c. Enclose scanner wires without armor cable in
metal cable or conduit.
d. Follow directions given in the flame detector
Instructions.
7. Maximum wire lengths:
a. For the RM7823A, the maximum length of
leadwire to the terminal inputs is 300 feet.
b. For the Flame Detector leadwires, the maximum
flame sensor leadwire length is limited by the
flame signal strength.
8. Make sure loads do not exceed the terminal ratings.
Refer to the label on the RM7823A or to the ratings in the
Specifications, see Table 1.
Fig. 7—Wiring the RM7823A
WHITE
YELLOW
1
120V, 60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
3
OUTPUTS SHOWN ARE WHEN THE DEVICE DOES NOT SEE FLAME.
G
L2
3
4
5
6
7
3
COMMON
8
NORMALLY
9
OPEN
NORMALLY
10
CLOSED
F
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL,
OR INFRARED
(LEAD SULFIDE)
FLAME DETECTOR
OR
C7027A, C7035A, OR
BLUE
C7044A ULTRAVIOLET
FLAME DETECTOR
OR
C7012A,C,E,F OR
BLUE
C7076A ULTRAVIOLET
FLAME DETECTOR
WHITE
WHITE
BLACK
BLACK
9. Check the power supply circuit. The voltage and
frequency tolerance must match those of the RM7823A. Do
not connect the RM7823A to a power supply circuit that can
have line voltage variations like on-off switching of heavy
loads. A separate power supply circuit may be required for the
RM7823A with the required disconnect means and overload
protection added.
10. Check all wiring circuits and complete the Static
Checkout, see Table 4, before installing the RM7823A on
the subbase.
11. Install all electrical connectors.
12. Restore power to the panel.
Q7800
12
3
13
COMMON
NORMALLY
(L1)
14
CLOSED
NORMALLY
15
OPEN
16
17
2
18
19
20
21
22
L1
(HOT)
L2
MASTER
SWITCH
L2
L1
L2
11
RM7823A
INSTALLATION
1
M5153
65-0106—2