Preface
Thank you for purchasing VD530 series inverters!
VD530 is a high-performance vector control inverter developed by VicRuns. Adopting advanced
vector control algorithm, it is widely used for asynchronous motor speed control. Through its
integrated EMC design and with optimized PWM control technique to meet users' demand on
environmental requirement such as low-noise in application places and low EMI. It has perfect
anti-tripping control and good adaptive ability to bad power grid, temperature, humidity and dust, in
order to satisfy various sophisticated requirement under high precision drive applications, thus to
satisfy users expectation of higher reliability and stronger adaptability to environment of their
equipment, achieving industry specialization and personalized motor drive and control system
solution.
VD530 series high performance vector control inverter has following outstanding features:
1. Various control method
Supporting control method: SVC, FVC, V/F control.
2. Leading vector control algorithm
Optimized sensorless FVC control has better low speed stability, stronger low frequency load capacity,
supporting speed control and torque control.
3. Support multi-function I/O extension and multi-function MFI extension port
Multi-function I/O extension card, multi-function MFI extension port can connect related extension
function unit defined by manufacturer.
This manual provides the related issues: user installing and site wiring, quick debug, parameters
setting, failure diagnose and eliminate and daily maintenance and correlation matters. Please read
this manual to make sure you can install, use and maintain the inverter correctly, then play their
superior performance.
Please send this manual to the user or maintainer of this inverter, and properly kept.
Unpacking and Inspection:
Every inverter has been inspected rigorously before shipping.
Please confirm carefully when unpacking the packing carton:
● Check if any damage signs of the product and its package.
● Check if the model and inverter rated values on the nameplate are the same as stated on your order
and user manual.
● The box contains the inverter, manufacturer certificate, user manual.
If the product is damaged during transportation, or there is any omission or damage, please contact
our company or your local supplier immediately.
First time use suggests:
The users who use this product for the first time shall read this manual carefully. For any doubt on
certain functions and performances, please contact the technical support personnel of our company
for help, so as to use this product properly. With commitment to the constant improvement of the
inverter products, our company may change the information provided without additional notice.
VD530 series inverter is confirmed to below international standard, has passed the CE certification.
IEC/EN 61800-5-1: 2003 adjustable speed electric drive system safety regulation requirements;
IEC/EN 61800-3: 2004 adjustable speed electric drive system: part 3: product EMC standard and its
specific test method;
IEC/EN61000-2-1, 2-2, 3-2, 3-3, 4-2, 4-3, 4-4, 4-5, 4-6; EMC international and EU standard .

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VD530 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Vicruns VD530 Series

  • Page 1 With commitment to the constant improvement of the inverter products, our company may change the information provided without additional notice. VD530 series inverter is confirmed to below international standard, has passed the CE certification. IEC/EN 61800-5-1: 2003 adjustable speed electric drive system safety regulation requirements;...
  • Page 3: Table Of Contents

    Contents Chapter 1 Safety and Precautions ......................- 1 - 1.1 Safety Definition ........................... - 1 - 1.2 Safety Precautions ..........................- 1 - 1.3 General Precautions ..........................- 3 - Chapter 2 Product Information ........................- 6 - 2.1 Designation Rules ..........................- 6 - 2.2 Nameplate .............................
  • Page 4 Chapter 7 EMC Guide ..........................- 205 - 7.1 Definition............................- 205 - 7.2 EMC Standard Introduction ......................- 205 - 7.3 EMC Guide ............................- 205 - Chapter 8 Fault Shooting and Solutions ....................- 207 - 8.1 Fault Alarm and Countermeasures ....................- 207 - 8.2 Common Faults and Solutions......................
  • Page 5: Chapter 1 Safety And Precautions

    VD530 Series Inverter User Manual Safety and Precautions Chapter 1 Safety and Precautions 1.1 Safety Definition During the installation, commissioning and maintenance of the system, please make sure to follow the safety and precautions of this chapter. In case of a result of illegal operations, caused any harm and losses is nothing to do with the manufacturer.
  • Page 6 Safety and Precautions VD530 Series Inverter User Manual ● When two inverters are installed in the same cabinet, arrange the installation positions properly to ensure normal cooling effect, keep the cabinet with good ventilation. 1.2.3 At Wiring DANGER ● Wiring must be performed only by qualified personnel under instructions described in this manual.
  • Page 7: General Precautions

    VD530 Series Inverter User Manual Safety and Precautions 1.2.6 During Operation DANGER ● Do not touch the cooling fan or braking resistor etc, otherwise may cause personal injury! ● Do not do inspection while inverter run, except for professional technician, otherwise may cause inverter damaged or personal injury.
  • Page 8 Safety and Precautions VD530 Series Inverter User Manual 1.3.5 Regarding Motor Heating and Noise Inverter output voltage is PWM wave, with some higher harmonic, so motor temperature rising, noise and vibration should increase a little comparing with power frequency, which is normal.
  • Page 9 VD530 Series Inverter User Manual Safety and Precautions damage or performance reduce. - 5 -...
  • Page 10: Chapter 2 Product Information

    Product Information VD530 Series Inverter User Manual Chapter 2 Product Information 2.1 Designation Rules VD530-4T-11GB/15PB Vicruns series Voltage level Adaptable moter power Brake unit 220V B : Including brake unit G type 11 kW moter 220V None 380V P type 15 kW moter Fig 2.1-1 Designation Rules...
  • Page 11 VD530 Series Inverter User Manual Product Information VD530-2S-3.7GB 35.0 17.0 VD530-2S-5.5GB 50.0 25.0 Three-phase power supply: 380V, 50/60Hz VD530-4T-0.7GB 0.75 VD530-4T-1.5GB VD530-4T-2.2GB VD530-4T-3.7GB 10.5 VD530-4T-5.5GB VD530-4T-5.5PB 14.6 13.0 VD530-4T-7.5GB VD530-4T-7.5PB 11.0 20.5 17.0 VD530-4T-11GB VD530-4T-11PB 17.0 26.0 25.0 11.0 VD530-4T-15GB VD530-4T-15PB 21.0...
  • Page 12: Product Specifications

    Product Information VD530 Series Inverter User Manual 2.4 Product Specifications Table 2-2 Product technical specification Item Specifications Grade of rated voltage is 220V or 380V: voltage continued Rated input fluctuation±10%, brief fluctuation:-15~+10%, voltage voltage imbalance rated<3%, aberration rate meet IEC61800-2 requirements.
  • Page 13 VD530 Series Inverter User Manual Product Information Easy PLC, Via built-in PLC or control terminal can realize max 16 multi-stage speed stage speed run. Built-in PID Can realize process control conveniently. Auto-adjustment Can keep the output voltage constant automatically when...
  • Page 14: Physical Appearance And Main Structure Diagram

    Product Information VD530 Series Inverter User Manual Motor short-circuit detection at power-on, input/output Display and Protection phase loss protection, overcurrent protection, overvoltage Keypad function protection, undervoltage protection, overheat protection Operation and overload protection etc. Installation Indoor, free from direct sunlight, without dust, corrosive location gas, combustible gas, oil smoke, vapor, drip or salt etc.
  • Page 15: Product Appearance And Installation Dimension

    VD530 Series Inverter User Manual Product Information 2.6 Product Appearance and Installation Dimension Fig 2.6-1 Schematic diagram for physical dimensions and mounting dimensions (below 7.5kW) Fig 2.6-2 Schematic diagram for physical dimensions and mounting dimensions (11kW~110kW) Fig 2.6-3 Schematic diagram for physical dimensions and mounting dimensions (up 132 kW)
  • Page 16 Product Information VD530 Series Inverter User Manual Table 2-3 Physical Dimensions and Installation Hole (mm) Diameter Weight Mounting Hole Physical Dimensions (mm) (mm) Mounting (kg) Model Hole (mm) Single-phase 220V, 50/60Hz VD530-2S-0.7GB VD530-2S-1.5GB 106.5 VD530-2S-2.2GB VD530-2S-3.7GB VD530-2S-5.5GB Three-phase 380V, 50/60Hz VD530-4T-0.7GB...
  • Page 17: Physical Dimensions Of External Keyboard

    VD530 Series Inverter User Manual Product Information VD530-4T-220G/250P VD530-4T-250G/280P 1000(H) 1450(C) VD530-4T-280G/315P VD530-4T-315G/355P VD530-4T-355G/400P VD530-4T-400G/450P 1300(H) 1270 1240 1750(C) VD530-4T-450G/500P VD530-4T-500G/560P 2.7 Physical Dimensions of External Keyboard 2-M4 Physical dimensions of keyboard Physical dimensions of keyboard holder Fig 2.7-1 External keyboard and holder dimension 78.5...
  • Page 18: Braking Unit Model Selection Guide

    Product Information VD530 Series Inverter User Manual 2.8 Braking Unit Model Selection Guide 2.8.1 Resistor Value Selection When braking, the regenerative energy of the motor is almost all consumed in the braking resistor. According to formula U*U/R=Pb In formula U---braking voltage when system is stability braking (different system with different value,...
  • Page 19: Routine Repair And Maintenance Of Inverter

    VD530 Series Inverter User Manual Product Information ≥26.5Ω VD530-4T-22G/30P 4.4kW ≥19.4Ω VD530-4T-30G/37P External VDBU-4T-70G ≥15.8Ω VD530-4T-37G/45P 7.4kW ≥13Ω VD530-4T-45G/55P ≥10.6Ω VD530-4T-55G/75P 11kW External VDBU-4T-110G ≥7.8Ω VD530-4T-75G/90P 15kW ≥6.5Ω VD530-4T-90G/110P 18kW External VDBU-4T-160G ≥5.3Ω VD530-4T-110G/132P 22kW ≥4.4Ω VD530-4T-132G/160P 26.4kW External VDBU-4T-250G ≥3.6Ω...
  • Page 20 Product Information VD530 Series Inverter User Manual 2.9.1 Daily Round Check Daily Inspection Projects WARNING ● If the heat from motor and the run inverter is higher than normal temperature ● If any abnormal noise or vibration from motor and the run inverter ●...
  • Page 21: Warranty Introduction

    VD530 Series Inverter User Manual Product Information WARNING ● Do not keep it in high temperature, humid or vibrated place with metal powder, and keep good ventilation. ● If inverter kept too long without run, the filter capacitor performance will reduce.
  • Page 22: Chapter 3 Mechanical And Electrical Installation

    Mechanical and Electrical Installation VD530 Series Inverter User Manual Chapter 3 Mechanical and Electrical Installation 3.1 Installation Environment The ambient temperature exerts great influences on the service life of the inverter and is not allowed to exceed the allowable temperature range (-10 ℃ Celsius to 40℃ Celsius).
  • Page 23: Removing And Mounting The Cover Plate And Keyboard

    VD530 Series Inverter User Manual Mechanical and Electrical Installation 3.3 Removing and Mounting the Cover Plate and Keyboard Fig 3.3-1 Removing and mounting the keyboard diagram Disassembly of control panel: put the middle finger on upper part of control panel, lightly press the upper clip and pull out.
  • Page 24: Inverter And External Electrical Parts Connection

    Mechanical and Electrical Installation VD530 Series Inverter User Manual Bottom Corver plate Fig 3.3-3 Removing and installing the cover plate of sheet-metal enclosure Disassembly and installation of sheet-metal enclosure: with cross screwdriver to screw off the two screws at the bottom of the undercover plate, then loosen the two screws at the top of the undercover plate, pull-down the undercover plate can be disassemble, reverse order the undercover plate can be install.
  • Page 25 VD530 Series Inverter User Manual Mechanical and Electrical Installation Table 3-1 the peripheral devices Must install the isolation switch device such as a obvious segmentation between the grid and frequency inverter, and ensure the personal safety when equipment maintenance. Breaker The capacity of breaker is 1.5~2 time of frequency inverter rated...
  • Page 26 Mechanical and Electrical Installation VD530 Series Inverter User Manual Note: the data in the table in only two conductors using the same metal case is correct, if not so, protective conductor cross-sectional area should be through the method of conductivity coefficient equivalent using the determined.
  • Page 27 VD530 Series Inverter User Manual Mechanical and Electrical Installation Three-phase 380V 50/60Hz VD530-4T-0.7GB VD530-4T-1.5GB VD530-4T-2.2GB VD530-4T-3.7GB/5.5PB VD530-4T-5.5GB/7.5PB VD530-4T-7.5GB/11PB VD530-4T-11GB/15PB VD530-4T-15GB/18.5PB VD530-4T-18.5G/22P VD530-4T-22G/30P VD530-4T-30G/37P VD530-4T-37G/45P VD530-4T-45G/55P VD530-4T-55G/75P VD530-4T-75G/90P VD530-4T-90G/110P VD530-4T-110G/132P VD530-4T-132G/160P VD530-4T-160G/185P VD530-4T-185G/200P VD530-4T-200G/220P 150*2 150*2 VD530-4T-220G/250P 150*2 150*2 VD530-4T-250G/280P 185*2...
  • Page 28 Mechanical and Electrical Installation VD530 Series Inverter User Manual Table 3-5 Selection table of input/output AC Reactor, DC reactor Input AC Reactor Output AC Reactor DC Reactor Inverter Capacity(kW) Inductance Inductance Inductance Current(A) Current(A) Current(A) (mH) (mH) (mH) VD530-4T-0.7GB VD530-4T-1.5GB VD530-4T-2.2GB...
  • Page 29: Standard Wiring Diagram

    VD530 Series Inverter User Manual Mechanical and Electrical Installation 3.5 Standard Wiring Diagram 3.5.1 Standard Wiring Diagram for Single-phase 220V Inverter Brake unit VicRuns Collector output FWD/Stop +24V REV/Stop +24V COM HDO1 Free stop High pulse output Fault reset HDI1...
  • Page 30 Mechanical and Electrical Installation VD530 Series Inverter User Manual 3.5.2 Standard Wiring Diagram for Three-phase and Lower than 15kW Inverter: Brake unit L1/R L2/S L3/T VicRuns Collector output FWD/Stop REV/Stop +24V HDO1 +24V COM Free stop High pulse output Fault reset...
  • Page 31: Main Circuit Terminals

    VD530 Series Inverter User Manual Mechanical and Electrical Installation 3.5.3 Standard Wiring Diagram for Three-phase and High than 18.5kW Inverter: Brake unit VDBU L1/R L2/S L3/T VicRuns Collector output FWD/Stop +24V REV/Stop HDO1 +24V COM Free stop High pulse output...
  • Page 32 Mechanical and Electrical Installation VD530 Series Inverter User Manual 3.6.1.2 Wiring Diagram of Main Circuit of Three-phase and Lower Than 2.2kW Inverter PB P+ Three phrase Three phrase Brake unit motor power Fig 3.6-2 Wiring diagram of main circuit of three-phase and lower than 2.2kW inverter 3.6.1.3 Wiring Diagram of Main Circuit of Three-phase 3.7kW-15Kw Inverter...
  • Page 33 Mechanical and Electrical Installation DANGER ● The voltage class of VD530 series inverter 3phase power has two grades: 220V, 380V, before connecting power, please make sure the power class on inverter nameplate is the same with the accessing power. Otherwise do not connect.
  • Page 34: Control Circuit Terminal

    Mechanical and Electrical Installation VD530 Series Inverter User Manual 3.7 Control Circuit Terminal 3.7.1 Control Terminals and Functional J3J4 485+ 485- 5/10V AI2 AO1 HDI1 DI2 OPEN +24V T1/A T1/B T1/C PE GND DI5 COM HDO1 DO1 T2/A T2/C Fig3.7-1 Diagram of main control board and function extension card connection 3.7.2 Description of Control Circuit Terminal...
  • Page 35 VD530 Series Inverter User Manual Mechanical and Electrical Installation Connect to 24V by default, J14 jumper on main control board to select +24V or COM External connection. power Power Supply OPEN When external power is used to drive DI1~DI5, input...
  • Page 36 Mechanical and Electrical Installation VD530 Series Inverter User Manual Analog Support 0V~10V voltage or 0/4mA~20mA AO2-GND output current output, decided by jumper J4, default terminal 2 0V~10V voltage output Optical coupling isolation, dual polarity open collector output; Digital DO1-COM Pull-up voltage range: 5V~24V(pull-up...
  • Page 37 VD530 Series Inverter User Manual Mechanical and Electrical Installation When jump cap plug connect to A, AO2 terminal select A terminal DC0/4mA-20mA current signal output When jump cap plug connect to V, AO2 terminal select DC0V-10V V terminal voltage signal output...
  • Page 38 Mechanical and Electrical Installation VD530 Series Inverter User Manual +24V +24VOPEN COM +24V OPEN HDI1、 3.3k DI1~DI5 VicRuns External control Internal circuit Fig 3.7-2 Schematic diagram for connection of terminal of digital input +24V +24VOPEN COM +24V Fuse Protector OPEN DC24V HDI1、...
  • Page 39 VD530 Series Inverter User Manual Mechanical and Electrical Installation ≤20m External Analog source DC0~20mA DC4~20mA Proximal cable grounding VicRuns External circuit Internal circuit Fig 3.7-5 Schematic diagram of analog input terminal input current signal with shield twist cable Cross in the same...
  • Page 40 Mechanical and Electrical Installation VD530 Series Inverter User Manual 3.7.5.4 Digital Output Terminal Using External Power DC 5~24V DO1、HDO1 Flyback Relay Diode VicRuns Internal circuit External control Fig 3.7-9 Schematic diagram of digital output terminal using external power 4.7kΩ HDO1...
  • Page 41 VD530 Series Inverter User Manual Mechanical and Electrical Installation DC0~20mA VicRuns Internal circuit Exteranl control Fig 3.7-12 Schematic diagram of terminal of analog output of current signal 3.7.5.6 Output Terminals of Relay +24V +24V Short-Circuit Plate or Wire T1/A Halt Indicate...
  • Page 42: Chapter 4 Operation And Display

    Operation and Display VD530 Series Inverter User Manual Chapter 4 Operation and Display 4.1 Introduction to Operation and Display Interface With the operation panel, it can perform such operations on the inverter as function parameter modification, inverter working status monitoring and inverter run control (startup and stop).
  • Page 43 VD530 Series Inverter User Manual Operation and Display This key is used to operate on the inverter in key Run key operation mode This key is used to stop in running state and it is limited Stop/Reset key by function code F7-01...
  • Page 44: Motor Parameter Self-Learning

    Select vector control mode, before inverter operation, must input the parameter from the nameplate of the motor, VD530 series inverter will match standard motor parameter according to this message. Vector control mode is highly dependent on motor parameter, so to acquire good control performance, it needs correct motor parameter.
  • Page 45: Password Setting

    After self-learning, the function code recover to 0. 4.3 Password Setting The VD530 series inverter provides user password protection function. When FF-00 is set to non-zero value, it indicates the user password, and the password protection turns Enabled after exiting the function code editing status.
  • Page 46: Chapter 5 Function Parameter Table

    Function Parameter Table VD530 Series Inverter User Manual Chapter 5 Function Parameter Table The symbols in the function table are described as follows: ○——It indicates that the parameter setup value can be modified when the inverter is in run state;...
  • Page 47 VD530 Series Inverter User Manual Function Parameter Table Auxiliary Frequency Same as F0-02 (Main Frequency ◎ F0-04 Source A Source A Selection) Selection Unit’s digit: frequency source selection 0: Main frequency source A 1: Main auxiliary operation result (operational relationship is determined by...
  • Page 48 Function Parameter Table VD530 Series Inverter User Manual Frequency ○ F0-13 Upper Limit 0.00Hz~max frequency F0-10 0.00Hz Offset Frequency ○ F0-14 0.00Hz~frequency upper limit F0-12 0.00Hz Lower Limit Frequency ● F0-15 Command 2: 0.01Hz Resolution Frequency Command 0: Running frequency ◎...
  • Page 49 VD530 Series Inverter User Manual Function Parameter Table command binding frequency source selection, same as above Thousand’s digit: Automatic operation command binding frequency source selection, same as above Communication ● F0-23 Protocol 0: Modbus Selection 0: Motor 1 ◎ F0-24...
  • Page 50 Function Parameter Table VD530 Series Inverter User Manual Initial Frequency ○ F1-09 of Stop DC 0.00Hz~max frequency 0.00Hz Braking Waiting Time of ○ F1-10 0.0s~100.0s 0.0s Stop DC Braking Stop DC Braking ○ F1-11 0%~100% Current Stop DC Braking ○...
  • Page 51 VD530 Series Inverter User Manual Function Parameter Table Over-excitation ○ F1-25 0~200 Gain Over-excitation ○ F1-26 Filter 0~10 Coefficients 0: Straight-line acceleration/deceleration Acceleration/De ◎ F1-27 1: S curve acceleration/deceleration A celeration Mode 2: S curve acceleration/deceleration B Time Ratio of S ◎...
  • Page 52 Function Parameter Table VD530 Series Inverter User Manual 0.001Ω~65.535Ω (Inverter Asynchronous power≤55kW) Tune ◎ F2-06 Motor Stator 0.0001Ω~6.5535Ω (Inverter parameter Resistance power>55kW) 0.001Ω~65.535Ω (Inverter Asynchronous power≤55kW) Tune ◎ F2-07 Motor Rotor 0.0001Ω~6.5535Ω (Inverter parameter Resistance power>55kW) 0.01mH ~655.35mH (Inverter Asynchronous power≤55kW)
  • Page 53 VD530 Series Inverter User Manual Function Parameter Table Speed Loop ○ F3-01 0.01s~10.00s 0.50s Integral Time 1 Switch ○ F3-02 0.00~F3-05 5.00Hz Frequency 1 Speed Loop ○ F3-03 Proportional 1~100 Gain 2 Speed Loop ○ F3-04 0.01s~10.00s 1.00s Integral Time 2 Switch ○...
  • Page 54 Function Parameter Table VD530 Series Inverter User Manual Speed Loop 0: Disabled Integral ○ F3-17 Separation 1: Enabled Enable Max Weak ○ F3-20 Magnetic 1%~300% Current Weak Magnetic ○ F3-21 Automatic Gain 10%~500% 100% Adjustment Weak Magnetic ○ F3-22 Integral...
  • Page 55 VD530 Series Inverter User Manual Function Parameter Table Manual Torque ◎ F4-03 Boost Cutoff 0.00Hz~max frequency 50.00Hz Frequency MS VF ◎ F4-04 Frequency Point 0.00Hz~F4-05 0.00Hz MS VF Voltage ◎ F4-05 0.0%~100.0% 0.0% Point 1 MS VF ◎ F4-06 Frequency Point F4-04~F4-07 0.00Hz...
  • Page 56 Function Parameter Table VD530 Series Inverter User Manual F5 Input Terminal Factory Function Parameter Setting Range Default Property Code Name Value 0: Two-line mode 1 1: Two-line mode 2 2: Three-line mode 1 Terminal ◎ F5-00 Command Mode 3: Three-line mode 2...
  • Page 57 VD530 Series Inverter User Manual Function Parameter Table effective for keypad control) 29: External stop terminal 2 (According to the deceleration time 4) 30: Emergency stop 31: PID pause 32: PID integral pause 33: Reverse PID action direction 34: PID parameter switching...
  • Page 58 Function Parameter Table VD530 Series Inverter User Manual Ten thousand’s digit: DI5, same as above Unit’s digit: HDI1 0: High level effective DI1 Terminal 1: Low level effective ◎ F5-11 Mode Selection 0x0000 Ten’s digit: reserved 2 Effectively Hundred’s digit: reserved Thousand’s digit: reserved...
  • Page 59 VD530 Series Inverter User Manual Function Parameter Table AI Curve 1 Min ○ F5-22 -10V~F5-24 0.00V Input Corresponding Setting of AI ○ F5-23 -100.0%~+100.0% 0.0% Curve 1 Min Input AI Curve 1 Max ○ F5-24 F5-22~+10.00V 10.00V Input Corresponding Setting of AI ○...
  • Page 60 Function Parameter Table VD530 Series Inverter User Manual Corresponding ○ F5-40 Setting of Pulse -100.0%~+100.0% 100.0% Max Input PULSE Filter ○ F5-41 0.00s~10.00s 0.10s Time Travel Switch ○ F5-42 0.00s~10.00s 1.00s Lock Time 0: Voltage ○ F5-43 AI2 Input Type...
  • Page 61 VD530 Series Inverter User Manual Function Parameter Table 16: Frequency lower limit reached (output when stop) 17: Current 1 reached output 18: Current 2 reached output 19: Zero current state 20: Output current limit exceeded 21: Motor overload pre-alarm 22: Inverter overload pre-alarm...
  • Page 62 Function Parameter Table VD530 Series Inverter User Manual RELAY 1 Output ○ F6-08 0.0s~3600.0s 0.0s Delay Time RELAY 2 Output ○ F6-09 0.0s~3600.0s 0.0s Delay Time DO1 Output ○ F6-10 0.0s~3600.0s 0.0s Delay Time DO5 (expansion ○ F6-11 card) Output 0.0s~3600.0s...
  • Page 63 VD530 Series Inverter User Manual Function Parameter Table Corresponding Setting Value of ○ F6-19 AO1 Output F6-17~100.0% 100.0% Voltage Upper Limit AO1 Output ○ F6-20 0.00s~10.00s 0.00s Filter Time AO2 Output ○ F6-21 Voltage Lower 0.00V~10.00V 0.00V Limit Corresponding Setting Value of ○...
  • Page 64 Function Parameter Table VD530 Series Inverter User Manual F7 AIAO Keyboard and Display Factory Function Parameter Setting Range Default Property Code Name Value 0: Invalid 1: Operation panel command channel and switching with remote command channel (terminal command channel or...
  • Page 65 VD530 Series Inverter User Manual Function Parameter Table Bit08: Line speed Bit09: Current power on time (Hour) Bit10: Current running time (Min) Bit11: PULSE input frequency (Hz) Bit12: Communication setting value Bit13: Encoder feedback speed (Hz) Bit14: Main frequency A display (Hz)
  • Page 66 Function Parameter Table VD530 Series Inverter User Manual F8 Protection Parameters Factory Function Parameter Setting Range Default Property Code Name Value Motor 1 0: Disabled Overload ○ F8-00 Protection 1 : Enabled Selection Motor 1 ○ F8-01 Overload 0.20~10.00 1.00...
  • Page 67 VD530 Series Inverter User Manual Function Parameter Table Quick Start Over current ○ F8-13 0~1000 Suppression Gain Short-circuit to 0: Invalid ○ F8-14 Ground Upon 1: Valid Power-on Input Phase 0: Disabled ○ F8-15 Loss Protection 1: Enabled Selection Output Phase 0: Disabled ◎...
  • Page 68 Function Parameter Table VD530 Series Inverter User Manual Voltage Judgment Value ○ F8-27 Upon 60.0%~100.0% (Standard bus voltage) 80.0% Instantaneous Power Failure Encoder 0.0: No limit ○ Reverse F8-28 0.0s 0.1s~60.0 Testing Time Biggest Change of V/F ○ F8-29 1~30000...
  • Page 69 VD530 Series Inverter User Manual Function Parameter Table 27: Running time reached 28: Power-on time reached 29~30: Reserved 31: Encoder / PG card abnormal 32: Encoder reverse fault 33~34: Reserved 35: User-defined fault 1 36: User-defined fault 2 37: Offload...
  • Page 70 Function Parameter Table VD530 Series Inverter User Manual Frequency Upon ● F9-13 the Second Time Fault Current Upon ● F9-14 the Second Time Fault Bus Voltage Upon the ● F9-15 Second Time Fault Input Terminal State Upon the ● F9-16...
  • Page 71 VD530 Series Inverter User Manual Function Parameter Table Power on Time ● F9-29 Upon the First Time Fault Running Time ● F9-30 Upon the First Time Fault Fault Automatic ○ F9-33 0~20 Reset Times Fault Automatic ○ F9-34 Reset Interval 0.1s~100.0s...
  • Page 72 Function Parameter Table VD530 Series Inverter User Manual 2: Continue to run Hundred’s digit: running time reached (27) 0: Coast to stop 1: Stop according to stop mode 2: Continue to run Thousand’s digit: speed deviation is too larg (40)
  • Page 73 VD530 Series Inverter User Manual Function Parameter Table 0: Run to the current running frequency Continue 1: Run at set frequency Running ○ F9-40 Frequency 2: Run at frequency upper limit Selection at 3: Run at frequency lower limit Failure 4: Run at abnormal standby frequency 60.0%~100.0%...
  • Page 74 Function Parameter Table VD530 Series Inverter User Manual PID Reverse ○ FA-08 Cut-off 0.00~max frequency 2.00Hz Frequency PID Deviation ○ FA-09 0.0%~100.0% 0.0% Limit PID Differential ○ FA-10 0.00%~100.00% 0.10% Limiting PID Given ○ FA-11 0.00s~650.00s 0.00s Change Time PID Feedback ○...
  • Page 75 VD530 Series Inverter User Manual Function Parameter Table PID Feedback 0.0%: Don’t judge feedback lost ○ FA-26 Lost Detection 0.0% 0.1%~100.0% Value PID Feedback ○ FA-27 Lost Detection 0.0s~20.0s 0.0s Time PID Feedback Lost Detection ○ FA-28 0.00Hz~max frequency 10.00Hz...
  • Page 76 Function Parameter Table VD530 Series Inverter User Manual Deceleration Time 1 and time ○ Fb-11 0.00Hz~max frequency 0.00Hz 2 Switching Frequency Point 0.00Hz: frequency hopping point is not Hopping valid ○ Fb-12 0.00Hz Frequency 1 0.01Hz~max frequency 0.00Hz: frequency hopping point is not...
  • Page 77 VD530 Series Inverter User Manual Function Parameter Table Any Frequency Reaching ○ Fb-23 0.00Hz~max frequency 50.00Hz Detection Value Any Frequency Reaching ○ Fb-24 0.0%~100.0% (max frequency) 0.0% Detection Amplitude 2 0.0%~300.0% Zero Current ○ Fb-25 5.0% 100.0% corresponding rated motor...
  • Page 78 Function Parameter Table VD530 Series Inverter User Manual Fb-38 Timing Run ○ Fb-38 0.0Min~65000.0Min 0.0Min Function Module ○ Fb-39 Temperature 0°C~100°C 75°C Reached Lower Limit of AI1 Input ○ Fb-40 0.00V~Fb-41 3.10V Voltage Protection Value Upper Limit of AI1 Input ○...
  • Page 79 VD530 Series Inverter User Manual Function Parameter Table ○ Fb-57 Actual Length 0m~65535m Number of Pulse ○ Fb-58 0.1~6553.5 100.0 per Meter ○ Fb-59 Set Count Value 1~65535 1000 Designated ○ Fb-60 1~65535 1000 Count Value 0: Disabled MS Speed ○...
  • Page 80 Function Parameter Table VD530 Series Inverter User Manual Multi-reference ○ FC-14 -100.0%~100.0% 0.0% Multi-reference ○ FC-15 -100.0%~100.0% 0.0% 0: Stop when single run end Simple PLC Run 1: Keep the final value when single run ○ FC-16 Mode 2: Always circulation Unit’s digit: power failure retentive...
  • Page 81 VD530 Series Inverter User Manual Function Parameter Table Run Time of ○ FC-26 Simple PLC 0.0s (h)~6553.5s (h) 0.0s (h) Reference 4 Acceleration/De celeration Time ○ FC-27 Selection of Simple PLC Reference 4 Run Time of ○ FC-28 Simple PLC 0.0s (h)~6553.5s (h)
  • Page 82 Function Parameter Table VD530 Series Inverter User Manual Run Time of ○ FC-38 Simple PLC 0.0s (h)~6553.5s (h) 0.0s (h) Reference 10 Acceleration/De celeration Time ○ FC-39 Selection of Simple PLC Reference 10 Run Time of ○ FC-40 Simple PLC 0.0s (h)~6553.5s (h)
  • Page 83 VD530 Series Inverter User Manual Function Parameter Table 0: s Simple PLC Run ○ FC-50 Time Unit 1: h 0: Coding FC-00 given 1: AI1 2: AI2 3: AI3 (expansion card) Multi-reference 0 ○ FC-51 4: PULSE Setting Method 5: PID...
  • Page 84 Function Parameter Table VD530 Series Inverter User Manual Communication 0: 0.01A ○ Fd-06 Read Current 1: 0.1A Resolution FF User Parameters Group Factory Function Parameter Setting Range Default Property Name Code Value ○ FF-00 User Password 0:~65535 0: No operation...
  • Page 85 VD530 Series Inverter User Manual Function Parameter Table Inverter Module ● FF-11 Radiator 0°C~120°C Temperature Accumulative ● FF-12 Power Time 0~65535h (time lock) Accumulative ● FF-13 Power 0°C~65535°C 0°C Consumption Accumulative ● FF-14 0h~65535h Run Time Accumulative ● FF-15 0h~65535h Power-on Time ☆...
  • Page 86 Function Parameter Table VD530 Series Inverter User Manual 0: Digital setting (A0-04) 1: AI1 Max Frequency 2: AI2 Source ◎ A0-03 Selection under 3: AI3 (expansion card) the Torque 4: PULSE Control Forward 5: Communication setting 6: Keypad potentiometer Max Frequency Digital Setting ○...
  • Page 87 VD530 Series Inverter User Manual Function Parameter Table High Frequency Torque ○ A0-13 0.0%~50.0% 3.0% Compensation Amount High Frequency Torque ○ A0-14 Compensation 0.00Hz~Max frequency 25.00Hz Frequency Upper Limit Rotational 0: Internal frequency Inertia ◎ A0-15 1: Feedforward frequency variation...
  • Page 88 Function Parameter Table VD530 Series Inverter User Manual DPWM Switching ○ A1-02 0.00Hz~15.00Hz 12.00Hz Frequency Upper Limit 0: Asynchronous modulation ○ A1-03 Modulation 1: Synchronous modulation Mode 0: Without compensation Dead Zone ○ A1-04 Compensation 1: Compensation 1 Mode Selection...
  • Page 89 VD530 Series Inverter User Manual Function Parameter Table A2 Motor 2 Parameters Factory Function Parameter Setting Range Default Property Code Name Value 0: Common Asynchronous motor Motor Type ◎ A2-00 1: Frequency conversion asynchronous Selection motor Rated Motor Model ◎...
  • Page 90 Function Parameter Table VD530 Series Inverter User Manual Encoder ◎ A2-21 0.0~359.9° 0.0° Mounting Angle Pole Pairs of ◎ A2-24 Rotary 1~1000 Tansformer Speed Feedcack 0.0: No action ◎ A2-25 0.0s Disconnection 0.1s~10.0s Detection Time 0: No operation ◎ A2-26...
  • Page 91 VD530 Series Inverter User Manual Function Parameter Table The full scale of option 1~7 corresponding A3-10 Torque Upper Limit Digital ○ A3-10 0.0%~200.0% 150.0% Setting in Speed Control Mode Excitation ○ A3-13 Regulation 0~60000 2000 Proportion Gain Excitation ○ A3-14...
  • Page 92 Function Parameter Table VD530 Series Inverter User Manual A4 Motor 2 V/F Control Parameters Factory Function Parameter Setting Range Default Property Code Name Value 0: Straight line V/F 1: Multipoint V/F 2: Square V/F 3: 1.2#power V/F V/F Curve ◎...
  • Page 93 VD530 Series Inverter User Manual Function Parameter Table 0: Digital setting (F4-14) 1: AI1 2: AI2 3: AI3 (expansion card) 4: PULSE setting The Separation ○ A4-14 of VF Voltage 5: MS instruction Source 6: Simple PLC 7: PID 8: Communication setting...
  • Page 94 Function Parameter Table VD530 Series Inverter User Manual ○ b0-14 User Code 14 FF-06 ○ b0-15 User Code 15 FF-06 ○ b0-16 User Code 16 FF-06 ○ b0-17 User Code 17 FF-06 ○ b0-18 User Code 18 FF-06 ○ b0-19...
  • Page 95 VD530 Series Inverter User Manual Function Parameter Table Virtual VDI5 Terminal ◎ b1-04 0~59 Function Selection Unit’s digit: virtual VDI1 0: By virtual VDOx state to decide VDI is valid or not 1: By code b1-06 setting VDI is valid or Virtual VDI Ten’s digit: virtual VDI2, same as above...
  • Page 96 Function Parameter Table VD530 Series Inverter User Manual 0: Short circuit with physical DIX internal Virtual VDO1 ○ b1-11 Output Function 1~43: see the F6 group physical DO Selection output selection 0: Short circuit with physical DIX internal Virtual VDO2 ○...
  • Page 97 VD530 Series Inverter User Manual Function Parameter Table VDO4 ○ b1-25 Disconnection 0.0s~3600.0s 0.0s Delay VDO5 ○ b1-26 Disconnection 0.0s~3600.0s 0.0s Delay b2 AI Curve Setting Factory Function Parameter Setting Range Default Property Code Name Value AI Curve 4 Min ○...
  • Page 98 Function Parameter Table VD530 Series Inverter User Manual Corresponding Setting of AI ○ b2-11 Curve 5 -100.0%~+100.0% -30.0% Inflection Point 1 Input AI Curve 5 ○ b2-12 Inflection Point 2 b2-10~b2-14 3.00V Input Corresponding Setting of AI ○ b2-13 Curve 5 -100.0%~+100.0%...
  • Page 99 VD530 Series Inverter User Manual Function Parameter Table AI2 Measured Factory ○ b3-04 0.500V~4.000V Voltage 1 Correction AI2 Displayed Factory ○ b3-05 0.500V~4.000V Voltage 1 Correction AI2 Measured Factory ○ b3-06 6.000V~9.999V Voltage 2 Correction AI2 Displayed Factory ○ b3-07 6.000V~9.999V...
  • Page 100 Function Parameter Table VD530 Series Inverter User Manual AO1 Current ○ b3-22 Correction 0.0~200.0% 100.0% Coefficient AO2 Current ○ b3-23 Correction 0.0~200.0% 100.0% Coefficient C0 Special Group of Tension Control Factory Function Parameter Setting Range Default Property Code Name Value...
  • Page 101 VD530 Series Inverter User Manual Function Parameter Table 0: Function code seting (C0-11) 1: AI1 2: AI2 Tension Set ◎ C0-10 Source 3: AI3 (expansion card) 4: Pulse input setting 5: Communication setting ○ C0-11 Tension Setting 0N~C0-12 0.0N Maximum ◎...
  • Page 102 Function Parameter Table VD530 Series Inverter User Manual Coil Diameter to ○ C0-23 Reach the Set 1mm~10000mm 500mm Value Coil Diameter 0: Memory when power down Power Down ○ C0-24 Memory 1: No memory when power down Selection Maximum ◎...
  • Page 103 VD530 Series Inverter User Manual Function Parameter Table Coil Diameter Calculation the 200.0m/mi ○ C0-36 0.1m/min~6000.0m/min Lowest Linear Velocity Automatic 0: Disabled Detection ○ C0-37 Selection of 1: Enabled Starved Feeding Automatic Detection ○ C0-38 Minimum 0.00Hz~F0-10 10.00Hz Frequency of...
  • Page 104 Function Parameter Table VD530 Series Inverter User Manual MS Torque 0: Disabled ○ C0-49 Calculation 1: Enabled Selection Torque ○ C0-50 0.0%~C0-08 0.0% Increment 1 Reeling and ○ C0-51 Unreeling Time 0s~C0-48 1000s Torque ○ C0-52 0.0%~C0-08 0.0% Increment 2 Reeling and ○...
  • Page 105 VD530 Series Inverter User Manual Function Parameter Table AI3 (expansion ● U0-11 0.01V card) Voltage (V) ● U0-12 Roll Diameter ● U0-13 Set Tension 0.1N ● U0-14 Thickness 0.001mm ● U0-15 PID Setting ● U0-16 PID Feedback ● U0-17 PLC Stage Input PULSE ●...
  • Page 106 Function Parameter Table VD530 Series Inverter User Manual Value ● U0-33 Reserved Surplus Running ● U0-35 0.1Min Time ● U0-36 Reserved Power Factor ● U0-37 0.1° Angle ● U0-38 ABZ position VF Separation ● U0-39 Target Voltage VF Separation ●...
  • Page 107: Chapter 6 Parameter Description

    VD530 Series Inverter User Manual Parameter Description Chapter 6 Parameter Description F0 Basic Function Led unit’s digit: motor 1 0: V/F control 1: SVC 2: FVC ◎ F0-00 Motor Control Mode 0x00 Led ten’s digit: motor 2 0: V/F control...
  • Page 108 Parameter Description VD530 Series Inverter User Manual 0: Digital setting(F0-09, UP/DOWN can be modified, no memory when power failure) 1: Digital setting(F0-09, UP/DOWN can be modified, memory when power failure) 2: AI1 3: AI2 Main Frequency 4: AI3 (expansion card) ◎...
  • Page 109 VD530 Series Inverter User Manual Parameter Description Frequency is given by terminal pulse setting. Pulse signal given specifications: voltage range 9V~30V and frequency range of 0kHz~100kHz. Pulse can only be given from multi-function input terminal HDI1 input. HDI1 terminal input pulse frequency and the corresponding set of relations, through the F5-37~F5-40 setting, the corresponding relations of 2 points of straight line, the corresponding set of input pulses 100.0%, is refers to the relative maximum frequency F0-10 percentage.
  • Page 110 Parameter Description VD530 Series Inverter User Manual Unit’s digit: frequency source selection 0: Main frequency source A 1: Main auxiliary operation result(operational relationship is determined by ten Bits) 2: Main frequency source A switching with auxiliary frequency source B Frequency Source 3: Main frequency source A switching with ○...
  • Page 111 VD530 Series Inverter User Manual Parameter Description Take the minimum absolute of main frequency A and auxiliary frequency B as the target frequency. In addition, when the frequency source selection for the main and auxiliary operation, can be set the offset frequency through F0-08, superimposed offset frequency on the main and auxiliary operation result in a flexible response to all kinds of needs.
  • Page 112 Parameter Description VD530 Series Inverter User Manual Frequency Upper Frequency lower limit F0-14~max frequency ○ F0-12 50.00Hz Limit F0-10 Frequency Upper ○ F0-13 0.00Hz~max frequency F0-10 0.00Hz Limit Offset When the frequency upper limit for analog or PULSE setting, F0-13 as the offset of set value, the offset frequency and F0-11 set frequency upper limit value superposition, as the final frequency upper limit set value.
  • Page 113 VD530 Series Inverter User Manual Parameter Description reference frequency (F0-21) deceleration to zero frequency, as show in figure 6-1 in the t2. Output frequency(Hz) Acceleration / deceleration reference frequency Set frequency Time(t) Actual acceleration Actual time deceleration time Set deceleration...
  • Page 114 Parameter Description VD530 Series Inverter User Manual 6: MS reference 7: Simple PLC 8: PID 9: Communication setting Ten’s digit: terminal command binding frequency source selection, same as above Hundred’s digit: communication command binding frequency source selection, same as above Thousand’s digit: Automatic operation...
  • Page 115: F1 Start/Stop Control Group

    VD530 Series Inverter User Manual Parameter Description F1 Start/Stop Control Group 0: Direct start ○ F1-00 Start Mode 1: Speed tracking restart 2: Pre excitation start (AC asynchronous ) 0: direct start If start dc braking time is set to 0, the frequency inverter starting run from start frequency.
  • Page 116 Parameter Description VD530 Series Inverter User Manual Starting DC Braking ◎ F1-03 Current/ Pre-excitation 0%~100% Current Starting DC Braking ◎ F1-04 Current/ Pre-excitation 0.0s~100.0s 0.0s Current Start the dc braking, generally used to make the running motor restart after stop. Pre excitation is used to make the asynchronous motor build magnetic field first then restart, improve the response speed.
  • Page 117 VD530 Series Inverter User Manual Parameter Description Stop DC Braking ○ F1-11 0%~100% Current ○ F1-12 Stop DC Braking Time 0.0s~100.0s 0.0s Initial frequency of stop dc braking: in the process of deceleration, when reduce the running frequency to the frequency, began to dc braking process.
  • Page 118 Parameter Description VD530 Series Inverter User Manual Used to run command source is terminal control. Enabled: when terminal run command has maintained, inverter will autostart after power on self-inspection normal and delay the time of F1-16. Disabled: when terminal run command has maintained, inverter will not autostart after power on self-inspection normal, only start when run command given again after disconnecting.
  • Page 119 VD530 Series Inverter User Manual Parameter Description Output frequency(Hz) Forward Reverse Dead-zone time Fig 6-3 Schematic diagram of forward/reverse dead-zoen time 0: Disabled Dynamic Braking ○ F1-22 Enable 1: Enabled ○ F1-23 Braking Usage Rate 0%~100% 100% Only be effective for the inverter that built-in braking unit.
  • Page 120 Parameter Description VD530 Series Inverter User Manual 1: S curve acceleration/deceleration A Output frequency increase or decrease according to the S curve. S curve is used in the pace with gentle start or stop demand, such as elevator, conveyor belt, etc. Function code F1-28 and F1-29 respectively defined the time scale of inertial stage and finish stage of S curve acceleration/deceleration.
  • Page 121 VD530 Series Inverter User Manual Parameter Description Output frequency(Hz) Set frequency(f) Rated frequency(f Time(t) S curve acceleration/deceleration B diagram Fig 6-4 S curve acceleration/deceleration diagram 0: No voltage output Zero Frequency 1: Voltage output ○ F1-30 Voltage Output 2: Output according to stop DC braking...
  • Page 122: F2 Motor 1 Parameter

    Parameter Description VD530 Series Inverter User Manual F2 Motor 1 Parameter 0: Ordinary asynchronous motor ◎ F2-00 Motor Type Selection 1: Frequency conversion asynchronous motor Model ◎ F2-01 Rated Motor Power 0.1kW~1000.0kW dependent Model ◎ F2-02 Rated Motor Voltage 1V~2000V dependent 0.01A~655.35A (Inverter power≤55kW)
  • Page 123 VD530 Series Inverter User Manual Parameter Description If the site can’t tuned for asynchronous motor, can according to the parameters given by motor manufacturer, input the above corresponding function code. ◎ F2-17 Encoder Line Number 1~65535 2000 Set ABZ or UVW incremental encoder pulse per number.
  • Page 124 Parameter Description VD530 Series Inverter User Manual parameters F2-00~F2-05. Asynchronous motor static tuning, inverter can obtain F2-06~F2-08 three parameters. Action description: set the function code to 1, and then press RUN key, inverter will conduct static tuning. 2: Asynchronous motor complete tuning In order to guarantee the dynamic control performance of the frequency inverter, please select complete tuning, the motor must disconnect with load, and to keep the motor for the idling condition.
  • Page 125: F3 Motor 1 Vector Control Parameter

    VD530 Series Inverter User Manual Parameter Description F3 Motor 1 Vector Control Parameter 01~100 Speed Loop ○ F3-00 Proportional Gain 1 Speed Loop Integral ○ F3-01 0.01s~10.00s 0.50s Time 1 ○ F3-02 Switch Frequency 1 0.00~F3-05 5.00Hz Speed Loop ○...
  • Page 126 Parameter Description VD530 Series Inverter User Manual Speed Loop Filter Time ○ F3-07 0.000s~0.100s 0.000s Constant Under the vector control mode, the output of the speed loop controller for torque current instruction, the parameter is used for filtering for torque instruction. Generally do not need to adjust the parameters, it can be appropriately increase the filtering time when speed is volatile;...
  • Page 127 VD530 Series Inverter User Manual Parameter Description Max Weak Magnetic ○ F3-20 1%~300% Current Weak Magnetic ○ F3-21 Automatic Gain 10%~500% 100% Adjustment Weak Magnetic ○ F3-22 2~10 Integral Multiples Change the F3-21 and F3-22 can change the adjustment speed of weak magnetic current, but weak magnetic current adjust faster could lead to instability, generally do not need to manually modify.
  • Page 128: F4 Motor 1 V/F Control Parameter

    Parameter Description VD530 Series Inverter User Manual F4 Motor 1 V/F Control Parameter This function code is only effective for V/F control, is invalid for vector control. V/F control is suitable for general load such as fan, water pump, or one inverter with more motor, or inverter power and motor power different applications.
  • Page 129 VD530 Series Inverter User Manual Parameter Description than the set frequency, torque boost failure, see below instructions. Output voltage Output frequency V1: manual torque boost voltage Vb: max output voltage V1:Manual torque boost voltage Vb:Max output voltage f1: manual torque boost cutoff frequency f1:Manual torque boost cutoff frequency...
  • Page 130 Parameter Description VD530 Series Inverter User Manual ◎ F4-10 VF Slip Compensation Gain 0.0%~200.0% 20.0% This parameter is only effective for asynchronous motor. V/F slip compensation gain: can compensate asynchronous motor caused motor speed deviation when the load increases, to make the speed of the motor can basically remained stable when the load changes.
  • Page 131 VD530 Series Inverter User Manual Parameter Description 5: MS instruction When voltage source for MS instruction, to set up the F5 and FC group parameters, to determine the corresponding relation of given signal and given voltage. 6: Simple PLC When voltage source for simple PLC, you need to set up the FC group parameters to determine given output voltage.
  • Page 132: F5 Input Terminal Group

    VD530 Series Inverter User Manual F5 Input Terminal Group VD530 series inverter with six multi-function digital input terminals (including HDI1 can be used as a high speed pulse input terminal), two analog input terminals. If the system needs more input and output terminals, the multi function input and output extension cards can be selected.
  • Page 133 VD530 Series Inverter User Manual Parameter Description Fig 6-10 Schematic diagram of two line mode 2 Three-line control mode 1: In this mode, Dln is enabled terminal, and the direction is controlled by DIx, DIy respectively. Terminal function set as below.
  • Page 134 Parameter Description VD530 Series Inverter User Manual SB1: Stop button SB2: Run button K: forward/reverse switchover Alternative control mode: this mode Din as enabled terminal, run and the rotating direction and stop are separately controlled by Din DIy alternatively. Terminal function as below:...
  • Page 135 VD530 Series Inverter User Manual Parameter Description DIn Back and forth control mode (FWD) (REV) Digital command end VicRuns External circuit Fig 6-14 Back and forth control mode DI1 Input Terminal ◎ F5-01 Function Selection DI2 Input Terminal ◎ F5-02...
  • Page 136 Parameter Description VD530 Series Inverter User Manual Fb-00, Fb-01, Fb-02 description. Reverse Jog(RJOG) Inverter block output, at present motor stop is not controlled by Coast to stop inverter. This method is the same as F1-08 described coast to stop. Inverter deceleration stop, but all run parameter is in memory state.
  • Page 137 VD530 Series Inverter User Manual Parameter Description eration time through the 4 states of two terminals. selection terminal 1 Acceleration/decel eration time selection terminal 2 PULSE frequency (Only effective for HDI1 as the function of the pulse input terminals. HDI1) Used to switch between the keypad control and terminal control.
  • Page 138 Parameter Description VD530 Series Inverter User Manual Swing frequency The inverter output at center frequency, swing frequency reset function valid. Make inverter switching between torque control and speed Switching between control. When the terminal is invalid, the inverter running on the speed control and defined mode of A0-00 (speed/torque control mode);...
  • Page 139 VD530 Series Inverter User Manual Parameter Description selection 1 the 4 kinds of coiled material is selected. Reference the sechdule 2 acceleration deceleration time to select terminal Thickness function instructions. selection 2 Number of When calculating the diameter of the coil by using the integral...
  • Page 140 Parameter Description VD530 Series Inverter User Manual Used to set the terminal UP/DOWN to adjust the setting frequency, the speed of frequency change, that is the frequency variation per second. When F0-15 (frequency decimal point) is 2, the value range is from 0.001Hz/s to 65.535Hz/s.
  • Page 141 VD530 Series Inverter User Manual Parameter Description The above function code is used to set the relationship between the analog input voltage and the setting value of the representative. When the analog input voltage is greater than the set ―maximum input‖ (F5-24), the analog voltage is caculated according to the ―Maximum input‖;...
  • Page 142 Parameter Description VD530 Series Inverter User Manual Corresponding Setting of ○ F5-35 -100.0%~+100.0% 100.0% AI Curve 3 Max Input AI3 (expansion card) ○ F5-36 0.00s~10.00s 0.10s Filter Time The function and using method of curve 3, please refer to the instructions of curve 1.
  • Page 143: F6 Output Terminal Function Group

    VD530 Series Inverter User Manual Parameter Description F6 Output Terminal Function Group 0: HS Pulse output HDO1 Terminals Output ○ F6-00 Mode Selection 1: Switch signal output HDO1 terminal is programmable multiplexing terminal. It can be used as high-speed pulse output terminal, it can also be used as collector open circuit output terminal.
  • Page 144 Parameter Description VD530 Series Inverter User Manual Frequency 1 Please refer to the instruction of function code Fb-21, Fb-22. reached output Frequency 2 Please refer to the instruction of function code Fb-23, Fb-24. reached output Zero speed running When frequency inverter is running and the output frequency is 1 (no output when 0, then output ON signal.
  • Page 145 VD530 Series Inverter User Manual Parameter Description Accumulative When frequency inverter accumulative running time more than running time reached the setting time of Fb-35, output ON signal. Accumulative When frequency inverter accumulative power-on time more power-on time than the setting time of Fb-35, output ON signal.
  • Page 146 Parameter Description VD530 Series Inverter User Manual Define HDO1 (digital output), relay 1, relay 2 and DO1 and DO5 (expansion card) output logic. 0: Positive logic, digital output terminal and the corresponding piplic end connected to valid state, disconnect as invalid state;...
  • Page 147 VD530 Series Inverter User Manual Parameter Description Length 0~maximum set length Count value 0~Max count value Communication 0.0%~100.0% setting Motor rotate speed 0~maximum output frequency corresponding rotate speed When≤55Kw, 100% corresponding 100.00A; when >55kW, Output current 100% corresponding 1000.0A Output voltage 0.0V~1000.0V...
  • Page 148 Parameter Description VD530 Series Inverter User Manual 0: Voltage ○ F6-26 AO1 Output Type 1: Current 0: Voltage ○ F6-27 AO2 Output Type 1: Current AO1 and AO2 there are two modes of voltage and current input, when In the selection of the corresponding input types of hardware, the parameters are selected as the same type.
  • Page 149: F7 Keyboard And Display Function Group

    VD530 Series Inverter User Manual Parameter Description F7 Keyboard and Display Function Group 0: Invalid 1: Operation panel command channel switching with remote command channel (terminal command channel or JOG / REV Key Function communication command channel) ◎ F7-00 Selection...
  • Page 150 Parameter Description VD530 Series Inverter User Manual Bit09: AI1 voltage (V) Bit10: AI2 voltage (V) Bit11: AI3 (expansion card) (V) Bit12: Coil diameter (mm) Bit13: Set tension (0.1N) Bit14: Thickness (0.001mm) BIT15: PID setting 0000~0xFFFF Bit00: PID feedback Bit01: PLC stage...
  • Page 151 VD530 Series Inverter User Manual Parameter Description AI2 voltage before Output torque (%) 0x0040 0x0040 correction (V) AI3 (expansion card) DI input state 0x0080 voltage before 0x0080 correction (V) DO output state 0x0100 Linear velocity 0x0100 Current power on time...
  • Page 152 Parameter Description VD530 Series Inverter User Manual Stop display parameter F7-04 corresponding table Corresponding display parameter Hexadecimal Set frequency (Hz on) 0x0001 Bus voltage (V on) 0x0002 Input terminal state 0x0004 Output terminal state 0x0008 PID given value (% flash)
  • Page 153: F8 Protection Parameters

    VD530 Series Inverter User Manual Parameter Description If the inverter in a stop state, the load speed display for set frequency corresponding to the speed, namely ―setting load speed‖. At a set frequency of 50.00Hz for example, the stop state load speed is: 50.00*2.000=100.00 (two decimal point display).
  • Page 154 Parameter Description VD530 Series Inverter User Manual capability. The biger the value is, the greater the inhibition of overvoltage ability is. On the premise of not occur overvoltage, the gain settings as small as possible. For small inertia load, the gain of the overvoltage stall is small is better, otherwise the system dynamic response is slow.
  • Page 155 VD530 Series Inverter User Manual Parameter Description detection levels F8-18 and duration time is greater than the offload detection time F8-19, the inverter output frequency decreased to 7% of the rated frequency automatically. During the offload protection, if the load recovery, then frequency inverter automatic recovery to run according to set ferquency.
  • Page 156 Parameter Description VD530 Series Inverter User Manual Instantaneous power voltage Instantaneous pick up judgment time power failure F8-26 judgment voltage Bus voltage F8-25 Instantaneous power failure action judgment voltage F8-27 Running frequency (F8-24=1:deceleration) Time Running frequency Deceleration time 1 Acceleration time 1 (F8-24=2:Decelerate to Stop time)...
  • Page 157: F9 Fault Record And Setting Parameter Group

    VD530 Series Inverter User Manual Parameter Description F9 Fault Record and Setting Parameter Group Fault Types for the First ● F9-00 Time Fault Types for the ● F9-01 0~43 Second Time Fault Types for the Third ● F9-02 Time (Last Time) Record recently three failure types of inverter, 0 is no fault.
  • Page 158 Parameter Description VD530 Series Inverter User Manual Inverter State Upon the ● F9-18 Second Time Fault Power on Time Upon the ● F9-19 Second Time Fault Running Time Upon the ● F9-20 Second Time Fault Frequency Upon the First ●...
  • Page 159 VD530 Series Inverter User Manual Parameter Description 0: Coast to stop 1: Stop according to stop mode 2: Continue to run Ten thousand’s digit: communication abnormal (18) 0: Coast to stop 1: Stop according to stop mode 2: Continue to run Unit’s digit: encoder / PG card abnormal...
  • Page 160 Parameter Description VD530 Series Inverter User Manual 2: Continue to run Thousand’s digit: offload (37) 0: Coast to stop 1: Stop according to stop mode 2: Decelerate to 7% of the rated motor frequency continue running, automatically restored to the set frequency operation when no offload Ten thousand’s digit: PID feedback lost...
  • Page 161: Fa Process Pid Parameter Group

    VD530 Series Inverter User Manual Parameter Description FA Process PID Parameter Group Process PID closed-loop control is the control mode in the control system using proportion (P), integral (I) and differential (D) controller of three parts, make the diviation between the feedback value and the instruction valueis gradually reduced, suitable for the flow rate, pressure, temperature and other process control.
  • Page 162 Parameter Description VD530 Series Inverter User Manual 0: Positive action ○ FA-03 PID Action Direction 1: Anti-action Positive action: when the feedback signal of PID is less than the quantitative, the output frequency of inverter is increased. Such as the tension control of the Coil situation.
  • Page 163 VD530 Series Inverter User Manual Parameter Description ○ FA-11 PID Given Change Time 0.00s~650.00s 0.00s PID given changes time, refers to the PID given value time needed from 0.0% to 100.0%. When PID given changes, PID given value according to the given time linear changes, reduce adverse effects caused by given mutations on the system.
  • Page 164 Parameter Description VD530 Series Inverter User Manual ○ FA-21 PID Initial Value 0.0%~100.0% 0.0% PID Initial Value Hold ○ FA-22 0.00s~650.00s 0.00s Time When the frequency converter starts up, the PID output is fixed to the PID initial FA-21, continuous PID initial value after holding time FA-22, PID to start the closed-loop adjustment operation.
  • Page 165: Fb Enhance Function Group

    VD530 Series Inverter User Manual Parameter Description with according to the selected fault processing method. PID Feedback Lost ○ FA-28 Detection Starting 0.00Hz~max frequency 10.00Hz Frequency 0: No operation when stop ○ FA-29 PID Stop Operation 1: Operation when stop Used to select the PID in stop condition, PID whether to continue operations.
  • Page 166 Parameter Description VD530 Series Inverter User Manual ○ Fb-09 Emergency Stop Time 0.0s~6500.0s 10.s When the DI function 30 is effective, the set time of Fb-09 will be delecerate to stop. Acceleration Time 1 and ○ Fb-10 time 2 Switching 0.00Hz~max frequency...
  • Page 167 VD530 Series Inverter User Manual Parameter Description Actual output frequency Hopping frequency range Hopping frequency range Set frequency Hopping frequency Fig 6-21 Schematic diagram of hopping frequency Hopping Frequency 0: Disabled Whether Valid in the ○ Fb-15 Process of 1: Enabled...
  • Page 168 Parameter Description VD530 Series Inverter User Manual Lagged Value (FDT2) When the running frequency is higher than the frequency detecion values, the frequency converter multi-function output DO output ON signal, and the frequency is lower than a certain frequency values of the detection values, the DO output ON signal is cancelled.
  • Page 169 VD530 Series Inverter User Manual Parameter Description Output frequency(Hz) Detection frequency range Time(t) Frequency reaching detection signal Fig 6-24 Schematic diagram of frequency reached detect amplitude Any Frequency Reaching ○ Fb-21 0.00Hz~max frequency 50.00Hz Detection Value 1 Any Frequency Reaching ○...
  • Page 170 Parameter Description VD530 Series Inverter User Manual Running frequency Frequency Any frequency detection range reaching Frequency detection range Time(t) Any frequency reaching detection DO or relay Fig 6-25 Schematic diagram of any frequency reaching detection 0.0%~300.0% Zero Current Detection ○...
  • Page 171 VD530 Series Inverter User Manual Parameter Description When the output current of the inverter is greater than or limit exceed detection point, and the duration is more than the software overcurrent point detection delay time, inverter multi-function DO output ON signal, the following figure is the output current limit exceed function diagram.
  • Page 172 Parameter Description VD530 Series Inverter User Manual Accumulative Power-on ○ Fb-34 0h~65535h time Reached Used to set the inverter power on time. When the accumulative power on time (FF-15) reached the setting accumulative power on time, frequency converter multi-function digital DO output ON signal.
  • Page 173 VD530 Series Inverter User Manual Parameter Description This set of parameters are used to realize the dormancy and wakeup function in water supply applications. In the running process of frequency converter, when setting frequency less than or equal to Fb-44 dormancy frequency, after Fb-45 delay time, frequency converter to enter a dormant state, and automatically stop.
  • Page 174 Parameter Description VD530 Series Inverter User Manual 1: relative maximum frequency (F0-10), as the swing system, swing fixed. Swing Frequency ○ Fb-52 0.0%~100.0% 0.0% Amplitude Jumping Frequency ○ Fb-53 0.0%~50.0% 0.0% Amplitude Through this parameter to determine the value of the amplitude and jumping frequency.
  • Page 175 VD530 Series Inverter User Manual Parameter Description Number of Pulse per ○ Fb-58 0.1~6553.5 100.0 Meter The above function code is used to fixed-length control. Length information need to be collect by the multi-function digital input terminals, terminal sampling pulse number and the number of pulses per meter Fb-58 division, can calculate the actual length Fb-57.
  • Page 176 Parameter Description VD530 Series Inverter User Manual FC Multi-reference and Simple PLC Parameters Group ○ FC-00 Multi-reference 0 -100.0%~100.0% 0.0% ○ FC-01 Multi-reference 1 -100.0%~100.0% 0.0% ○ FC-02 Multi-reference 2 -100.0%~100.0% 0.0% ○ FC-03 Multi-reference 3 -100.0%~100.0% 0.0% ○ FC-04 Multi-reference 4 -100.0%~100.0%...
  • Page 177 VD530 Series Inverter User Manual Parameter Description Output frequency Time Time MS terminal 1 Time MS terminal 2 Time MS terminal 3 Time MS terminal 4 Fig 6-32 Multistage speed operation schematic diagram Schedule 2 is function instruction of multi-reference.
  • Page 178 Parameter Description VD530 Series Inverter User Manual Multi-reference in addition to as a multistage speed function, also can be a given source of PID, or as a voltage source of V/F separation control etc., to meet the demand of the need of switching between different given values.
  • Page 179 VD530 Series Inverter User Manual Parameter Description Unit’s digit: power failure retentive selection 0: Non-retentive at power failure Simple PLC Power 1: Retentive at power failure ○ FC-17 Failure Retentive 0x00 Selection Ten’s digit: stop retentive selection 0: Non-retentive at stop...
  • Page 180 Parameter Description VD530 Series Inverter User Manual Acceleration/Deceleratio ○ FC-31 n Time Selection of Simple PLC Reference 6 Run Time of Simple PLC ○ FC-32 0.0s (h)~6553.5s (h) 0.0s (h) Reference 7 Acceleration/Deceleratio ○ FC-33 n Time Selection of Simple PLC Reference 7 Run Time of Simple PLC ○...
  • Page 181: Fd Communication Parameter Group

    VD530 Series Inverter User Manual Parameter Description Simple PLC Reference Run Time of Simple PLC ○ FC-48 0.0s (h)~6553.5s (h) 0.0s (h) Reference 15 Acceleration/Deceleratio n Time Selection of ○ FC-49 Simple PLC Reference 0: s Simple PLC Run Time ○...
  • Page 182: Ff User Parameters Group

    Parameter Description VD530 Series Inverter User Manual FF User Parameters Group ○ FF-00 User Password 0:~65535 FF-00 set any non-zero number, and then the password protection function will be enabled. When enter the menu next time, must input password correctly, otherwise can’t view and modify the function parameters, please keep in mind that the user password is set.
  • Page 183 VD530 Series Inverter User Manual Parameter Description Unit’s digit: user custom parameter group display selection 0: Not display 1: Display ○ FF-05 Fast Debugging Setting 0x10 Ten’s digit: user change parameter group display selection 0: Not display 1: Display When F7-00 selection for 5 (fast debugging) function, to set open or close the JOG/REV key by FF-05 can switch of three kinds of parameters display.
  • Page 184: Fp Factory Parameter Group

    Parameter Description VD530 Series Inverter User Manual Date of Production Factory ● FF-10 0~31 (Date) Setting Product information. Inverter Module Radiator ● FF-11 0°C~120°C Temperature Inverter module temperature. Accumulative Power ● FF-13 0°C~65535°C 0°C Consumption Show the inverter accumulative power consumption so far.
  • Page 185: A0 Motor 1 Torque Control Parameter Group

    VD530 Series Inverter User Manual Parameter Description A0 Motor 1 Torque Control Parameter Group 0: Speed control Speed/Torque Control ◎ A0-00 Mode Selection 1: Torque control Used to select the inverter control mode: speed control or torque control. VD530’s multi-function digital DI terminal, have two function associated with torque control: torque control prohibit (function 40), speed control/torque control switch (function 39).
  • Page 186 Parameter Description VD530 Series Inverter User Manual Max Frequency Digital 50.00H ○ A0-04 Setting under the Torque 0.00Hz~max frequency Control Forward 0: Digital setting (A0-06) 1: AI1 2: AI2 Max Frequency Source ◎ A0-05 Selection under the 3: AI3 (expansion card)
  • Page 187 VD530 Series Inverter User Manual Parameter Description High Frequency Torque ○ A0-13 0.0%~50.0% 3.0% Compensation Amount High Frequency Torque ○ A0-14 Compensation 0.00Hz~Max frequency 25.00Hz Frequency Upper Limit The related parameters of the torque compensation, torque compensation for low frequency and high frequency, stable output.
  • Page 188: Ai Optimize Control Parameter Group

    Parameter Description VD530 Series Inverter User Manual AI Optimize Control Parameter Group Carrier Model ○ A1-00 0.5kHz~16.0kHz Frequency dependent This function is used to adjust the carrier frequency of the inverter. By adjusting the carrier frequency can reduce motor noise and avoid the resonance point of mechanical system, reduce the line of floor drain current and reducing interference caused by frequency inverter.
  • Page 189 VD530 Series Inverter User Manual Parameter Description 0: Asynchronous modulation ○ A1-03 Modulation 1: Synchronous modulation Mode Only valid for V/F control. Synchronization modulation, refers to the carrier frequency linear changes with the output frequency change to ensure that both ratio (carrier ratio) not chance, generally used in the output frequency is higher, is conductive to the quality of the output voltage.
  • Page 190: A2, 3, 4 Motor 2 Parameter Function Group

    Parameter Description VD530 Series Inverter User Manual Dead Zone Time ○ A1-09 100%~200% 150% Adjustment Aimed at 1140V voltage level setting. Adjustment this value can improve the effective utilization of voltage, adjustment is too small easy to cause system unstable.
  • Page 191: User Customize Function Code

    VD530 Series Inverter User Manual Parameter Description User Customize Function Code ○ b0-00 User Code 0 F0-00 ○ b0-01 User Code 1 F0-01 ○ b0-02 User Code 2 F0-02 ○ b0-03 User Code 3 F0-09 ○ b0-04 User Code 4 F0-18 ○...
  • Page 192: B1 Virtual Io Parameter Group

    Parameter Description VD530 Series Inverter User Manual ○ b0-30 User Code 30 FF-06 ○ b0-31 User Code 31 FF-06 This function code is the users customize parameter group. Users can in all VD530 function code, select the needed parameter summary to b0 group, as the user customization parameters, convenient to view and change such as operation.
  • Page 193 VD530 Series Inverter User Manual Parameter Description Unit’s digit: virtual VDI1 0: Disabled 1: Enabled Ten’s digit: virtual VDI2, same as above Virtual VDI Terminal ◎ b1-06 0x00000 Hundred’s digit: virtual VDI3, same as state setting above Thousand’s digit: virtual VDI4, same as above Ten thousand’s digit: virtual VDI5,...
  • Page 194 Parameter Description VD530 Series Inverter User Manual 1: Low electrical level enable Ten’s digit: AI2, same as above Hundred’s digit: AI3, same as above As the group function code is used to AI used as DI, when AI used as DI, when the AI input voltage is greater than 7V, AI terminal state for high level, when the AI input voltage is lower than 3V, AI terminal state for low level.
  • Page 195 VD530 Series Inverter User Manual Parameter Description VDO2 Output Delay ○ b1-17 0.0s~3600.0s 0.0s Time VDO3 Output Delay ○ b1-18 0.0s~3600.0s 0.0s Time VDO4 Output Delay ○ b1-19 0.0s~3600.0s 0.0s Time VDO5 Output Delay ○ b1-20 0.0s~3600.0s 0.0s Time Unit’s digit: VDO1...
  • Page 196: B2 Ai Curve Setting Parameter Group

    Parameter Description VD530 Series Inverter User Manual b2 AI Curve Setting Parameter Group ○ b2-00 AI Curve 4 Min Input -10.00V~b2-02 0.00V Corresponding Setting of ○ b2-01 -100.0%~+100.0% 0.0% AI Curve 4 Min Input AI Curve 4 Inflection ○ b2-02 b2-00~b2-04 3.00V...
  • Page 197 VD530 Series Inverter User Manual Parameter Description Analog input corresponding setting 100% AI Max input setting AI curve inflection point 1 corresponding setting AI curve AI input inflection point 2 voltage 0V(0mA) AI curve AI curve inflection point 1 (20mA)...
  • Page 198: B3 Aiao Correction Parameter Group

    Parameter Description VD530 Series Inverter User Manual b3 AIAO Correction Parameter Group Factory ○ b3-00 AI1 Measured Voltage 1 0.500V~4.000V Correction Factory ○ b3-01 AI1 Displayed Voltage 1 0.500V~4.000V Correction Factory ○ b3-02 AI1 Measured Voltage 2 6.000V~9.999V Correction Factory ○...
  • Page 199 VD530 Series Inverter User Manual Parameter Description Factory ○ b3-16 Target Voltage 1 Of AO2 0.500V~4.000V Correction Factory ○ b3-17 AO2 Measured Voltage 1 0.500V~4.000V Correction Factory ○ b3-18 AO2 Target Voltage 2 6.000V~9.999V Correction Factory ○ b3-19 AO2 Measured Voltage 2 6.000V~9.999V...
  • Page 200: C0 Special Group Of Tension Control

    Parameter Description VD530 Series Inverter User Manual C0 Special Group of Tension Control 0: Prohibit Tension ◎ C0-00 Control 1: Tension closed loop speed control Mode 2: Tension open loop vector control Using this parameter to select the tension control mode: 0: Prohibit: tension control is invalid, the inverter is basically the same as the general inverter.
  • Page 201 VD530 Series Inverter User Manual Parameter Description F0-00=01 Open loop vector control F0-01=1 Terminal command F0-10=70.00Hz Maximum frequency F0-12=70.00Hz Frequency upper limit F1-08=1 Coast to stop F5-01=1 DI1: forward running F5-02=57 DI2: coil diameter reset F5-05=8 DI5: fault reset C0-00=2:...
  • Page 202 Parameter Description VD530 Series Inverter User Manual Empty 0: Function code setting (C0-06) Salver 1: AI1 ◎ C0-05 Setting 2: AI2 Source Selection 3: AI3 (expansion card) Empty Salver ○ C0-06 0.0~200.0% 0.0% Torque Setting Setting mode of empty salver torque.
  • Page 203 VD530 Series Inverter User Manual Parameter Description 0: Linear velocity method 1: AI1 Coil 2: AI2 Diameter ◎ C0-13 Calculation 3: AI3 (expansion card) Method 4: Strip thickness cumulative method 5: Wire thickness cumulative method The function code to selection coil diameter calculation method. In tension control system, it is very important to calculatie the coil diameter, and it can achieve the higher precision tencion control only by getting accurate coil diameter.
  • Page 204 Parameter Description VD530 Series Inverter User Manual Initial Winding ○ C0-16 1mm~10000mm 100mm Diameter 1 (Diameter) Initial Coil ○ C0-17 Diameter 2 1mm~10000mm 100mm (Diameter) Initial Coil ○ C0-18 Diameter 3 1mm~10000mm 100mm (Diameter) 0: Empty salver diameter Initial Coil...
  • Page 205 VD530 Series Inverter User Manual Parameter Description Coil Diameter to ○ C0-23 1mm~10000mm 500mm Reach the Set Value Set the DO output function to 45 (set the coil diameter to arrrive), when the coil diameter calculated to achieve this value, DO has been output ON signal.
  • Page 206 Parameter Description VD530 Series Inverter User Manual Number of ◎ C0-32 Pulse per 1~30000 Cycle Refers to the material around a layer, the number of turns of the reel, generally used for wire. Number of 0: Frequncy Computatio ◎ C0-33...
  • Page 207 VD530 Series Inverter User Manual Parameter Description Automatic Detection ○ C0-40 Filter Time 0.1s~60.0s 2.0s of Starved Feeding This set of parameter used to inverter automatic detection srarved feeding. C0-37: set to 1, the automatic detection function of starved feeding detection opened;...
  • Page 208 Parameter Description VD530 Series Inverter User Manual between taper inflection point 1 and taper inflection point 2 for two sets of rolling taper linear switch. Disful 0: Function code setting (C0-07) Torque 1: AI1 ◎ C0-47 Increment 2: AI2 Source...
  • Page 209: Chapter 7 Emc Guide

    VD530 Series Inverter User Manual EMC Guide Chapter 7 EMC Guide 7.1 Definition Electromagnetic compatibility is the ability of the electric equipment to run in the electromagnetic interference environment and implement its function stably without interferences on the electromagnetic environment.
  • Page 210 EMC Guide VD530 Series Inverter User Manual placed nearby the inverter or together with the inverter in the same control cabinet, they are easy to suffer interference and thus generate error actions. It is recommended to handle with the following methods: Put in places far away from the interference source;...
  • Page 211: Chapter 8 Fault Shooting And Solutions

    VD530 Series Inverter User Manual Fault Shooting and Solutions Chapter 8 Fault Shooting and Solutions 8.1 Fault Alarm and Countermeasures VD530 inverter has warning information and fault protection function. In case of abnormal fault, the inverter error relay contactor will be in action, before user seeking for help, please do self-inspection according to this chapter to analyze causes and find out solution.
  • Page 212 Fault Shooting and Solutions VD530 Series Inverter User Manual 1. Extend deceleration time 1. Deceleration time is too short Deceleration 2. Add external energy Err.05 overcurrent 2. Load inertia torque is too big consumption braking unit (software) 3. Inverter power is too small 3.
  • Page 213 VD530 Series Inverter User Manual Fault Shooting and Solutions 1. Whether the load is too large 1. Reduce the load and check the Inverter or motor stalling motor and mechanical conditions Err.12 overload 2. Small frequency converter 2. Selection inverter with bigger...
  • Page 214 Fault Shooting and Solutions VD530 Series Inverter User Manual 1. The abnormal change of the Starved coil diameter caused by the 1. Check whether the starved feeding straved feeding Err.22 feeding, if straved feeding, it will be detection resumed. 2. No use line speed calculation...
  • Page 215: Common Faults And Solutions

    VD530 Series Inverter User Manual Fault Shooting and Solutions 1. In the process of inverter Switch motor running through the terminal to 1. Switch motor operation after Err.39 when running change the current motor inverter stop selection 1. Correctly set the encoder 1.
  • Page 216: Chapter 9 Communication Protocol

    (PC), industrial control machine or programmable logical controller(PLC) etc., and the slave refers to the VD530 series inverter or other control equipment with the same communication protocol. Master not only visits some slave, but also sends the broadcast information to all the slaves.
  • Page 217: Command Code And Communication Data Description

    VD530 Series Inverter User Manual Communication Protocol times marks the end of the message. A new message can begin after this interval) The entire message frame must be transmitted as a continuous stream. If a silent interval of more than 1.5 character times occurs before completion of the frame, the receiving device flushes the incomplete message and assumes that the next byte will be the address field of a new message.
  • Page 218 Communication Protocol VD530 Series Inverter User Manual START T1-T2-T3-T4 ADDR Bit number Output frequency high Bit xx H Output frequency low Bit xx H Setting frequency high Bit xx H Setting frequency low Bit xx H Motor run speed high Bit...
  • Page 219 VD530 Series Inverter User Manual Communication Protocol CRC CHK high Bit xx H T1-T2-T3-T4 9.6.2 Command Code: 06H (0000 0110), write one word Such as: Put 5000 (1388H) (namely write-in setting frequency 50.00Hz) write to slave address 01H inverter 3001H (communication set frequency address). The frame structure description as below: RTU Master command information.
  • Page 220 Communication Protocol VD530 Series Inverter User Manual to Keeping the parity of the data unchanged. For example, the transmitting data ―11001110‖, there is 5 ―1‖ in the data, if using even parity check, the even check Bit is ―1‖, if using odd parity check, the odd check Bit is ―0‖, when transmitting, the parity check Bit will be processed and put at the position of format check Bit.
  • Page 221 VD530 Series Inverter User Manual Communication Protocol the use of manufacturers or monitoring) : Function code parameter address label rules: By function block number and the label for the parameter address said rules: High byte: F0 ~ FF (group F), A0 - AF (group A), 70-7 F (U) low byte: 00 to FF Such as: F3-12, address represented as F30C;...
  • Page 222 Communication Protocol VD530 Series Inverter User Manual 1019H Linear speed 101AH Current power on time 101BH current running time 101CH PULSE input pulse frequency, unit 1Hz 101DH Communication set value 101EH Reserved 101FH Main frequency X display Auxiliary frequency Y display...
  • Page 223 VD530 Series Inverter User Manual Communication Protocol Pulse output control: (only write) Command Address Command Content 2002H 0~7FFF indicate 0%~100% Inverter fault description: Inverter fault address Inverter fault information 0000H: no fault 0001H: acceleration over current (hardware) 0002H: deceleration over current (hardware)
  • Page 224: Fd Communication

    Communication Protocol VD530 Series Inverter User Manual 0004: invalid address 0005: invalid parameter 0006: parameter change is invalid 0007: system is lock 0008: EEPROM operation Fd Communication 0: 300BPS 1: 600BPS 2: 1200BPS 3: 2400BPS 4: 4800BPS ○ Fd-00 Baud Rate...
  • Page 225 VD530 Series Inverter User Manual Communication Protocol 0: Non standard MODBUS protocol Data Transfer Format ○ Fd-05 Selection 1: Standard MODBUS protocol Fd - 05 = 1: choose the standard Modbus protocol. Fd - 05 = 0: read command, from the machine returns number of bytes is more than the standard Modbus protocol a byte, specific see "communications data structures"...
  • Page 226: Appendix A Multi-Function I/O Extension Card

    VD530 Series Inverter User Manual Appendix A Multi-function I/O Extension Card VD530 series inverter support multi-function I/O extension card. There have 3 DI input terminal, 1 DO output terminal and 1 AI input terminal in multi-function I/O extension card. Multi-function extension card and installation diagram as show below: 1.After dismantling the original...
  • Page 227 VD530 Series Inverter User Manual Appendix A Multi-function I/O Extension Card A.2 Socket Function Description Table A-1 Socket function description Socket Code Function Function Description Multi-function J20 is connection port of main control board and power board, I/O extension control board supply power to multi-function I/O extension card card –...
  • Page 228: Appendix B Incremental Pg Card

    Appendix B Incremental PG Card VD530 Series Inverter User Manual Appendix B Incremental PG Card VD530 series inverter support close-loop vector control, incremental PG card, the model is: V5GT005PG3Y0. Separate dial any of a set of dialswitch to realize frequency division output: S1, S2, S3, S4 corresponding 2,4,6,8,16 frequency division 1.After dismantling the original...
  • Page 229 VD530 Series Inverter User Manual Appendix B Incremental PG Card Frequency division difference signal OA+, OA- 0~300kHz output terminal Frequency division difference signal OB+, OB- 0~300kHz output terminal Difference open collector output OA, OB 0~300kHz terminal Output terminal 5. Dial switch introduction: PG card frequency division coefficient determined by dial the code switch on the card.
  • Page 231 3. If there is any failure or damage to the product, please correctly fill out the Product Warranty Card in detail. 4. The maintenance fee is charged according to the latest Maintenance Price List of Vicruns. 5. The product Warranty Card is not re-issued. Please keep the card and present it to the maintenance personnel when asking for maintenance.
  • Page 232 Product Warranty Card Address: Contact Person: Customer Company Name: Information Tel of Email: Postcode: Product Model: Product Serial No: Information Name of supplier who supplied you the unit: Failure Description (eg. Fault code) Maintenance Personnel:...