QC SERIES WATER SOURCE GENERAL INFORMATION
QC Model Nomenclature
QC
50
Model Number
QC - Q-TEC™ Model
Capacity
50 - 4 ton
Volts & Phase
A - 230/208-60-1
K - 115-60-1
L - 277-60-1
NOTE 1: Electric heat available
for -A models only
No.
Rated
Field
Volts &
Power
Models
Phases
Circuits
QC501-A0Z
-A05
230/208-1
-A10
-A15
1 or 2
QC501-K0Z
115-1
QC501-L0Z
277-1
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Manual 2100-416L
Page
4 of 29
1 – A
10
KW
0Z - 0 KW
05 - 5 KW
Revision
10 - 10 KW
15 - 15 KW
(NOTE 1)
Ventilation Option
B - Blank Off Plate (no ventilation)
X - Barometric Fresh Air Damper (no exhaust)
V - Commercial Ventilator (w/Exhaust)
P - Commercial Ventilator (w/Exhaust) Motorized, Power Return
R - Energy Recovery Ventilator (w/Exhaust) - 230/208-60-1 versions only
Factory Built-in Electric Heat Table
Models
KW
5.0
10.0
15.0
Electrical Specifications
SINGLE CIRCUIT
Maximum
External
Minimum
Fuse or
Circuit
Circuit
Ampacity
Breaker
1
7
15
1
33
35
1
58
60
83
90
1
10
15
1
6.5
10
X
X
X
Filter Options
X - 1" Fiberglass
(Standard)
F - 2" Fiberglass
P - 2" pleated
Color
V - Platinum w/Slate
Front (vinyl)
4 - Gray Paint
TABLE 1
QC501-A
240V-1
208V-1
BTUH
BTUH
16,380
12,290
32,670
24,570
49,150
36,860
TABLE 2
Minimum
Circuit
Field
Ampacity
Power
Ground
Wire
Wire
CKT
CKT
Size
Size
A
B
14
14
–
–
8
10
–
–
6
10
–
–
4
8
50
33
14
14
–
–
14
14
–
–
X
X
X
Valve Options
4 - 2-way valve
5 - 3-way valve
Internal Controls
X - None
Climate Control
X - None
D - Electronic/prog/man/auto
DUAL CIRCUIT
Maximum
External
Field
Fuse or
Power
Circuit
Wire
Breaker
Size
CKT
CKT
CKT
CKT
CKT
A
B
A
B
A
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
50
40
8
8
10
–
–
–
–
–
–
–
–
–
–
Ground
Wire
Size
CKT
B
–
–
–
10
–
–