Hitachi RAK-15QPB Service Manual page 57

Hide thumbs Also See for RAK-15QPB:
Table of Contents

Advertisement

,for
RAK-15Q PB,RAK-18/ 25/ 50RPB only
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming as the preset temperature =
(room temperature at the time) - (2°C).
(2) The indoor fan is operated in the "Lo" mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
- 57 -