Honeywell 7800 Series Manual page 3

Relay module
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

ENVIRONMENTAL RATINGS:
Ambient Temperature:
Operating: -40° F to 140° F.
Storage: -40° F to 150° F.
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
DIMENSIONS: Refer to Figs. 1 and 2.
Plug-in Flame Signal Amplifiers
Self-
Type
Color
Checking
Rectification
Green
No
No
No
Dynamic
AMPLI-
CHECK™
Dynamic
AMPLI-
CHECK™
Dynamic
AMPLI-
CHECK™
Dynamic
Self-Check
Infrared
Red
No
Dynamic
AMPLI-
CHECK™
Ultraviolet
Purple
No
Dynamic
AMPLI-
CHECK™
Blue
Dynamic
Self-Check
a
The C7012A,C, C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once
every twenty-four hours. Appliances with burners that remain on continuously for twenty-four hours or longer should
use the C7012E,F Flame Detector with the R7847C Amplifier or the C7076A,D Flame Detector with the R7886A
Amplifier as the ultraviolet flame detection system.
b
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during
burner operation and shuts down the burner if the detection system fails.
c
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the burner if
the amplifier fails.
d
Order flame rod separately; see holder Instructions.
e
Use only Honeywell Photocell, part no. 38316.
WEIGHT: RM7823A with Dust Cover: 1 pound 13 ounces,
IMPORTANT: Flame Detection System available for use
TABLE 2—FLAME DETECTION SYSTEMS .
Flame
Failure
Response
Model
Time
R7847A
.8 or 3 sec
R7847A
.8 or 3 sec
R7847A
3 sec
c
R7847B
.8 or 3 sec
c
R7847B
.8 or 3 sec
c
R7847B
3 sec
b
R7847C
3 sec
R7848A
3 sec
c
R7848B
3 sec
R7849A
.8 or 3 sec
c
R7849B
.8 or 3 sec
b
R7886A
3 sec
3
unpacked.
with RM7823A. To select your Plug-in Flame Signal
Amplifier and applicable Flame Detector, see Table 2 and
Figs. 3-5.
Applicable Flame Detectors
Fuel
Type
Gas
Rectifying
Flame Rod
d
Holders
Oil
Rectifying
Photocell
Gas, oil,
Ultraviolet
coal
(Purple Peeper)
Gas
Rectifying
Flame Rod
d
Holders
Oil
Rectifying
e
Photocell
Gas, oil,
Ultraviolet
coal
(Purple Peeper)
Gas, oil,
Ultraviolet
coal
(Purple Peeper)
Gas, oil,
Infrared
coal
(Lead Sulfide)
Gas, oil
Infrared
coal
(Lead Sulfide)
Gas, oil
Ultraviolet
(Minipeeper)
Gas, oil
Ultrviolet
(Minipeeper)
Gas, oil,
Ultraviolet
coal
(Adjustable
Sensitivity)
RM7823A
SPECIFICATIONS
Models
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
C7003, C7010,
C7013, C7014.
a
C7012A,C.
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
C7003, C7010,
C7013, C7014.
a
C7012A,C.
C7012E,F.
C7015.
C7015.
a
C7027, C7035, C7044.
a
C7027, C7035, C7044.
C7076.
65-0106—2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rm7823a

Table of Contents