Haier AD35S2SM3FA Operation Manual And Installation Manual page 12

Duct type air conditioner
Hide thumbs Also See for AD35S2SM3FA:
Table of Contents

Advertisement

The machine is adaptive in following situation
1. Applicable ambient temperature range:
Indoor temperature
Cooling
Outdoor temperature
Indoor temperature
Heating
Outdoor temperature
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T5.0/250V(for series AD35/
50/71S2SM3/4FA)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
2
H05RN-F 3G 4.0mm
The connecting cable should be:
2
H05RN-F 4G 2.0mm
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10. For AD35S2SM3FA/AD35S2SM4FA/AD50S2SM3FA/AD50S2SM4FA/AD71S2SM3FA ,we can get the 10 different ESP
through adjust wired controllerYR-E17,please refer below:
Stactic pressure
1
grade
Stactic pressure
25Pa
Adjsutment metchod bywired controller YR-E17: In the state of ON and non screen saving state, press Fan+ Set keys for
5s to enter static pressure grade adjustmentstate with static pressure icon flashing and current staticpressure grade
statically displaying. Press key↑↓ to changestatic pressure grade, then press Set key to confirm.
Details please refer to wired controller operation & installation manual.
Adjsutment metchod by Infrared remote controller+Infrared receiver RE-02:Step a:set the Infrared remote controller at
condition: FAN mode ,fan speed high Step b:then aim the remote controller at the infrared remote receiver RE-02,
press HEALTH button 4+N times(1≤N≤10,integer)within 12 seconds ,then the receiver will beep N+1 times ,the
static pressure level N is been set successfully.
Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller's at OFF status first, then
open the button cover press FRESH button will enter FAN mode interface.
max. DB/WB
32/23 C
min. DB/WB
18/14 C
max. DB/WB
46/26 C
min. DB/WB
10/6 C
max. DB/WB
min. DB/WB
max. DB/WB
24/18 C
min. DB/WB
;
2
3
37Pa
50Pa
27 C
15 C
-15 C
5
4
70Pa
90Pa
100Pa
AD35S2SM3FA AD35S2SM4FA
AD50S2SM3FA AD50S2SM4FA
AD71S2SM3FA AD71S2SM4FA
10
7
8
6
110Pa
120Pa
9
10
130Pa
150Pa

Advertisement

Table of Contents
loading

Table of Contents