Mitsubishi Electric thermoscreens HX2-S/M 1000 DXE Installation, Operation & Maintenance Instructions Manual page 29

Heat pump range air curtains
Table of Contents

Advertisement

Air Curtain
Discharge Air
Target Temp. (°C)
In case of difficulty refer to the Mitsubishi Electric instruction booklet that comes with the PAR-W21MAA
Remote Controller, Section 7 – Initial Setting, Page 22.
Check the operation of the air curtain in Weather Compensation Control (HEATING
ECO mode). The smaller number in the middle of the screen shows the actual
discharge air temperature and the larger number at the left of the screen indicates the
discharge air 'target temperature' as calculated against the outdoor air temperature by
the heating curve above (see User Instructions).
Now set the Function Limit in the PAR-W21MAA Remote Controller to skip the Hot
Water mode and Anti-freeze mode (refer to Figure 3):
1. Press button
2. Hold down button
'CHANGE LANGUAGE'
3. Press button
4. Press button
5. Press button
6. Press button
7. Press button
8. Press button
9. Press button
10. Press button
11. Press button
12. Hold down button
instruction is written to the PAR-W21MAA Remote Controller
NB. It is also possible to skip HEATING mode (Discharge Air Temperature Control)
using the above key strokes so only the more energy efficient Weather
Compensation Control (HEATING ECO mode) can be selected.
In case of difficulty refer to the Mitsubishi Electric instruction booklet that comes with the PAR-W21MAA
Remote Controller, Section 6 – Operation mode skip setting, Page 19 & 20.
T9901105-1-1 UK
2
Heated Air Curtain
40
30
4
20
1
-5
0
to switch air curtain OFF
I
and button
E
, screen will say 'FUNCTION SELECTION'
E
, screen will say 'LOCKING FUNCTION'
G
again, screen will say 'SELECT HEATING'
G
, screen will say 'SELECT HEATING ECO'
D
again, screen will say 'SELECT HOT WATER'
D
to change on to oFF on the screen
J
, screen will say 'SELECT ANTI-FREEZE'
D
to change on to oFF on the screen
J
, screen will say 'MODE SELECTION' – flashing!
E
and button
E
Weather Compensation Control
5
10
Outdoor Air Temperature (°C)
together for 2 seconds, screen will say
D
together for 2 seconds and this
D
Figure 4
(HEATING ECO mode)
typical heating curve
Ambient Air Curtain
3
15
20
Page 29 of 42

Advertisement

Table of Contents
loading

Table of Contents