Honeywell 7800 Series Manual page 5

Relay module
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

Plug-in Flame Signal Amplifiers
Type
Color
Checking
Rectification
Green
Dynamic
(Continued)
Self-Check
Infrared
Red
No
Dynamic
AMPLI-
CHECK™
Ultraviolet
Purple No
Dynamic
AMPLI-
CHECK™
Blue
Dynamic
Self-Check
a
Order flame rod separately; see holder Instructions.
b
Use only Honeywell Photocell, part no. 38316.
c
The C7012A,C, C7027, C7035 and C7044 flame detectors should be used only on burners that cycle on-off at least once every
twenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer should use the
C7012E,F Flame Detector with the R7847C Amplifier or the C7076A Flame Detector with the R7886A Amplifier as the
ultraviolet flame detection system.
d
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the burner if the
amplifier fails.
e
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during
burner operation and shuts down the burner if the detection system fails.
SEQUENCE TIMING FOR NORMAL OPERATION:
Device
Initiate
RM7838B
10 sec.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A Purge Card is selected.
*** Immediate or deferred main flame.
ACCESSORIES:
Optional:
ControlBus 5-Wire Connector—part no. 203541.
COMBUSTION SYSTEM MANAGER™—
part no. ZM7850A1001.
Communication Interface Base Unit—
part no. Q7700A1014.
Communication Interface ControlBus™ Module—
part no. QS7800A1001.
Keyboard Display Module—part no. S7800A1001.
DATA CONTROLBUS MODULE™—
part no. S7810A1009.
Remote Reset Module—part no. S7820A1007.
Expanded Annunciator—part no. S7830A1005.
TABLE 2—FLAME DETECTION SYSTEMS (Continued)
Flame
Failure
Self-
Response
Model
Time
e
R7847C
3 sec
R7848A
3 sec
d
R7848B
3 sec
R7849A
.8 or 3 sec
d
R7849B
.8 or 3 sec
e
R7886A
3 sec
Standby
Purge
Pilot Flame Establishing
*
**
Applicable Flame Detectors
Fuel
Type
Gas, oil,
Ultraviolet
coal
(Purple Peeper)
Gas, oil,
Infrared (Lead
coal
Sulfide)
Gas, oil,
Infrared (Lead
coal
Sulfide)
Gas, oil
Ultraviolet
(Minipeeper)
Gas, oil
Ultrviolet
(Minipeeper)
Gas, oil,
Ultraviolet
coal
(Adjustable
Sensitivity)
Main Flame Establishing
Period (PFEP)
4/10
General Purpose Interface ControlBus™ Module—
part no. QS7850A1006.
Electrical Access Slot Covers—part no. 221779
Remote Display Mounting Bracket—part no. 203765.
Tester—part no. A7800A1002.
Remote Display Power Supply—part no. 203968A
Plug-in.
Sixty-inch Extension Cable Assembly—
part no. 221818A.
NEMA 4 Display Enclosure —part no. 204718A.
NEMA 4 Display Enclosure with Remote Reset
Button—part no. 204718C
Flame Simulator
—Ultraviolet—part no. 203659.
—Rectification—part no. 123514A.
5
SPECIFICATIONS
Models
C7012E,F.
C7015.
C7015.
C7027, C7035,
c
C7044.
C7027, C7035,
c
C7044.
C7076.
Run
Period (MFEP)
10 ***
*
65-0120—1