Section 2. Unit Location Considerations

2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models
H x W x D (in)
A4AC6018A
28.6 X 23.6 X 23.6
A4AC6024A
28.6 X 25.6 X 25.6
A4AC6030A
28.6 X 29.8 X 29.8
A4AC6031A
36.6 X 29.8 X 29.8
A4AC6036A
32.6 X 29.8 X 29.8
A4AC6037A
36.6 X 34.3 X 34.3
A4AC6042A
44.6 X 34.3 X 34.3
A4AC6048A
44.6 X 34.3 X 34.3
A4AC6060A
44.6 X 34.3 X 34.3
* Weight values are estimated.
When mounting the outdoor unit on a roof, be
sure the roof will support the unit's weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
4
Weight* (lb)
130
134
163
184
161
212
252
256
277
W
H
D
Standard
Line Set
60' Max
Line Length
88-A4AC6001-1E-EN