Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 35-3001A-04-03, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 35-3001A-04-03 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 35-3001A-04-03 as described in this manual.
Page 8
A ball in the flowmeter column indicates the flow rate to the sensor. The flowmeter measures the flow in the range 0.2 to 2.0 SCFH (Standard Cubic Feet per Hour). The optimum flow rate is 1.0 SCFH. 8 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Page 9
A charcoal filter is located between the amplifier and the flow block. It scrubs out interfering gases which may cause the CO sensor to respond, such as H S or certain hydrocarbons. Replace the charcoal filter when false high CO readings are noticed, especially in the presence of H 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector • 9...
Page 10
Rubber Boot and Spacer A rubber boot and spacer are installed on the sensor. They help ensure that the detector remains plugged into the detector housing body. 10 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Page 11
The black test point in the lower left corner is the negative (-) test point and the red test point below the zero pot is the positive (+) test point. 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector • 11...
1/4” O.D. rigid polypropylene, Teflon, or flexible polyurethane tubing may be used. RKI Instruments, Inc. recommends using either 1/4” O.D. x 1/8” I.D. or 1/4” O.D. x 0.170” I.D. tubing based on your length requirements. See “Specifications” on page 5 for maximum tubing lengths based on tubing size.
Push 1/4” O.D. rigid polypropylene or rigid Teflon sample tubing into the fitting until it stops. Flexible polyurethane tubing may be used with an appropriate insert. RKI Instruments, Inc. recommends using either 1/4” O.D. x 1/8” I.D. or 1/4” O.D. x 0.170” I.D. tubing based on your length requirements.
Page 15
Connect the wires to the applicable detector/transmitter terminal strip at the controller as shown in Figure 6. Refer to the controller operator’s manual and the controller detector head specification sheet for the 35-3001A-04-03 for detector/terminal strip connections specific to the controller.
Enable alarms or place the controller in normal operation. CAUTION: Allow the sample-draw detector to warm up for 5 minutes before you continue with the next section, “Setting the Zero Reading.” 16 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Alternatively, the contacts could be used to power a device that does not exceed the relay contact ratings below. The ratings are for a resistive load. Table 3: Low Flow Relay Specifications Voltage Amps 125 VAC 0.6 A 30 VDC 110 VDC 0.6 A 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector • 17...
Controller” on page 14 describes sensor wiring connections. Calibrate the sample-draw detector as described in “Calibration” on page 25. If the fail condition continues, replace the sensor as described in “Replacing Components of the Sample-Draw Detector” on page 20. 18 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Page 19
If the fail condition continues, contact RKI Instruments, Inc. for further instruction. Slow or No Response/Difficult or Unable to Calibrate Symptoms • The sensor responds slowly or does not respond during the monthly response test. • Unable to accurately set the zero or response reading during the calibration procedure.
NOTE: If installing a new plug-in sensor along with a new detector housing body, be sure to move the rubber boot and spacer from the old plug-in sensor to the new plug-in sensor. Screw the new detector housing body back into the flow block. 20 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
Page 21
Pull the charcoal filter away from the main circuit board so that it is easier to access. Disconnect the filter from the rubber elbows on each end of the filter, then remove the filter from the sample-draw detector. 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector • 21...
Page 22
Install the new particle filter onto the tubing stub. Be sure the arrow on the particle filter is pointing toward the inlet line. Turn on power to the controller. Turn on the controller. 22 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
If the low flow alarm is set too high, turn the pressure switch adjustment screw slightly clockwise. Repeat steps 3 and 4 if necessary. Use the sensor flow control valve to set the flow to 1.0 SCFH. Make sure the sample-draw detector’s Fail LED is off. 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector • 23...
Screw the inlet fitting tube nut back onto the fitting body. See “Connecting the Sample Lines to the Sample-Draw Detector” on page 13 for instructions to install a new piece of tubing into the fitting. 24 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
3 months is adequate for most carbon monoxide sample draw detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months for the carbon monoxide sample draw detector.
Remove the voltmeter leads from the amplifier test points. Close the housing door. Follow the instructions in the controller’s operator’s manual to exit the calibration mode. Store the components of the calibration kit in a safe and convenient place. 26 • 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector...
65-2408 CO replacement detector housing body (does not include plug-in sensor, rubber boot, or spacer) 71-0476 Operator’s Manual, 35-3001A-04-03 Carbon Monoxide Sample-Draw Detector 81-0064RK-01 Calibration cylinder, 50 ppm CO in air, 34 liter steel 81-0064RK-03 Calibration cylinder, 50 ppm CO in air, 103 liter...