)
(SW1)
Number of
outdoor units
(3 units setting)
Outdoor Unit
Remote controller
Case 1
Auto Address Control from Outdoor Unit
1. Regarding the number of outdoor units, set the Dip switch (SW6) for setting the number of outdoor units on Unit 1 control P.C.B to 3
ON
ON
units
and the Unit Number Setting Dip switch (SW5) to unit number 1.
1
2
3
OFF
This unit becomes the outdoor main unit.
2. Set the Unit Number Setting switch (SW5) on unit 2 control P.C. board to unit number 2.
Set the Unit Number Setting switch (SW5) on unit 3 control P.C. board to unit number 3.
3. Check the refrigerant system's Address Setting Rotary switch (SW1) on outdoor main unit control P.C. board to "1" and the Dip switch
(SW2) to "0" (at shipment).
4. Regarding the setting of the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number of
indoor units on outdoor main unit control P.C. board connected to the outdoor unit to "1".
If the Rotary switch (SW3) set to "0", 10 units can be prepared for operation.
5. Turn on power to indoor and outdoor units.
6. Short circuit the A.ADD pin (CN30) on outdoor main unit control P.C. board for over 1 second long and open circuit.
Communication for auto address setting begins.
* To cancel, short circuit the A.ADD pin (CN30) again for over 1 second long and then open circuit. The LED that
indicates auto address setting goes out and the process is stopped.
Be sure to perform auto address setting again.
Auto address setting is completed when LEDs 1 and 2 on outdoor main unit control P.C. board go out.
7. Remote control operation is now available.
* When auto address setting is controlled by the remote controller, perform auto address setting by the remote controller after step 5
described above.
See to section "Auto Address Setting from Remote Controller".
01_302412_Eng.indd 47
No. of indoor units
(10 units setting)
(SW3)
0
(SW2)
ON
ON
(SW4)
ON
ON
1
2
OFF
1
2
3
OFF
(SW6)
Unit
(SW5)
ON
number
ON
ON
ON
setting
1
2
3
OFF
(unit 1)
1
2
3
OFF
Set the terminating
resistance pin
to SHORT side.
Unit 1
(CN67)
(Main)
Inter-outdoor unit
control wiring
Inter-unit control wiring
1-1
1-2
Indoor unit
ON
ON
1
2
OFF
* It is not necessary to control the terminating
resistance pin (3P) (CN67) on the outdoor unit
P.C. board.
3P pin is plugged in SHORT side at shipment.
Confirm it is plugged in SHORT side.
Unit 2 setting
(SW5)
Unit
Unit
ON
ON
number
number
setting
setting
1
2
3
OFF
(unit 2)
(unit 3)
Unit 2
(Sub)
Inter-outdoor unit
control wiring
1-3
Remote control
communication wiring
ON
1
2
ON
1
ON
1
ON
1
47
3P terminating
resistance pin
(SHORT side)
SHORT
Unit 3 setting
(SW5)
ON
ON
1
2
3
OFF
Unit 3
(Sub)
1-10
3
2
3
2
3
ON
2
3
OFF
OPEN
2018/7/4 13:31:01