Hydraulic Series Troubleshooting Guide
Start•All Hydraulic Series
Troubleshooting Guide
Rev 11122019

Advertisement

Table of Contents
loading

Summary of Contents for Vanair Goodall START-ALL Hydraulic Series

  • Page 1 START•ALL ® Hydraulic Series Troubleshooting Guide Start•All Hydraulic Series Troubleshooting Guide Rev 11122019...
  • Page 2: Table Of Contents

    TESTING THE VOLTAGE CONTROL ............6 FIXING REVERSE POLARITY GENERATORS ........7 12/24 VOLT RED LABEL VOLTAGE CONTROL TEST ......8 RED LABEL ENERGIZE BUTTON TEST ..........8 MAINTENANCE LOG ................9 CONTACT INFORMATION ..............10 VANAIR.COM • 800-526-8817 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...
  • Page 3: Safety Precautions & Instructions

    Battery acid may cause blindness and burn skin. WARNING Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm. VANAIR.COM • 800-526-881 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...
  • Page 4 Since there are many variations in the circumstances surrounding the installation, operation, and maintenance of this unit, we cannot possibly anticipate or provide advice or safety messages to cover every situation. VANAIR.COM • 800-526-8817 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...
  • Page 5: General Inspection

    DO NOT HOOK UP THE VOLTAGE CONTROL WIRES AT THIS TIME. FIELD POST ARMATURE POST FIELD POST ARMATURE POST GROUND POST FIG. 2 FIG. 1 GROUND VANAIR.COM • 800-526-881 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...
  • Page 6: Testing The Solenoids

    FIG. 4 TESTING THE 850-597 VOLTAGE CONTROL IF YOUR UNIT HAS THE TWO WIRE 70-600-K VOLTAGE CONTROL, YOU WILL NEED TO CALL VANAIR MFG AT 844-526-8817 FOR AN UPGRADE KIT. ® 1. Confirm the fuse on the orange wire is not open. If open, replace with a 30 amp fuse (FIG. 5). If the fuse is not open, proceed to the next step.
  • Page 7: Fixing Reverse Polarity Generators

    4. Once you have done this a few times, you will have reversed the polarity back to positive in all of the generators, as long as the wires have been hooked back up correctly. VANAIR.COM • 800-526-881 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE...
  • Page 8: 12/24 Volt Red Label Voltage Control Test

    If YES - Voltage coming from the engine battery is good. b. If NO - Ensure that engine starting battery is good and fully charged. Repair/replace wire from battery if necessary. VANAIR.COM • 800-526-8817 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE...
  • Page 9: Maintenance Log

    MAINTENANCE LOG VANAIR.COM • 800-526-881 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...
  • Page 10: Contact Information

    When calling for technical support, it is important to provide the serial number of the Start•All unit. ® The serial number will be a white tag with black type located on the front panel on the Start•All ® VANAIR.COM • 800-526-8817 START•ALL HYDRAULIC SERIES TROUBLESHOOTING GUIDE ®...