Tone Table
Part Number
Primary Tone
45681-705
Apollo Evacuation Tone
XPERT Card Addressing
Select the desired address and remove the pips indicated in black. Remove pips with a small screwdriver.
© Copyright Apollo Fire Detectors Limited 2013
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo- re.co.uk Website: www.apollo- re.co.uk
www.acornfiresecurity.com
Secondary Tone
567Hz for 0.5s, 850Hz for 0.5s
Apollo Alert Tone
1s off, 1s 850Hz
5
www.acornfiresecurity.com
39214-788/Issue 4
General
This guide describes the installation of the following base variants
Part number
Product Description
45681-705
XP95 Sounder VAD Base (White) with Isolator
45681-709
XP95 VAD Base (White) with Isolator
45681-292
White Cap only (Lockable)
45681-293
Red Cap only (Lockable)
Connect the devices only to control panels using the XP95 protocol.
The XP95 Sounder VAD Bases combine a sounder with a visual alarm and a detector base in one unit.
The VAD is activated whenever the sounder is active and cannot be controlled separately.
All XP95 Sounder VAD Base variants with short circuit isolator have a yellow LED which illuminates through
the moulding if a short circuit is detected on the loop wiring (see Fig 1).
Note: All XP95 Sounder VAD Base variants are not suitable for outdoor use.
Mounting Instructions
All base variants may be secured to a UK standard conduit box or surface mounted (providing there is
access through the surface for cabling). If a detector is tted, lock it if required by screwing in the grub
screw in the detector with a 1.5mm hex driver (part no 29600-095).
The XP95 Sounder VAD Bases are ceiling mounted devices. For coverage volume information please refer
to PP2478.
Wiring Details
Note: These products are polarity sensitive (supply reversal protected) and will not function if wired
incorrectly.
Terminate all loop cables in the two way terminal blocks. Connect the incoming loop cables to L1 IN (–)
and L2 (+) and the outgoing cables to L1 OUT (–) and L2 (+). Functional earth or screen may be connected
to the EARTH connection. The isolator LED can be seen through the moulding as shown in Fig 1.
DO NOT CONNECT LOOP CABLES TO THE OUTER TERMINALS OF ISOLATED MODELS.
When using as a stand-alone unit, a cap is available (red cap part no 45681-293 or white cap part no 45681-
292) and is secured with a 1.5mm, AF hexagon socket head screw. A hexagonal driver (part no 29600-095)
is available from Apollo.
Technical Data
Operating Voltage
Sounder Output
High Tone Setting Volume
(Complies to EN54-3)
Low Tone Setting Volume*
Sound pressure level information published in document PP2203 and isolator operation information
published in document PP2090, both available on request.
Current Consumption at 24V DC
Quiescent
Switch on Surge
Sounder/VAD Operating
VAD Frequency
IP Rating
*Low tone setting does not comply to EN54–3 and should not be used for re alarm applications
XP95 Sounder VAD Bases
Installation Guide
17—28V DC
nominally 75dB(A) to 91dB(A)
nominally 55dB(A) to 75dB(A)
1.2mA for 1 sec
1
Category
O
O
N/A
N/A
350µA
14mA
0.5Hz
IP21C

Advertisement

loading

Summary of Contents for Apollo 45681-705

  • Page 1 14mA © Copyright Apollo Fire Detectors Limited 2013 VAD Frequency 0.5Hz Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK IP Rating IP21C Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754 *Low tone setting does not comply to EN54–3 and should not be used for re alarm applications Email: techsales@apollo- re.co.uk Website: www.apollo- re.co.uk...
  • Page 2 www.acornfiresecurity.com Commissioning It is important that the base variants be fully tested after installation. An XP95 Test Set, part no 55000-870, may be used to carry out functional testing of individual units. The test set can also perform data integrity tests of an entire system.
  • Page 3 Coverage radius of a single VAD = 2.50m Centre dark spot radious of a single VAD = 0.97m Depth of section from the ceiling = 2.40m Centre to centre spacing of VADs + 1.53m For alternative mounting heights, please contact Apollo Fire Detectors Limited www.acornfiresecurity.com...