Installation Guidelines

This section describes how to establish the connections with the programmable controller and the
process I/O.
2.1
24 V DC Supply
The IP 265 is a non-floating module. The 24 V DC load current circuits share the same ground with
the control circuit of the PLC.
Figure 2-1 shows the simplified connection of the IP 265 to the PLC.
Central ground
Figure 2-1. Simplified Representation for Non-Floating Connection of the IP 265 to the PLC
Note
When using the IP 265, you must connect the ground of the IP 265 load voltage con-
nector with the CPU ground via an external connection at the central grounding point.
When doing so, please make sure you use a low-resistance connecting cable (cable
should be as short as possible).
2.2

Establishing the Connection to the S5-100U Bus

The IP 265 is like an I/O module of the S5-100U system and is snapped onto a bus unit. You must
note the following points when assembling and dismantling the module:
The IP 265 may be plugged in or removed only without load voltage and when the CPU is in the
STOP state.
The memory submodule may be plugged in or removed only when the module and the CPU are
in the POWER OFF state.
The IP 265 can only be snapped onto a bus unit in slots 0 to 7 of the programmable controllers.
For instructions on assembling and dismantling the module, see the IP 265 Manual or the
System Manuals for the S5-100U, S5 90/95U or ET 200.
EWA 4NEB 812 6131-02
CPU
L+
M
L+
M
External power supply
Installation Guidelines
IP
L+
M
Connector for
load voltage
2-1