QC SERIES WATER SOURCE GENERAL INFORMATION

QC Model Nomenclature

QC
50
Model Number
QC - Q-TEC™ Model
Capacity
50 - 4 ton
Volts & Phase
A - 230/208-60-1
K - 115-60-1
L - 277-60-1
NOTE 1: Electric heat available
for -A models only
No.
Rated
Field
Volts &
Power
Models
Phases
Circuits
QC501-A0Z
-A05
230/208-1
-A10
-A15
1 or 2
QC501-K0Z
115-1
QC501-L0Z
277-1
 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual 2100-416L
Page
4 of 29
1 – A
10
KW
0Z - 0 KW
05 - 5 KW
Revision
10 - 10 KW
15 - 15 KW
(NOTE 1)
Ventilation Option
B - Blank Off Plate (no ventilation)
X - Barometric Fresh Air Damper (no exhaust)
V - Commercial Ventilator (w/Exhaust)
P - Commercial Ventilator (w/Exhaust) Motorized, Power Return
R - Energy Recovery Ventilator (w/Exhaust) - 230/208-60-1 versions only
Factory Built-in Electric Heat Table
Models
KW
5.0
10.0
15.0
Electrical Specifications
SINGLE CIRCUIT
Maximum
External
Minimum
Fuse or
Circuit
Circuit
Ampacity
Breaker
1
7
15
1
33
35
1
58
60
83
90
1
10
15
1
6.5
10
X
X
X
Filter Options
X - 1" Fiberglass
(Standard)
F - 2" Fiberglass
P - 2" pleated
Color
V - Platinum w/Slate
Front (vinyl)
4 - Gray Paint
TABLE 1
QC501-A
240V-1
208V-1
BTUH
BTUH
16,380
12,290
32,670
24,570
49,150
36,860
TABLE 2
Minimum
Circuit
Field
Ampacity
Power
Ground
Wire
Wire
CKT
CKT
Size
Size
A
B
14
14
8
10
6
10
4
8
50
33
14
14
14
14
X
X
X
Valve Options
4 - 2-way valve
5 - 3-way valve
Internal Controls
X - None
Climate Control
X - None
D - Electronic/prog/man/auto
DUAL CIRCUIT
Maximum
External
Field
Fuse or
Power
Circuit
Wire
Breaker
Size
CKT
CKT
CKT
CKT
CKT
A
B
A
B
A
50
40
8
8
10
Ground
Wire
Size
CKT
B
10