INSTALLATION

Mounting the Unit

When installing a QC unit near an interior wall on the
left side, a minimum of 8" is required; 12" is preferred.
When installing a QC unit near an interior wall on the
right side, a minimum of 12" is required as additional
space is required to connect the drain.
This clearance is required to allow for the attachment
of the unit to the wall mounting brackets and the side
trim pieces to the wall.
This unit is to be secured to the wall when there is not
a vent sleeve used with the wall mounting brackets
provided. (NOTE: See Figure 5 on page 10 for wall and
sleeve bracket locations on shipping crate and for a
pictorial representation of brackets.) The unit itself, the
supply duct and the free blow plenum are suitable for
"0" clearance to combustible material.
NOTE: When a wall sleeve is to be used, attach the unit
to the sleeve with bracket supplied with the wall
sleeve. See Figure 5 for wall sleeve bracket.
Following are the steps for mounting the QC units; for
reference see Figure 15.
1. Attach wall mounting bracket to the structure
wall with field-supplied lag bolts. The fluid piping
connections are to be within the confines of
this bracket. See Figure 1 on page 6 for cabinet
openings and location of fluid coil connection
points.
2. Position the unit in front of the wall mounting
bracket.
3. Remove the locking screws from the wheels. Refer
to Figure 14.
4. Roll the unit up to the wall mounting bracket.
The unit must be level from side to side. If any
adjustments are necessary, shim up under the
rollers with sheets of steel or any substance that is
not affected by moisture.
5. Secure the unit to the wall bracket with provided
#10 hex head sheet metal screws. There are
prepunched holes in the cabinet sides and the
bracket has slotted holes to allow for some
misalignment.
6. Position the bottom trim piece to the unit and
attach with provided screws (dark colored).
7. Position side trim pieces to the wall and attach
with field-supplied screws. There are two long and
two short pieces supplied. The long pieces are to
enclose the gap behind the unit. The short pieces
are to fill the gap behind the cabinet extension or
the free blow plenum box. They may be cut to suit
Manual 2100-416L
Page
18 of 29
the ceiling height or overlap the unit side trim.
There is sufficient length to trim up to a 10'-2"
ceiling.
FIGURE 14
Removing Locking Screws from Wheels
REMOVE SCREWS
FROM WHEELS BEFORE
ROLLING INTO PLACE