Lutron Electronics EcoSystem Energi Savr Node Installation Manual
Lutron Electronics EcoSystem Energi Savr Node Installation Manual

Lutron Electronics EcoSystem Energi Savr Node Installation Manual

Advertisement

Quick Links

EcoSystem
Energi Savr Node
®
Please read this guide before installing.
Contents
Ratings and Model number overview ....................................1
Product overview..................................................................2
Wiring overview....................................................................2
Mounting ..............................................................................3
Control power wiring ............................................................3
EcoSystem Link wiring .........................................................4
Input group wiring ................................................................5
Contact closure inputs ..........................................................6
QS link wiring .......................................................................7
Applications .........................................................................9
Out of box functionality .........................................................9
System Programming Connection .......................................10
Troubleshooting ..................................................................11
Warranty ............................................................................12
Contact information ............................................................12
System Example
EcoSystem
Digital Links
(up to 64 ballasts each)
Control Power
120-277 V
Emergency
Contact
Contact
Closure
Closure
Input
Input
EcoSystem
Energi Savr Node
®
TM
Page
Wired
Daylight
Sensors
(up to 4)
1,2
QS link
seeTouch
QS Wallstation
®
Wired Daylight
Sensors (up to 4)
2
Wired Occupancy
Sensors (up to 4)
Wired EcoSystem
Wallstation or
IR receivers
(up to 4)
Installation Guide
TM
|
Installation Guide
Control Panel Ratings
Control Power: 120-277 V
Output:
18 V
Operating environment: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
Maximum humidity: 90% non-condensing
Thermal dissipation: 40 BTU/hr
Input Groups: 20 V
QS link: 24 V
1 A 30 PDU (Power Draw Units)
Model number overview
QSN-1ECO-S EcoSystem Energi Savr Node
QSN-2ECO-S EcoSystem Energi Savr Node
QSN: Energi Savr Node
1:
1 EcoSystem Digital Link
2:
2 EcoSystem Digital Links
ECO: EcoSystem
S:
Surface mount
Wired
Wired
Occupancy
Wallstation
Sensors
or IR Receivers
(up to 4)
1
(up to 4)
1
Radio Powr Savr
Occupancy
Sensor (up to 10
per QSM)
Wireless
Communication
QSM (new!)
Notes:
1 Up to 4 wired inputs total (of any type).
2 Up to 16 wired daylight sensors total
IR Transmitter
per EcoSystem link.
50/60 Hz 0.5 A
250 mA per EcoSystem link
65 mA per group
IR Transmitter
Pico
Wireless
TM
®
Controller
(up to 10 per
QSM)
Radio Powr Savr
Daylight Sensor
(up to 10 per QSM)
Lutron
1
|
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EcoSystem Energi Savr Node and is the answer not in the manual?

Questions and answers

Summary of Contents for Lutron Electronics EcoSystem Energi Savr Node

  • Page 1: Table Of Contents

    1 A 30 PDU (Power Draw Units) EcoSystem Link wiring ............4 Model number overview Input group wiring ..............5 QSN-1ECO-S EcoSystem Energi Savr Node Contact closure inputs ............6 QSN-2ECO-S EcoSystem Energi Savr Node QS link wiring ...............7 QSN: Energi Savr Node 1 EcoSystem Digital Link Applications .................9...
  • Page 2: Product Overview

    – 1 emergency contact closure input (defaults to Emergency Mode in the absence of a contact closure across the input) • The QS Link can have up to 100 zones, 100 areas, and 100 QS devices. • The EcoSystem Energi Savr Node unit counts as 1 QS device and 1-100 zones on the QS link (depending on system programming). • In a system, a maximum of 100 wired or wireless daylight sensors, 100 wired or wireless occupancy sensors, and 100 wired or wireless controllers (Pico wireless controllers, EcoSystem wallstations, IR receivers, or QS wallstations).
  • Page 3: Mounting

    Step 1: Mounting the EcoSystem Energi Savr 9.25 (234.95) Node Unit 1.31 1.66 (33.27) (42.16) Note: Mount the EcoSystem Energi Savr Node unit in a posi- 1.22 (30.99) tion where it can be easily located and accessed if service or 3.16 (80.26) troubleshooting is necessary. 1.62 (41.15)
  • Page 4: Ecosystem Link Wiring

    LED lights green when powered up. 6. The ECO1 and ECO2 LEDs should flash green. See LED Behavior tables on page 11 for more details. 7. The EcoSystem Energi Savr Node unit outputs EcoSystem- compliant voltage levels (18 V ). Use a voltage meter to confirm this voltage.
  • Page 5: Input Group Wiring

    Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must be accessed by a certified electrician, following local codes. Note: The EcoSystem Energi Savr Node unit accepts only one IR input (either daylight/IR sensor, IR receiver, or EcoSystem wallsta- tion) per group.
  • Page 6: Contact Closure Inputs

    (100% by default) and disable control from inputs and QS devices. When the closure is restored, ballasts and/or drivers will return to their previous level. Note: The EcoSystem Energi Savr Node unit will default to GROUP 1 GROUP 2 GROUP 3...
  • Page 7: Qs Link Wiring

    See diagram on the right for QS link wiring. wires. Two 12 AWG (4.0 mm ) conductors will not fit. Connect as 1. Connect terminals 1, 3 and 4 to all EcoSystem Energi Savr Node shown below using appropriate wire connectors. units.
  • Page 8 EcoSystem Energi Savr Node Installation Guide ® QS Link Wiring (continued) Daisy-chain Wiring Example EcoSystem Energi Savr Node unit seeTouch QS Wallstations ® QS Control Link Sivoia ® Smart Power Sivoia QS Panel Shade T-tap Wiring Example seeTouch QS Wallstations EcoSystem Energi Savr Node unit...
  • Page 9: Applications

    IR Receiver Connected to Controls link 1 only Controls link 1 only • Emergency contact closure input is normally closed (NC). The input group 1 EcoSystem Energi Savr Node unit is shipped with a jumper pre- Connected to Controls link 2 only Controls link 2 only installed. input group 2 • If the Emergency input is open, the EcoSystem Energi Savr...
  • Page 10: System Programming Connection

    • Lutron recommends that an EcoSystem Energi Savr Node unit be wired to an Ethernet jack in the space for ease of access and prox- imity to power for the wireless router. • Works with any standard wireless router available. • Apple iPod touch or iPhone can program other Energi Savr Node units connected to an EcoSystem Energi Savr Node unit via the QS Link (except when part of a Quantum system).
  • Page 11: Troubleshooting

    EcoSystem Energi Savr Node Installation Guide ® Using LEDs to troubleshoot WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power to all power feeds via circuit breaker or isolator before wiring or servicing the EcoSystem Energi Savr Node unit.
  • Page 12: Warranty

    Lutron, EcoSystem, Pico, seeTouch, and Sivoia are registered trademarks and Energi Savr Node and TEL +44.(0)20.7702.0657 Hong Kong: 800.901.849 Radio Powr Savr are trademarks of Lutron Electronics Co., Inc. FAX +44.(0)20.7480.6899 Singapore: 800.120.4491 NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.