Motor Protector Module; Current Overload; Thermal Overload; Current Unbalance / Loss Of Phase - York YCRS Series Installation, Operation And Maintenance Manual

Water cooled remote condenser 81 tons through 194 tons (285 kw through 682 kw)
Table of Contents

Advertisement

module, mounted in the power panel, utilizes a 7 seg-
ment display which provides operating status and fault
diagnostic information. The 7 segment display will dis-
play either a stationary or a flashing alphanumeric value
which can be decoded by the operator:
TABLE 1 – MOTOR PROTECTOR FAULTS
0
NORMAL - NO FAULT DETECTED
FLASHING "0" MOTOR OFF OR UNLOADED < 5A AC
CURRENT LEVEL
1
HIGH CURRENT FAULT
2
LOADED PHASE TO PHASE CURRENT
IMBALANCE > 17%
3
UNLOADED PHASE TO PHASE
CURRENT IMBALANCE > 25%
4
IMPROPER INCOMING PHASE
ROTATION
5
HIGH MOTOR TEMPERATURE
TRIP POINT = 13 KOHM RESET =
3.25 KOHM
6
COMMUNICATION ERROR
E
OUT OF RANGE OF RLA CALIBRATION
OTHER
DEFECTIVE MODULE OR SUPPLY
SYMBOLS
VOLTAGE
Whenever a motor protector trips, the motor protector
contacts wired in series with the motor contacts, open
and the motor contactor de-energizes allowing the mo-
tor to stop. The microprocessor senses the low motor
current and shuts the system down. The microproces-
sor will try two more starts before locking the system
out. The system locks out because the motor protector
is a manual reset device. After the first start the protec-
tor contacts will be open, thus preventing the motor
contactors from energizing. Power must be removed
and re-applied to reset the module.

Current Overload

The protector module uses integral current transform-
ers per phase to provide protection against rapid cur-
rent overload conditions. The module responds to
changes in current and must be set-up using the DIP
switches located on the module (refer to Section 5 for
details). Integral trip curves allow for in-rush currents
during Star/Delta starting without nuisance tripping.

Thermal Overload

Three PTC (positive temperature coefficient) ther-
mistors in the motor windings of each phase provide
YORK INTERNATIONAL
thermal protection. The sensor resistance stays rela-
tively constant at 1 kW until a temperature of 266°F
(130°C) is sensed. The sensor experiences a rapid rise
in resistance beyond this temperature. Whenever the
resistance of one of the sensors reaches 13 kW, the mod-
ule trips, which ultimately de-energizes the motor's
pilot circuit. Reset is manual after the motor cools and
the sensor resistance drops to 3.25 kW.
Current Unbalance (Loaded & Unloaded)
Loss of Phase
A 2 second delay at start-up allows for any unbalances
resulting during normal starting conditions. After this
initial delay, the protector module compares the "Op-
erating Current" to the measured half line current. The
"Operating Current" is given by 0.65 x factory over-
load current setting.
An unloaded compressor condition occurs when any
measured half line current is less than the "Operating
Current." A current unbalance exceeding an unloaded
level of 25% will result in the motor pilot circuit being
de-energized.
A loaded compressor condition occurs when any mea-
sured half line current is greater than or equal to the
"Operating Current." A current unbalance exceeding a
loaded level of 17% will result in the motor pilot cir-
cuit being de-energized.

Improper Phase Sequence

The protector module calculates the phase sequence at
start-up using the three current transducers to deter-
mine whether the three phase sequence on the load side
of the main contactor is miswired. Upon detection of a
miswired motor load, the module will de-energize the
main contactor pilot circuit within 50 millisecond re-
sponse time.

KEYPAD CONTROLS

For a detailed description of the keypad controls refer
to the Microprocessor Based Control System Operat-
ing Section 7.

Status Key

This key provides a display of the current operational
and/or fault status of the unit or the individual refriger-
FORM 201.25-NM1 (302)
2
13

Advertisement

Table of Contents
loading

Table of Contents