WARNING This instrument must only be used by a competent, trained person and operated in strict accordance with the instructions. We will not accept liability for any damage or injury caused by misuse or non-compliance with the instruction or safety procedures. It is essential to read and understand the safety rules contained in the instructions.
FEATURES Custom microprocessor controlled for highest accuracy and reliability. 3 neons for checking correct wiring status. Direct reading of Prospective Shout Circuit Current (PSC). Large custom digital display readout on all models. Measures low loop impedance (resolution of 0.01 Ohm). High impedance ranges permit direct measurements of ground spikes.
SPECIFICATIONS Rated Voltage : 230V±10% 50Hz. Operating Temperature : 0℃ ~ 40℃ Storage Temperature : -5℃ ~ 60℃ Operating Humidity : 85% Maximum. Storage Humidity : 85% Maximum. Accuracy of Mains ±(2% + 2digit). Voltage Display : Accuracy (Loop Impedance) : ±(2%±3digit) Fuse Protection : 240V/13A, 6kA HRC ceramic fuses.
Page 7
Environmental Conditions The product is designed for indoor use and up to a maximum altitude of 2000m. Installation Category : 300V CAT Ⅲ(single phase 230V) Pollution Degree 2 This manual and product may use the following symbols adopted from International Safety Standards. Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION.
4-1 Voltage Measurement When the Loop and PSC Testers are first powered up by connecting them to the mains, they automatically display the mains voltage. The voltage display is updated automatically every 0.5s. When the test button is depressed (see section 5.1 first) the voltage mode is cancelled.
OPERATING INSTRUCTIONS 5-1 Correct Wiring Before pressing the “Test Button” always check the P-E, P-N, neon lamps for the following light sequence : P-E Neon must be ON P-N Neon must be ON Neon must be OFF If the sequence of lights is not as above DO NOT PROCEED with further testing.
Press the “Press to Test” button. The value of loop impedance will be displayed with the appropriate units. A bleep will sound on completion of the test. For best results always test on the lowest possible range. No harm will be done to the instrument by selecting too low a range.
5-4 Measurement of Prospective Short Circuit Current Note : There units are only intended for single phase operation. Set the instrument to the 20kA range. Connect the test lead to the instrument. Attach the plug to the socket to be tested. Check that the neons are lit in the sequence indicated in section 5-1.