Technical Data; Basic Function Principles - Beckhoff KL3224 Documentation

Table of Contents

Advertisement

2.2

Technical data

Technical data
Number of inputs
Power supply
Sensor types
Connection technology
Temperature range
Resolution
Electrical isolation
Conversion time
Measuring current
Measuring error (total meas.
range)
Bit width in process image
Current consumption via K-bus
Configuration
Special features
Weight
Permissible ambient temperature
during operation
Permissible ambient temperature
during storage
Permissible relative humidity
Vibration / shock resistance
EMC immunity / emission
Installation position
Protection class
Approval / identification
2.3

Basic function principles

Process data output format
In the delivery state, the measured value is displayed in increments of 1/10 °C in two's complement format
(integer). The complete measuring range is output for each resistance sensor. Other presentation types can
be selected via the feature register (e.g., signed amount representation, Siemens output format).
Measured value
Hexadecimal output
-250.0 °C
0xF63C
-200.0 °C
0xF830
-100.0 °C
0xFC18
-0.1 °C
0xFFFF
0.0 °C
0x0000
0.1 °C
0x0001
100.0 °C
0x03E8
200.0 °C
0x07D0
500.0 °C
0x1388
850.0 °C
0x2134
KL3224
KL3224
4
via the K-bus
PT1000, Ni1000
2-wire
0 °C ... +40 °C
0.1 °C per digit
500 V (K-bus / signal voltage)
approx. 250 ms
typically 0.5 mA.
< ± 1 °C (at 0 °C ... +55 °C)
Input: 4 x 16 bits of data (4 x 8 bit control/status optional)
typically 60 mA
no address setting, configuration via bus coupler or controller
Open-circuit recognition
approx. 70 g
0 °C ... +55 °C
-25 °C ... +85 °C
95% no condensation
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
variable
IP20
CE
Version: 2.0.0
Signed integer output
-2500
-2000
-1000
-1
0
1
1000
2000
5000
8500
Product overview
11