Fujitsu GENERAL ASHG24KMTA Design & Technical Manual page 29

Hide thumbs Also See for GENERAL ASHG24KMTA:
Table of Contents

Advertisement

2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
11
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er's recommended value).
Function number
30
(For cooling)
11-1. Function settings by using remote controller
Setting value
00
01
02
03
Setting value
00
01
02
03
04
05
06
07
08
31
(For heating)
09
10
11
12
13
14
15
16
17
Setting description
Standard (400 hours)
Long interval (1,000 hours)
Short interval (200 hours)
No indication
Setting description
Standard setting
No correction 0.0 °C
-0.5 °C
-1.0 °C
-1.5 °C
-2.0 °C
-2.5 °C
-3.0 °C
-3.5 °C
-4.0 °C
+0.5 °C
+1.0 °C
+1.5 °C
+2.0 °C
+2.5 °C
+3.0 °C
+3.5 °C
+4.0 °C
- 25 -
Factory setting
Factory
setting
More cooling
Less heating
Less cooling
More heating
11. Function settings